Is AC mains voltage correct?
(198 to 264V)
Is wire connection correct?
Compressor lead
(Board side, Compressor Side),
Reactor lead, Power supply lead.
Check wiring construction.
Ask repair of power supply.
Check wire connection
and correct it.
Check outdoor P.C.B MCC-5071.
Defect
→
Replace.
Are connections of CN802 on P.C.B MCC-5071
and CN802 on P.C.B MCC-1571 correct?
Are connections of CN804 on P.C.B MCC-5071
and CN800 on P.C.B MCC-1571 correct?
Correct connection.
Check outdoor P.C. Boards.
Defect
→
Replace.
Correct connection.
Check outdoor P.C. Boards.
Defect
→
Replace.
Is compressor under correct condition?
Check outdoor P.C.B MCC-1571.
Defect
→
Replace.
Is there refrigerant stagnation?
Compressor lock
→
Replace.
Does PMV correctly operate?
Check TE, TS sensors and PMV.
Detect
→
Replace.
Is PMV under correct conditions?
Is connection of CN600 on P.C.B. MCC-5071?
Is resistance value of TD sensor correct?
Is there gas leak?
Is there refrigerant shortage?
Repair defective position.
Recharge refrigerant.
Correct connector.
Sensor error
→
Replace.
Check outdoor P.C.B MCC-5071.
Defect
→
Replace.
Repair defective position.
Replace defective part.
Does an abnormal overload happen?
Remove and improve
the cause of overload.
NO
YES
YES
NO
NO
NO
YES
YES
NO
YES
YES
YES
NO
NO
YES
NO
NO
YES
YES
YES
NO
NO
Check
code
[1C]
(Continued)
[1D]
[1E]
Outdoor
LED display
z
{{
z
{{
z
{
z
{{{
zz
{{{{
z
{
zz
{
z
zz
{
z
{
z
Check and troubleshooting
(Item without special mention indicates part of outdoor unit.)
[Communication error between MCUs]
[Communication error between MCUs]
[Compressor lock]
[Discharge temp. error]
FILE NO. SVM-15036
- 85 -