– 111 –
Repair defective position.
Replace defective part.
Correct connector.
Sensor error
→
Replace.
Check outdoor P.C.B. MCC-5071
and indoor C room P.C. board.
Defect
→
Replace.
Is PMV under correct conditions?
Check temp. sensor of C room indoor unit?
TA sensor, TC sensor
Does an abnormal overload happen?
Is AC mains voltage correct?
(198 to 264V)
Is wire connection correct?
Compressor lead
(Board side, Compressor Side),
Reactor lead, Power supply lead.
Check wiring construction.
Ask repair of power supply.
Check wire connection
and correct it.
Remove and improve
the cause of overload.
Check outdoor P.C.B MCC-1571.
Defect
→
Replace.
YES
NO
OK
Error
Repair defective position.
Replace defective part.
Correct connector.
Sensor error
→
Replace.
Check outdoor P.C.B. MCC-5071
and indoor B room P.C. board.
Defect
→
Replace.
Is PMV under correct conditions?
Check temp. sensor of B room indoor unit?
TA sensor, TC sensor
YES
NO
OK
Error
Repair defective position.
Replace defective part.
Correct connector.
Sensor error
→
Replace.
Check outdoor P.C.B. MCC-5071
and indoor A room P.C. board.
Defect
→
Replace.
Is PMV under correct conditions?
Check temp. sensor of A room indoor unit?
TA sensor, TC sensor
YES
NO
OK
Error
YES
YES
YES
NO
NO
NO
Check
code
[1F]
Outdoor
LED display
l
¡¡
l
¡
l
Check and troubleshooting
(Item without special mention indicates part of outdoor unit.)
[Compressor break down]
[20]
¥¡
llll
¥
l
¡
lll
¥
ll
¡
ll
There is a possibility that it is one of the following errors.
Confirm LED on outdoor P.C. board to judge which error it is.
PMV error for A room, B room, C room, D room, E room.
[PMV error for A room]
[PMV error for B room]
[PMV error for C room]