– 104 –
D502, D511, D517, D524, D531 (Orange LED)
: Serial signal (Indoor
→
Outdoor)
D501, D508, D515, D520, D527 (Green LED)
: Serial signal (Outdoor
→
Indoor)
D800 (Green LED)
D801 (Red LED)
D802 (Red LED)
D803 (Red LED)
D804 (Red LED)
D805 (Red LED)
: Error display / various display
SW800,SW801,SW802
: Specific operation switch /
Selection of various initial settings
Service Support Function (LED Display, Switch Operation)
1. Outline
A various setup and operation check can be performed by DIP switches at 2 positions (SW801, SW802)
and the pushdown button switches (SW800) on the outdoor control P.C. board MCC-5071.
Operation part
Display part
Every LED is colorless when it goes off.
Control P.C.B MCC-5071
Part No.
SW800
SW801
SW802
Specifications
Pushdown button switch
DIP switch
DIP switch
Operation contents
Performs the specific operation to check maintenance and various initial settings.
Part No.
D502, D511, D517, D524, D531
D501, D508, D515, D520, D527
D800
D801 to D805
Specifications
Orange LED
Green LED
Green LED
Red LED
Operation contents
Indoor/Outdoor communication (Serial communication) signal display
(Receive signal from indoor signal)
Indoor/Outdoor communication (Serial communication) signal display
(Send signal from outdoor signal)
(1) Power-ON display
When the power of the outdoor unit is turned on, D800 LED goes on.
(2) Error display
When the outdoor controller detects some errors, some LEDs go on
or flash according to the error as described in Error display table.
(Refer to 11-6)
(3) Specific operation display
When SW800 is pushed and a specific operation is operated, some
LEDs go on or flash.