– 34 –
4. CONSTRUCTION VIEWS
4-1. Indoor Unit
RAS-M10PKVP-E, RAS-M13PKVP-E, RAS-M16PKVP-E, RAS-M18PKVP-E
Stud bolt hole
For dia.8 to dia.10
53(dia.80)
45.5(dia.65)
330
330
dia.65
53(dia.80)
45.5(dia.65)
790
Shape line
installation plate
590
450
312
46
100
12
100
dia.80
Center line
of main unit
Center line of
installation plate
Lower part
hanging section
Lower part
hanging section
Minimum
distance to
wall
130 or more
Minimum
distance to
ceiling
55 or more
Hanging
section
dia.80
dia.65
Stud bolt hole
For dia.8 to 10
Recommend
180 or more
Minimum
distance to
wall
130 or more
Recommend
180 or more
Recommend 70 or more
(Drain hose detail)
dia.28
dia.16
dia.14
Inner
diameter
Outer
diameter
Heat insulation
19
19
Wireless remote controller
163
58
Remote controller holder
4.5
74.5
64
34
dia.4.2
125.5
Refrigerant pipe
connecting port Liquid side
Flare dia. 6.35
Outside length 0.4m
Refrigerant pipe
connecting port Gas side
Flare dia. 9.52
(16,18PKVP-E: dia. 12.7)
Outside length 0.35m
Drain hose VP16
Outside length 0.54mm
312
Installation plate
hanging section
Installation plate
hanging section
37
Name Plate
18
77
62
77
Guard wire
100
From wall to air outlet length
8
62
77
Front panel
790
Plasma ion charger
Air filter
295
8
77
62
Piping port from
left/right sides
(Knockout system)
242
(Knockout system)
Piping port from
left/right sides
(At the time of a stop)
9
296.2
Moving panel
(At the time of operation)
790