– 109 –
Correct and replace piping.
Correct connector.
Sensor error
→
Replace.
Check outdoor P.C.B. MCC-5071.
Defect
→
Replace.
Repair defective position.
Recharge refrigerant.
Correct defective position.
Replace defective part.
Check outdoor P.C.B. MCC-5071.
Defect
→
Replace
Correct connector.
Sensor error
→
Replace.
Is there crushed pipe?
Is there gas leak?
Is there refrigerant shortage?
Check temp. sensor.
TS, TE, TG, TC
Is connection of CN604
on P.C.B MCC-5071 correct?
Is resistance value of TGa sensor correct?
Is connection of CN605
on P.C.B MCC-5071 correct?
Is resistance value of TGb sensor correct?
Is connection of CN606
on P.C.B MCC-5071 correct?
Is resistance value of TGc sensor correct?
Is connection of CN607
on P.C.B MCC-5071 correct?
Is resistance value of TGd sensor correct?
Is connection of CN608
on P.C.B MCC-5071 correct?
Is resistance value of TGe sensor correct?
Open service valve fully.
Is service valve fully opened?
Is PMV under correct conditions?
Correct connector.
Sensor error
→
Replace.
Check outdoor P.C.B. MCC-5071.
Defect
→
Replace.
Correct connector.
Sensor error
→
Replace.
Check outdoor P.C.B. MCC-5071.
Defect
→
Replace.
Correct connector.
Sensor error
→
Replace.
Check outdoor P.C.B. MCC-5071.
Defect
→
Replace.
Correct connector.
Sensor error
→
Replace.
Check outdoor P.C.B. MCC-5071.
Defect
→
Replace.
NO
YES
YES
NO
YES
NO
NO
YES
OK
Error
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
Check
code
[1C]
(Continued)
Outdoor
LED display
l
¡¡¡¡
l
l
¡
lll
¡
l
¡¡
ll
¡
lllll
¡
lll
¡
l
¡
l
¡¡¡
l
¡
Check and troubleshooting
(Item without special mention indicates part of outdoor unit.)
[A room gas side temp. sensor (TGa) error]
[B room gas side temp. sensor (TGb) error]
[C room gas side temp. sensor (TGc) error]
[D room gas side temp. sensor (TGd) error]
[E room gas side temp. sensor (TGe) error]
[Gas leak detection, PMV error]