Replace fan motor.
Rotate shaft of the fan motor by hands
during power-OFF, Can it rotate smoothly?
Is coil resistance of fan motor correct?
Between red and white lead wire :12 to 20
Ω
.
Between white and black lead wire :12 to 20
Ω
.
Between black and red lead wire :12 to 20
Ω
.
YES
NO
YES
NO
YES
NO
YES
NO
NO
NO
YES
NO
Correct connector.
Sensor error
→
Replace.
Check outdoor P.C.B MCC-5071
Defect
→
Replace.
Correct connector.
Sensor error
→
Replace.
Check outdoor P.C.B MCC-5071
Defect
→
Replace.
Is AC mains voltage correct?
(198 to 264V)
Is connection of CN603
on P.C.B MCC-5071 correct?
Is resistance value of TS sensor correct?
Is connection of CN601
on P.C.B MCC-5071 correct?
Is resistance value of TE sensor correct?
Correct connector.
Sensor error
→
Replace.
Check outdoor P.C.B MCC-5071
Defect
→
Replace.
Check wiring construction.
Ask repair of power supply.
Check outdoor P.C.B MCC-1571
Defect
→
Replace.
Is connection of CN600
on P.C.B MCC-5071 correct?
Is resistance value of TD sensor correct?
Correct connector.
Sensor error
→
Replace.
Check outdoor P.C.B MCC-5071
Defect
→
Replace.
Is connection of CN602
on P.C.B MCC-5071 correct?
Is resistance value of TO sensor correct?
Check
code
[18]
Outdoor
LED display
zzz
{{
z
Check and troubleshooting
(Item without special mention indicates part of outdoor unit.)
∗
There is a possibility that it is one of the following errors.
Confirm LED on outdoor P.C. board to judge which error it is.
Heat exchanger temp. sensor (TE) error, Suction temp. sensor (TS) error
[Suction temp. sensor (TS) error]
[Heat exchanger temp. sensor (TE) error]
[Discharge temp. sensor (TD) error]
[Fan system error]
[Outside temp. sensor (TO) error]
[1A]
[1B]
[19]
z
{
z
{{
z
zz
{{
zz
z
{{{
zz
zzzz
{
z
FILE NO. SVM-15036
- 82 -
Summary of Contents for RAS-5M34S3AV-A
Page 112: ......