background image

– 

97

 –

No.

‚

Part name

Front cabinet

Procedure

1. Detachment

1) Perform step 1 in 



.

2) Remove the fixing screws (ST1TØ4 × 10L

2 pcs.) used to secure the front cabinet
and inverter cover, the screws (ST1TØ4
× 10L  4 pcs.) used to secure the front
cabinet at the bottom, and the fixing
screws (ST1TØ4 × 10L  2 pcs.) used to
secure the motor base.

• The front cabinet is fitted into the side

cabinet (left) at the front left side so
pull up the top of the front cabinet to
remove it.

2. Attachment

1) Insert the claw on the front left side into

the side cabinet (left).

2) Hook the bottom part of the front right

side onto the concave section of the
bottom plate. Insert the claw of the side
cabinet (right) into the square hole in the
front cabinet.

3) Return the screws that were removed

above to their original positions and
attach them.

Remarks

FILE NO. SVM-12051

Front cabinet

Claw

Square 
hole

Concave section

Summary of Contents for RAS-B10N3KVP-E

Page 1: ...RVICE MANUAL SPLIT TYPE Indoor Unit Outdoor Unit High Wall Heat PumpType Heat PumpType RAS B13N3KVP E RAS 13N3AVP E FILE NO SVM 12051 1 RAS B10N3KVP E RAS 10N3AVP E RAS B16N3KVP E RAS 16N3AVP E Revised Nov 2012 ...

Page 2: ...5 5 WIRING DIAGRAM 17 6 SPECIFICATIONS OF ELECTRICAL PARTS 18 7 REFRIGERANT CYCLE DIAGRAM 19 8 CONTROL BLOCK DIAGRAM 22 9 OPERATION DESCRIPTION 24 10 INSTALLATION PROCEDURE 50 11 HOW TO DIAGNOSE THE TROUBLE 64 12 HOW TO REPLACE THE MAIN PARTS 89 13 EXPLODED VIEWS AND PARTS LIST 105 FILE NO SVM 12051 ...

Page 3: ... EXPLOSION TO PREVENT OVERHEATING THE INDOOR UNIT AND CAUSING A FIRE HAZARD PLACE THE UNIT WELL AWAY MORE THAN 2 M FROM HEAT SOURCES SUCH AS RADIATORS HEATERS FURNACE STOVES ETC WHEN MOVING THE AIR CONDITIONER FOR INSTALLING IT IN ANOTHER PLACE AGAIN BE VERY CAREFUL NOT TO GET THE SPECIFIED REFRIGERANT R410A WITH ANY OTHER GASEOUS BODY INTO THE REFRIGERATION CYCLE IF AIR OR ANY OTHER GAS IS MIXED ...

Page 4: ...t where flammable gas may leak It there is any gas leakage or accumulation around the unit it can cause a fire Do not select a location for installation where there may be excessive water or humidity such as a bathroom Deterioration of insulation may cause elestrical shock or fire Installation work must be performed following the instructions in this installation manual Improper installation may c...

Page 5: ... Ensure that drained water is discharged Improper drainage can result in water leakage causing water damage to furniture Tighten the flare nut with a torque wrench using the prescribed method Do not apply excess torque Otherwise the nut may crack after a long period of usage and it may cause the leakage of refrigerant Wear gloves heavy gloves such as cotton gloves for installation work Failure to ...

Page 6: ...erconnection Usable temperature range Indoor Cooling Heating C Outdoor Cooling Heating C Accessory Indoor unit Installation plate Wireless remote controller Batteries Remote controller holder Toshiba IAQ Filter Mounting screw Remote controller holder Pan head wood screw Plasma air purifier Installation manual Owner s manual Outdoor unit Drain nipple Water proof rubber cap 1 1 2 1 Ph 220 240V 50Hz ...

Page 7: ...S B16N3KVP E 0 2 4 6 8 10 12 0 10 20 30 40 50 60 70 80 90 100 110 120 Compressor Speed RPS Current A RAS B10N3KVP E RAS B13N3KVP E RAS B16N3KVP E RAS B10N3KVP E RAS B13N3KVP E RAS B16N3KVP E 50 55 60 65 70 75 80 85 90 95 100 105 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 Cooling Capacity ratio Outside Temperature o C Capacity ratio 100 2 51kW RAS B10N3KVP E 3 52kW RAS B13N3KVP E 4 53kW RAS B16N3...

Page 8: ... in the refrig eration cycle may become abnormally high so that a rupture or personal injury may be caused 5 After completion of installation work check to make sure that there is no refrigeration gas leakage If the refrigerant gas leaks into the room coming into contact with fire in the fan driven heater space heater etc a poisonous gas may occur 6 When an air conditioning system charged with a l...

Page 9: ...et joints Nominal diameter 1 4 3 8 1 2 5 8 Reference outer diameter of copper pipe jointed mm 6 35 9 52 12 70 15 88 Minimum joint thickness mm 0 50 0 60 0 70 0 80 3 2 2 Processing of Piping Materials When performing the refrigerant piping installation care should be taken to ensure that water or dust does not enter the pipe interior that no other oil than lubricating oils used in the installed air...

Page 10: ... to 0 5 0 to 0 5 0 to 0 5 0 to 0 5 Conventional flare tool Clutch type Wing nut type 1 0 to 1 5 1 5 to 2 0 1 0 to 1 5 1 5 to 2 0 1 0 to 1 5 2 0 to 2 5 1 0 to 1 5 2 0 to 2 5 Table 3 2 4 Dimensions related to flare processing for R22 Nominal diameter 1 4 3 8 1 2 5 8 Outer diameter mm 6 35 9 52 12 70 15 88 Thickness mm 0 8 0 8 0 8 1 0 A mm Flare tool for R22 clutch type 0 to 0 5 0 to 0 5 0 to 0 5 0 t...

Page 11: ...torque for R410A is the same as that for conventional R22 Incidentally when the torque is weak the gas leakage may occur When it is strong the flare nut may crack and may be made non removable When choosing the tighten ing torque comply with values designated by manufacturers Table 3 2 7 shows reference values NOTE When applying oil to the flare surface be sure to use oil designated by the manufac...

Page 12: ...ant charging Refrigerant cylinder Leakage detector Charging cylinder Usage Pipe flaring Flaring by conventional flare tool Connection of flare nut Evacuating refrigerant charge run check etc Vacuum evacuating Refrigerant charge Refrigerant charge Gas leakage check Refrigerant charge R410A air water heat pump installation Existence of new equipment for R410A Yes Yes Yes Yes Yes Yes Yes Yes Note 2 W...

Page 13: ...d the connecting port of the electronic balance and charge liquid refrigerant Indoor unit Outdoor unit Opened Opened Refrigerant cylinder with siphon Check valve Open close valve for charging Electronic balance for refrigerant charging Opened Closed Service port 3 4 Recharging of Refrigerant When it is necessary to recharge refrigerant charge the specified amount of new refrigerant according to th...

Page 14: ... of silver and copper It is used to join iron copper or copper alloy and is relatively expensive though it excels in solderability 2 Phosphor bronze brazing filler Phosphor bronze brazing filler is generally used to join copper or copper alloy 3 Low temperature brazing filler Low temperature brazing filler is generally called solder and is an alloy of tin and lead Since it is weak in adhesive stre...

Page 15: ... flux which does not contain chlorine 3 When adding water to the flux use water which does not contain chlorine e g distilled water or ion exchange water 4 Remove the flux after brazing 3 5 3 Brazing As brazing work requires sophisticated techniques experiences based upon a theoretical knowledge it must be performed by a person qualified In order to prevent the oxide film from occurring in the pip...

Page 16: ...ud bold 6 215 145 145 215 235 605 Flare 6 35 Drain hose 0 5m Hanger Connecting pipe 0 37m Connecting pipe 0 37m For 10 13k Flare 9 52mm 500 105 135 55 60 55 50 50 60 Knock out system 8 52 58 195 Front panel Knock out system Grille Inlet 8 60 Air inlet Plasma purifier Air filter Heat exchanger 250 For 16k Flare 12 7mm 58 18 188 63 26 149 Wireless remote controller Remote controller holder ...

Page 17: ...0 600 440 99 FAN GUARD 29 125 108 106 330 29 B 25 Drain outlet 2 11x14 Hole For 8 10 anchor bolt A 351 330 COVER PV View Z 630 299 View Z 137 92 5 4 Service port Gas side 10 13 Flare 9 52 16 Flare 12 70 Liquid side Flare 6 35 Electrical part 36 50 R15 6 hole 11x14 hole 330 316 B detail drawing Front leg 316 330 R15 50 36 R5 5 6 hole 600 A detail drawing Back leg FILE NO SVM 12051 4 2 Outdoor Unit ...

Page 18: ...Wireless Unit Assembly WP 027 DC5V DC12V Color indication BRW BROWN YEL YELLOW BLK BLACK RED RED BLU BLUE WHI WHITE GRN YEL GREEN YELLOW CN22 WHI CN42 BRW CN41 WHI RED Indoor Terminal Block POWER SUPPLY From outdoor Unit SHEET METAL BLK 1 2 3 3 1 1 1 2 2 1 1 2 2 1 1 2 2 4 4 3 3 5 5 6 6 1 1 1 1 2 2 3 3 4 4 5 5 1 1 2 2 3 3 4 4 5 5 1 2 3 4 5 6 7 8 9 10 11 1 2 3 4 5 6 7 8 9 10 11 1 2 3 4 5 6 7 8 9 10 ...

Page 19: ... DC12V 10 Coil for 4 way valve AC220 240V CAM MD12TCTH 5 STF H01AJ1872A1 Compressor 3 phases 4 poles 750W Inverter attached Inverter attached Inverter attached 8 Inverter attached DA111A1F 20F1 Parts name Model name Rating CH 57 FC ICF 140 43 4R No Fan motor for indoor 2 Room temp sensor TA sensor 10kΩ at 25 C 3 Heat exchanger temp sensor TC sensor 10kΩ at 25 C 4 Louver motor Output Rated 1W 16 po...

Page 20: ...al shape of heat insulator Allowable height difference 10m Allowable pipe length P Pressure measurement Gauge attaching port Vacuum pump connecting port Muffler Pulse Modulating valve at liquid side Ø1 2 x 80 Ø1 2 x 80 TD 4 way valve Compressor DA111A1F 24F TS T2 Outdoor heat exchanger Split capillary Temp measurement Propeller fan Refrigerant amount 1 05kg OUTDOOR UNIT Muffler Muffler TE TC TA Mi...

Page 21: ...able height difference 10m Allowable pipe length P Pressure measurement Gauge attaching port Vacuum pump connecting port Pulse Modulating valve at liquid side Ø1 2 x 80 Ø1 2 x 80 TD 4 way valve Compressor DA111A1F 24F TS T2 Outdoor heat exchanger Split capillary Temp measurement Propeller fan Refrigerant amount 1 05kg OUTDOOR UNIT Muffler Muffler TE TC TA Min 2m Chargeless 15m Charge 20g m 16 to 2...

Page 22: ...VP E 0 7 to 0 9 7 to 9 42 to 44 High High 83 Heating Tempeature Model name Standard Heat exchanger Indoor Outdoor Compressor condition C RAS pressure pipe temp fan mode fan mode revolution Indoor Outdoor P MPa T1 C T2 C rps 20 7 6 B10N3KVP E 2 5 to 2 7 36 to 38 2 to 3 High High 48 B13N3KVP E 2 7 to 2 9 40 to 42 2 to 3 High High 65 B16N3KVP E 2 9 to 3 1 49 to 51 1 to 2 High High 83 NOTES 1 Measure ...

Page 23: ...on Serial Signal Transmitter Receiver Micro Switch Converter D C circuit Noise Filter Indoor Air purifier unit Louver Motor Louver Motor Drive Control Indoor Fan Motor Control Initializing Circuit Clock Frequency Oscillator Circuit Power Supply Circuit Operation Heat Exchanger Sensor Tc Room Temperature Sensor Ta Infrared Rays Signal Receiver and Indication Functions Cold draft preventing Function...

Page 24: ...ynthesis function Input current release control IGBT over current detect control Outdoor fan control High power factor correction control Inverter output frequency control A D converter function P M V control Discharge temp control 4 way valve control Signal communication to indoor unit P M V Pulse Motor Valve M C U Micro Control Unit M C U For INDOOR UNIT 4 way valve P M V Inverter DC AC Gate dri...

Page 25: ...ion control 2 Role of outdoor unit controller Receiving the operation command signal Serial signal from the indoor unit controller the outdoor unit performs its role Compressor operation control Operation control of outdoor fan motor P M V control 4 way valve control Operations followed to judgment of serial signal from indoor side Detection of inverter input current and current release operation ...

Page 26: ...ir purifying control Detection of abnormality 37 12 Discharge temperature control 37 13 Pulse Modulating valve P M V control 38 14 Self Cleaning function 39 15 Remote A or B selection 40 9 3 Auto Restart Function 9 3 1 How to Set the Auto Restart Function 44 9 3 2 How to Cancel the Auto Restart Function 45 9 3 3 Power Failure During Timer Operation 45 21 FILTER Indicator 42 9 4 Remote Controller a...

Page 27: ...N OFF Air conditioner Air purifier Operation select COOL HEAT AUTO DRY Temperature setup Air direction Swing Air volume select AUTO LOW LOW MED MED HIGH ECO ON timer setup OFF timer setup Hi POWER Indoor unit control Command signal generating function of indoor unit operation Calculation function temperature calculation Activation compensation function of indoor fan Cold draft preventive function ...

Page 28: ...he operation mode the fan speed is controlled by the previous operation mode 4 DRY operation DRY operation is performed according to the difference between room temperature and the setup temperature as shown below In DRY operation fan speed is controlled in order to prevent lowering of the room temperature and to avoid air flow from blowing directly to persons 1 Detects the room temperature Ta whe...

Page 29: ...ording to the setup tempera ture room temperature and heat exchanger temperature Fig 1 Fig 2 2 5 Ta C 2 0 1 5 1 0 0 5 Tsc a b c d e M WB 3 4 5 L W6 Air volume AUTO L L M M H W6 L M 2 W9 M H 2 WC Indication Fan speed Fan speed setup COOL ON AUTO MANUAL 3 Fan speed M L x 3 4 L 4 Fan speed M L x 2 4 L 5 Fan speed M L x 1 4 L Linear approximation from M and L FILE NO SVM 12051 Table 1 Indoor fan air f...

Page 30: ...c 1 0 d 1 5 e 2 0 f 2 5 g 5 0 5 5 L W9 M WD 1 2 3 H WE H WE Line approximate H and SUL with Tc SUL W2 Stop 46 46 Tc 34 45 45 33 33 33 21 32 32 20 A 4 A 4 A 4 A 4 A 4 A 4 Fan speed MANUAL in starting Fan speed AUTO in stability Fan speed AUTO in starting L L M M H W8 L M 2 WA M H 2 WE Indication Fan speed Fan speed setup HEAT ON AUTO YES NO MANUAL TC 42 C Min air flow rate control Tc 52 51 42 41 Li...

Page 31: ...unit controller Fan motor ON 3 Fan lock OFF status of fan motor continues 4 Motor operates as shown in the table below 1 Outdoor unit operation command Outdoor fan control Air conditioner OFF Alarm display Compressor speed rps To 38 C To 28 C To To 15 C To 5 5 C To 0 C During To 38 C ECO mode To 38 C When To is abnormal 13 8 31 7 32 3 MAX MIN MAX MIN MAX MIN MAX f 2 f 3 f A f C f D f F f 2 f 3 f 7...

Page 32: ...rive circuit does not exceed the specified value 5 Current release control Set temp Ts Room temp Ta Correction of Hz signal Outdoor temp To Setup of current release point Change of compressor speed Remote controller Indoor unit Ts Ta Current decrease Correction value of Hz signal Operating Hz Outdoor unit inverter main circuit control current High Low Reduce compressor speed Operating current Setu...

Page 33: ...pressor speed is kept Q zone When temperature of the indoor heat exchanger drops in the range from 48 C to under 55 C the compressor speed is kept Q zone 2 When temperature of the indoor heat exchanger rises to 55 C or higher the compressor speed is reduced P zone 3 When temperature of the indoor heat exchanger does not rise to 52 C or when it drops below to 48 C the capacity control operation ret...

Page 34: ...lower stop the indoor fan Finish of defrost operation Returning conditions from defrost operation to heating operation 1 Temperature of outdoor heat exchanger rises to 8 C or higher 2 Temperature of outdoor heat exchanger is kept at 5 C or higher for 80 seconds 3 Defrost operation continues for 15 minutes Returning from defrost operation 1 Stop operation of the compressor for approx 50 seconds 2 I...

Page 35: ...either upper or lower limit position swing operation is performed in width 35 from the limit which the stop position exceeded 3 Swing 2 Louver position in heating operation 2 Air direction adjustment The position is automatically controlled according to the operation The set louver position is stored in memory by the microcomputer The angle of the louver is indicated as the louver closes fully is ...

Page 36: ...ssor speed 0Hz A zone aHz B zone a to cHz C zone cHz 0 0 5 1 0 1 5 2 0 2 5 3 0 4 0 5 0 6 0 7 0 8 0 9 0 10 0 11 0 Room temp Set temp 3 5 3 0 2 5 1 5 1 0 TSC 1 0 2 0 5 5 1H 2H 11 10 7 6 5 4 3 2 1 OFF Dry Max 12 11 9 8 10 TA 6 0 6 5 3H 4H 5 0 4 5 4 0 2 0 0 5 0 5 12 9 8 Time Zone Frequency FAN Min Hz Fan speed depend on presetting and can change every speed 1 The control target temperature increase 0 ...

Page 37: ...ration of air conditioner air purifier an operation of air conditioner air purifier starts by pushing AC button on the remote controller Operation of air conditioner air purifier is stored in memory 1 Swing is available 2 Fan speed is Fan Auto mode varies in order M 1 L L SL Filter lamp ON Press RESET button Did you press RESET button for 3 seconds or more Did you press RESET button for 10 seconds...

Page 38: ... an error is judged again 12 Discharge temperature control Reset by RESET button Reset by RESET button or by the stop direction from the remote controller When the breaker is turned ON In restart time after power failure or RESET button is pressed while the FILTER indicator is turned on the air purifier is not turned on until the integrated operation time of the indoor fan exceeds 1 hour after ope...

Page 39: ... in the range of set tempera ture Discharge temp control 4 When defrost operation is performed the open degree of valve is adjusted accord ing to each setup conditions during preparation for defrost and during defrost operation 4 way valve is inversed 5 To turn off the compressor while the air conditioner stops by control of the thermostat or by remote controller adjust the open degree of valve to...

Page 40: ... operation performed prior to the reception of the stop code 3 After the Self Cleaning operation has been performed for the specified period the unit stops operating Unit now performing cooling or dry operation Press STOP button Only timer indicator lights and Self Cleaning operation starts Time set now elapses Operation stops function During Self Cleaning operations The louver opens slightly The ...

Page 41: ... nearby rooms this operation prevents the remote controller signal from being received simultaneously by both units thus preventing both units from operating 3 Operation The indoor unit on which the remote controller selection has been set to B receives the signal of the remote control ler also set to B At the factory the remote controller selection is set to A on all the indoor units There is no ...

Page 42: ...tton to choose the operating hours Repeat pressing to select the hours If the COMFORT SLEEP button is pressed again means cancel comfort sleep mode Heating mode The preset temperature will drop down as show on ECO operation Item No 9 choose the operating hours Repeat Press the COMFORT SLEEP button to pressing to setect thehours If the COMFORT SLEEP button is pressed again means cancel comfort slee...

Page 43: ... temperature is 24ºC 4 Louver position is set as stored position of the operating mode 5 Fan is controlled as followings Mode POWER mark is indicated on the display of the remote controller and the unit operates as follows 1 Automatic operation The indoor unit operates in according to the current operation 2 Cooling operation remote controller does not change The indoor unit s fan speed level incr...

Page 44: ...100 75 or 50 The lower the percentage the higher the saving and also the longer the compressor lifetime When the level is selected Power SEL level flashes on LCD display for 3 seconds In case of 75 and 50 level number 75 or 50 also flashes for 2 seconds Note Due to the reason that POWER SELECT FUNCTION limits the maximum current inadequate capacity may occur Power Selection 50 is 50 of rate maximu...

Page 45: ... Function This indoor unit is equipped with an automatic restarting function which allows the unit to restart operating with the set operating conditions in the event of a power supply being accidentally shut down The operation will resume without warning three minutes after power is restored This function is not set to work when shipped from the factory Therefore it is necessary to set it to work...

Page 46: ...ired to operate at this time press RESET button once more or use the remote controller to turn it on 9 3 2 How to Cancel the Auto Restart Function To cancel auto restart function proceed as follows Repeat the setting procedure the unit receives the signal and beeps three times The unit will be required to be turned on with the remote controller after the main power supply is turned off When the sy...

Page 47: ...or clock up down button TEMP Mode select button MODE Swing louver button SWING Fan speed button FAN One Touch button ONE TOUCH Set louver button FIX 8 degree celcius operation button 8 C Economy button ECO High power button Hi POWER Plasma Air PuriÞer button PURE Comfort sleep button COMFORT SLEEP Power selection button POWER SEL On timer button ON Off timer button OFF Setup button SET Clear butto...

Page 48: ...peration preset temperature is 24 C and fan operation is automatic speed 9 TIMER OPERATION FILE NO SVM 12051 7 ECO OPERATION To automatically control room to save energy except in DRY and FAN ONLY mode Press Start and stop the operation Note Cooling operation the set temperature will increase automatically 1 degree hour for 2 hours maximum 2 degrees increase For heating operation the set temperatu...

Page 49: ...g operation the set temperature will increase automatically 1 degree hour for 2 hours maximum 2 degrees increase For heating operation the set temperature will decrease 14 8 C OPERATION 1 Press button to change to 8 C set temperature heating operation 2 Press to adjust setting temperature from 5 C to 13 C FILE NO SVM 12051 12 POWER SELECTION OPERATION This function is used when its circuit breaker...

Page 50: ... Press the Hi POWER button to start and press it again to stop the operation 8 PRESET indicator Flashes for 3 seconds when the PRESET button is pressed during operation The mark is shown when holding down the button for more than 3 seconds while the mark is flashing Press another button to turn off the mark 9 POWER SEL 10 A B change indicator remote controller When the remote controller switching ...

Page 51: ... the piping hole sloped slightly The auxiliary piping can be connected to the left rear left rear right right bottom right or bottom left Right Rear right Bottom right Rear left Bottom left Left 1 Batteries Flat head wood screw Remote control holder Vinyl tape Apply after carrying out a drainage test Wireless remote control Saddle Extension drain hose Not available provided by installer Shield pip...

Page 52: ...e 6 35 mm Gas side 9 52 mm Pipe insulating material polyethylene foam 6 mm thick Putty PVC tapes Part Code A B C Q ty One each 1 One each 12 70 mm 10 13k Series 16k Series FILE NO SVM 12051 10 2 Installation 10 2 1 Optional installation parts Fixing bolt arrangement of outdoor unit Drain outlet Air inlet Air outlet 125 mm 108 mm Ø25 mm 29 mm 330 mm 106 mm 121 mm 99 mm 600 mm When using a multi sys...

Page 53: ... 1 TOSHIBA New IAQ filter L x 1 Plasma air purifier x 1 Part No 4 5 6 Part No 7 8 9 Others Name Owner s manual Installation manual Part name Q ty Mounting screw 4 x 25 s x 6 Flat head wood screw 3 1 x 16 s x 2 Drain nipple x 1 10 2 2 Accessory and installation parts The part marked with asterisk is packaged with the outdoor unit 10 Cap water proof x 2 ...

Page 54: ... size have been changed to 1 2 UNF 20 threads per inch When purchasing a charge hose be sure to confirm the port size As pressure is high and gasification speed is fast it is difficult to read the indicated value by means of charging cylinder as air bubbles occur The size of opposite sides of flare nuts have been increased Incidentally a common wrench is used for nominal diameters 1 4 and 3 8 By i...

Page 55: ...llation of the piping to the outdoor unit A place which allows the front panel to be opened The indoor unit shall be installed as top of the indoor unit comes to at least 2 m height Also it must be avoided to put anything on the top of the indoor unit CAUTION Direct sunlight to the indoor unit s wireless receiver should be avoided The microprocessor in the indoor unit should not be too close to RF...

Page 56: ...conditioner NOTE Wire type More than H07RN F or 60245 IEC66 1 5 mm2 or more CAUTION This appliance can be connected to a mains in either of the following to ways 1 Connection to fixed wiring A switch or circuit breaker which disconnects all poles and has a contact separation of at least 3 mm must be incorporated in the fixed wiring An approved circuit breaker or switches must be used 2 Connection ...

Page 57: ...Since condensation results in machine trouble make sure to insulate both the connecting pipes separately Use polyethylene foam as insulating material Fig 10 3 8 Die cutting Front panel slit Changing drain hose Piping preparation Rear right Rear left Bottom left Left Bottom right Right FILE NO SVM 12051 1 0 mm2 or more When ataching the air inlet grille the contrary of the removed operation is perf...

Page 58: ... or a making off pin cut them with a pair of nippers or an equivalent tool Slit Fig 10 3 14 Bend the connecting pipe within a radius of 30 mm Left hand connection with piping Bend the connecting pipe so that it is laid within 43 mm above the wall surface If the connecting pipe is laid exceeding 43 mm above the wall surface the indoor unit may unstably be set on the wall When bending the connecting...

Page 59: ...ate at the upper hooks 2 Swing the indoor unit to right and left to confirm that it is firmly hooked on the installation plate 3 While pressing the indoor unit onto the wall hook it at the lower part on the installation plate Pull the indoor unit toward you to confirm that it is firmly hooked on the installation plate CAUTION Fig 10 3 17 For detaching the indoor unit from the installation plate pu...

Page 60: ...ain water does not cause any problems Precautions for adding refrigerant Use a scale having a precision with at least 10 g per index line when adding the refrigerant Do not use a bathroom scale or similar instrument Use liquid refrigerant when refilling the refrigerant Since the refrigerant is in liquid form it can fill quickly Therefore perform the filling operation carefully and insert the refri...

Page 61: ...d drain off the water For the position where the drain nipple is installed refer to the installation diagram of the indoor and outdoor units Check that the outdoor unit is horizontal and route the drain hose at a downward sloped angle while ensuring that it is connected tautly Do not use ordinary garden hose but one can flatten and prevent water from draining Fig 10 4 3 Commercially available drai...

Page 62: ... the pump does not flow back into the air conditioner pipes when the pump stops If oil inside the vacuum pump enters into the air conditioner circuit which uses R410A trouble with the refrigeration system may develop 1 Connect the charge hose from the manifold valve to the service port of the gas side packed valve 2 Connect the charge hose to the port of the vacuum pump 3 Open fully the low pressu...

Page 63: ... cable Power cord NOTE Connecting cable Wire type More than H07RN F or 245 IEC66 1 0 mm2 or more Fig 10 4 11 10 4 5 Wiring connection 1 Remove the valv Fig 10 4 10 e cover from the outdoor unit 2 Connect the connecting cable to the terminals as identified with their respective matched numbers on the terminal block of indoor and outdoor unit 3 When connecting the connecting cable to the outdoor uni...

Page 64: ...int the remote control at the indoor unit 3 Push and hold button on the Remote Control by the tip of the pencil 00 will be shown on the display 4 Press during pushing B will show on the display and 00 will disappear and the air conditioner will turn OFF The Remote Control B is memorized Note 1 Repeat above step to reset Remote Control to be A 2 Remote Control A have not A display 3 Detault setting...

Page 65: ...parts on the P C board by hand The new inverter 3DV inverter will be incorporated starting with this unit 3DV 3 shunt Discrete Vector control K The control circuitry has an uninsulated construction No 1 2 3 4 5 Troubleshooting Procedure First Confirmation Primary Judgment Judgment by Flashing LED of Indoor Unit Self Diagnosis by Remote Controller Judgment of Trouble by Every Symptom No 6 7 8 9 10 ...

Page 66: ...e components Sensor leads Do NOT lay the circuit board assembly flat K Precautions when inspecting the control section of the outdoor unit NOTE A large capacity electrolytic capacitor is used in the outdoor unit controller inverter Therefore if the power supply is turned off charge charging voltage DC280 to 380V remains and discharging takes a lot of time After turning off the power source if touc...

Page 67: ... Increasing of compressor motor speed stops approx 30 seconds after operation started and then compressor motor speed increases again approx 30 seconds after In AUTO mode the operation mode is changed In HEAT mode the compressor motor speed does not increase up to the maxi mum speed or decreases before the temperature arrives at the set temperature Description The OPERATION lamp of the indoor unit...

Page 68: ...onditioner operates 2 When item B and C and item B and a part of item E occur concurrently priority is given to the block of item B 3 The check codes can be confirmed on the remote controller for servicing OPERATION Green Flashing display 1 Hz OPERATION Green TIMER Yellow FILTER Orange Flashing display 5 Hz OPERATION Green FILTER Orange Flashing display 5 Hz OPERATION Green TIMER Yellow Flashing d...

Page 69: ...racters are used for the check codes is 5 is 6 is A is B is C is D Fig 11 4 1 68 11 4 Self Dia gnosis by Remote Controller Check Code 1 If the lamps are indicated as shown B to E in Table 11 4 1 execute the self diagnosis by the remote controller 2 When the remote controller is set to the service mode the indoor controller diagnoses the operation condition and indicates the information of the self...

Page 70: ...oom Operation Flashes when 1 Check the sensor TA and connection board temperature sensor is continues error is detected 2 In case of the sensor and its short Circuit or disconnection connection is normal check the P C board TC sensor The heat Operation Flashes when 1 Check the sensor TC and connection exchanger temperature continues error is detected 2 In case of the sensor and its sensor of the i...

Page 71: ...or unit open 4 The outdoor unit abnormal stop at circuit of signal some time Signal circuit of indoor If the other check codes are found P C board or outdoor concurrently check them together P C board is failure Check protector hardware such in some period as Hi Pressure switch Thermal Relay etc Check refrigerant amount or any possibility case which may caused high temperature or high pressure Che...

Page 72: ...resistance of compressor winding If circuit is shortage replace the compressor Current detect circuit of All OFF Flashes after Even if trying to operate again all inverter P C board error error is detected operations stop replace inverter 4 times P C board TE sensor The heat All OFF Flashes after 1 Check sensors TE TS and connection exchanger temperature error is detected 2 In case of the sensors ...

Page 73: ...rror count comes 4 times record error to check code But after re starting operation if no error is detected and air conditioner can operate more than 6 minutes error count is cleared The others Return signal of the outdoor Indoor unit Flashes when 1 Check power supply Rate 10 including unit has been sent when operates error is detected 2 If the air conditioner repeat operates compressor operation ...

Page 74: ...sound of initial operation etc 4 Observe any possibility cause which may affect high temperature of compressor Compressor is high current All OFF Flashes after 1 Check installation conditions such as though operation Hz is error is detected packed valve opening refrigerant decreased to minimum limit 4 times amount and power supply rate 10 Installation problem both of operation and non operation In...

Page 75: ...YES FILE NO SVM 12051 NO Turn off power supply once and 5 second later turn it on again Is OPERATION indicator flashing Is it possible to turn on power supply by pushing START STOP button on remote controller Is voltage DC12V or 5V indicated on rear of indoor control board normal Does transmission mark on remote controller flash normally and is its signal transmitted properly Is DC310 340V supplie...

Page 76: ...ible to detect DC 1V or more between 5 and 3 of motor connector CN31 Start to operate the indoor unit in except heating operation At this time is it possible to detect DC 1V or more between 5 and 3 of motor connector CN31 Check this condition within 15 seconds after starting unit Start to operate the indoor unit in except heating operation At this time is it possible to detect DC 1V or more betwee...

Page 77: ...an motor Cause The IC is built in the indoor fan motor Therefore the P C board is also mounted to inside of the motor If the P C board is soldered imperfectly or the IC is defective the fan motor may automatically rotate by turning on power supply Inspection procedure 1 Remove the front panel Remove 2 screws 2 Remove the cover of the fan motor lead wires 3 Check DC voltage with CN31 connector whil...

Page 78: ...r receiver or indoor unit Press button Batteries are exhausted Is transmission mark indicated Does indoor unit beep and operate Remote control is defective Does indoor unit start to operate by automatic restart function Does radio sound is affected by remote control when a signal is transmitted at distance of 5 cm from radio P C board is defective Keep indoor unit away from thyristor fluorescent l...

Page 79: ...transmission from indoor unit to outdoor unit is correctly performed based upon the follow ing diagram NOTE Measurement should be performed 2 minutes and 30 seconds after starting of the operation Be sure to prepare a diode for judgment Normal time Voltage swings between DC15 and 60V Inverter Assembly check 11 8 1 Abnormal time Voltage does not vary 2 Outdoor unit stops in a little while after ope...

Page 80: ...ressure is low Is connecter of coil connected to inverter Is coil of the pulse motor valve P M V correctly set Existence of condensation at outlet of P M V If there is condensation at outlet 1 4 inch Ø6 35mm valve side the valve is clogged Are temp sensors of indoor outdoor units correctly set to the holder NOTE The temperature sensors which are used to control pulse motor valve include indoor hea...

Page 81: ... C board Micro switch is stuck Micro switch malfunction To item Power supply is not turned on Replace the main P C board Replace micro switch Does the PURE indicator go off within 2 seconds after it was ON and does the FILTER indicator Orange go on Are the electric dust collector and ionizer dried Electrode check Dry the electric dust collector and ionizer Is DC 5V to DC 10V applied between Brown ...

Page 82: ...duction of micro switch connector under OFF status of the micro switch Front panel opened Is there conduction of micro switch connector under ON status of the micro switch Front panel closed Does the indoor fan rotate Does the PURE indicator Blue or the FILTER indicator Orange go on Is DC12V applied between Red DC12V and Brown GND of CN1 of the high voltage generator in the air purifier Micro swit...

Page 83: ...or S Summary If fuse was blown be sure to check the electrolytic capacitor and diode block DB01 Connect discharge resistance approx 100Ω 40W or soldering iron plug between terminals of the electro lytic capacitor 500µF or 760µF of C14 with printed CAUTION HIGH VOLTAGE on P C board OK if 500µF or 760µF DC280 to 380V Remove CN300 while pushing the part indicated by an arrow because CN300 is a connec...

Page 84: ...1 How to Check the P C Board Indoor Unit 1 Operating precautions 1 When removing the front panel or the P C board be sure to shut off the power supply breaker 2 When removing the P C board hold the edge of the P C board and do not apply force to the parts 3 When connecting or disconnecting the connectors on the P C board hold the whole housing Do not pull at the lead wire 2 Inspection procedures 1...

Page 85: ...Check whether or not all indicators OPERATION TIMER FILTER PURE and HI POWER are lit for 3 seconds and they return to normal 3 seconds later 1 Check whether or not the com pressor operates 2 Check whether or not the OPERATION indicator flashes 1 Check whether or not the com pressor operates 2 Check whether or not the OP ERATION indicator flashes 1 Check it is impossible to detect the voltage DC 15...

Page 86: ...0 10 20 30 40 50 Resistance value k Temperature C TD Discharge temp sensor TA Room temp sensor TC and Tcj Heat exchanger temp sensor TO Outdoor temp sensor TE Outdoor heat exchanger temp sensor TS Suction temp sensor TA TC Tcj TO TE TS TD 1 Sensor characteristic table 12V GND 5V ...

Page 87: ... 2 1 Refer to 11 5 1 5 Measure the resistance value of each winding coil by using the tester Under normal temp 25 C Position 1 to 2 1 to 3 1 to 4 1 to 5 Resistance value 250 20Ω Refer to 11 5 1 3 and 4 Under 20 C Disconnect the connector and measure resistance value with the tester Normal temperature Outdoor temperature sensor TO discharge temperature sensor TD suction temperature sensor TS outdoo...

Page 88: ...ered surface Heat sink IGBT side C12 C13 C14 Case that product is good Pointer swings once and returns slowly When performing test once again under another polarity the pointer should return C12 C13 C14 500µF or 760µF 400V Resistance value in good product Tester rod 2 3 2 3 4 1 1 2 3 DB01 4 4 2 3 1 10 to 20 Ω when the multimeter probe is reversed 2 Diode block 1 Turn OFF the power supply breaker 2...

Page 89: ...of the outdoor fan motor 4 Motor drive circuit failure of the outdoor P C board 3 How to simply judge whether outdoor fan motor is good or bad NOTE However GND circuit error inside of the motor may be accepted in some cases when the above check is performed When the fan motor does not become normal even if P C board is replaced replace the outdoor fan motor If the resistance value between 1 Red le...

Page 90: ...shed they may ignite any oil mixed with the refrigerant gas 2 Do not use welding equipment in an airtight room Carbon monoxide poisoning may result if the room is not properly ventilated 3 Do not bring welding equipment near flammable objects Flames from the equipment may cause the flammable objects to catch fire If keeping the power on is absolutely unavoidable while doing a job such as inspectin...

Page 91: ...e center positions and two low Holder Plasma air purifier Protrusion er center positions of the air outlet and then hang the hanging hooks 3 pcs at the top side of the front panel to the rear plate 2 Insert the plasma air purifier Holder Protrusion Plasma air purifier Press in the plasma air parifier until the protrusions on both sides are completely inserted into the holders If installation is in...

Page 92: ...e connectors of the high voltage generat 4 Attach the air ionizer to the back body How to assemble the high voltage generator 1 Insert the high voltage generator straight into the evaporator voltage generator from the evaporator Check whether it is completed inserted 3 Disconnect the connectors of the high voltage generator 4 Remove the fixing screws 2 pcs and remove the high voltage generator fro...

Page 93: ...ts box assembly onto the claws on the back body and secure it using the fixing screw Now attach the display unit Connect the connectors for the fan motor and louver motor 2 Secure the grounding wire using the fixing screw Insert the TC sensor into the sensor holder Be absolutely sure to loop the grounding wire and TC sensor leads once at the bottom 5 Disengage the display unit by simply pushing at...

Page 94: ... 1 Follow to the procedure in the item 2 Remove the pipe holder from the rear side of the main unit 3 Remove two fixing screws at the left side of the end plate of the heat exchanger Remarks 4 Remove one fixing screw on the heat exchage fixing holder to separate the heat exchage from the back body 5 Remove right side of the end plate from two fixing rib while sliding slightly the heat exchanger ri...

Page 95: ...nstall the cross flow fan so that the right end of the 1st joint from the right of the cross flow fan is set keeping 5 0 mm from closed wall of the main unit Holding the set screw install the cross flow fan so that flat area on shaft of the fan motor comes to the mounting hole of the set screw Perform positioning of the fan motor as follows When assembling the fan motor the fan motor must be insta...

Page 96: ... power supply off to stop the operation of air conditioner 2 Remove the front panel Remove the 2 fixing screws 3 Remove the electrical part base Remarks Replace terminal block microcomputer ass y and the P C board ass y 12 2 Microcomputer FILE NO SVM 12051 ...

Page 97: ...e the indoor unit 2 Attach the upper cabinet ST1TØ4 10L 5 pcs 3 Perform cabling of connecting cable and attach the cord clamp Fix the cord clamp by tightening the screws ST2T 4 x 14L 3 pcs fitting 2 concave parts of the cord clamp to each connecting cables 4 Attach the valve cover ST1T 4 x 10L 3 pcs Insert the upper part into the square hole of the side cabinet set hook claws of the valve cover to...

Page 98: ...t is fitted into the side cabinet left at the front left side so pull up the top of the front cabinet to remove it 2 Attachment 1 Insert the claw on the front left side into the side cabinet left 2 Hook the bottom part of the front right side onto the concave section of the bottom plate Insert the claw of the side cabinet right into the square hole in the front cabinet 3 Return the screws that wer...

Page 99: ... This capacitor is one with mass capacity Therefore it is dangerous that a large spark generates if short circuiting between Requirement As each connector has a lock mecha nism avoid to remove the connector by holding the lead wire but by holding the connector Discharging position Discharging period 10 seconds or more Plug of soldering iron The connector is one with lock so remove it while pushing...

Page 100: ...nect them they must be pressed in the direction of the arrow while pulling them out P C board base P C board CN700 CN602 CN300 CN701 CN603 CN601 CN600 FILE NO SVM 12051 CN703 CN703 Heater 2P White NOTE These connectors have a disconnect prevention mechanism as such the lock on their housing must be released before they are disconnected 2 Remove the control board assembly from the P C board base Re...

Page 101: ...at exchanger Remarks Detail A Detail B Detail C 1 Perform work of item 1 of and 2 Remove the flange nut fixing the fan motor and the propeller Flange nut is loosened by turning clock wise To tighten the flange nut turn counterclockwise 3 Remove the propeller fan 4 Disconnect the connector for fan motor from the inverter 5 Remove the fixing screws 4 pcs holding by hands so that the fan motor does n...

Page 102: ... burner Take care to keep the 4 way valve away from naked flames Otherwise it may malfunction 7 Remove the fixing screw of the bottom plate and heat exchanger ST1TØ4 10L 1 pc 8 Remove the fixing screw of the bottom plate and valve fixing plate ST1TØ4 10L 2 pcs 9 Pull upward the refrigeration cycle 10 Remove NUT 3 pcs fixing the compres sor to the bottom plate Remarks Reactor 1 Perform work of item...

Page 103: ...ng claws by pushing minus screwdriver according to the arrow mark in the right figure and remove the fan guard 2 Attachment 1 Insert claws of the fan guard in the holes of the front cabinet Push the hooking claws 9 positions by hands and fix the claws Check that all the hooking claws are fixed to the specified positions FILE NO SVM 12051 1 Detachment 1 Perform step 1 in all the steps in and 1 in 2...

Page 104: ...product will not be controlled properly and trouble will result if the sensors have not been installed in their proper positions Detail C TS sensor Suction pipe temperature sensor Attachment Install the senser onto the straight pipe part of the suction pipe Be careful for the lead direction of the sensor TD sensor Discharge pipe temperature sensor Attachment With its leads pointed upward install t...

Page 105: ... them 9 Wind the attached color tape round the both terminals of the protective tube when colored protective tube is used 10 Fix the sensor again Remarks 1 2 3 4 5 6 Parts name Sensor Sensor Spring A Sensor Spring B Thermal constringent tube Color tape Terminal Q ty 1 1 1 3 1 3 Cutting here Cutting here Cutting here Soldered part Dryer Winding the color tape 100 200 Connector Thermal sensor part T...

Page 106: ...44409 REFRIGERANT CYCLE ASSEMBLY RAS B10 13N3KVP E RAS B10 13N3KVP E 206 43T49010 PIPE SHIELD 219 43T44483 REFRIGERANT CYCLE ASSEMBLY RAS B16N3KVP E RAS B16N3KVP E 207 43T83305 HOLDER REMOTE CONTROL 221 43T00584 PANEL SERVICE ASSEMBLY 208 43T60382 MOTOR CORD 222 43T80327 FILTER AIR R 209 43T82310 INSTALLATION PLATE 223 43T80328 FILTER AIR L 210 43T69499 UNIT ELECTRIC PURIFIER 224 43T09479 GRILLE O...

Page 107: ...ATURE SENSOR 406 43T6V313 PC BOARD RAS B10N3KVP E 402 43T50306 TEMPERATURE SENSOR 406 43T6V314 PC BOARD RAS B13N3KVP E 403 43T69320 TEMPERATURE SENSOR 406 43T6V315 PC BOARD RAS B16N3KVP E 404 43T62340 CORD CLAMP 407 43T60378 TERMINAL 405 43T6V317 PC BOARD ASSY WRS LED 408 43T60417 TERMINAL Description Description ...

Page 108: ...R 8 43T41450 COMPRESSOR 22 43T47001 NUT FLANGE 9 43T43467 CONDENSER ASSEMBLY 23 43T97001 NUT RAS 10 13N3AVP E 24 43T49335 RUBBER CUSHION 9 43T43458 CONDENSOR ASSEMBLY 25 43T46375 4 WAY VALVE RAS 16N3AVP E 26 43T63337 4 WAY VALVE COIL ASSEMBLY 10 43T46358 VALVE PACKED 6 35 DIA 27 43T63319 HOLDER SENSOR 11 43T46366 VALVE PACKED 9 52 DIA 28 43T79305 DRAIN NIPPLE RAS 10 13N3AVP E 29 43T39341 MOTOR BAS...

Page 109: ...E 703 43T60392 TERMINAL 5P 701 43T62331 HEATSINK RAS 13 16N3AVP E 704 43T60326 FUSE 702 43T6V305 ASM PCB SERV RAS 10N3AVP E 705 43T60377 TEMPERATURE SENSOR 702 43T6V306 ASM PCB SERV RAS 13N3AVP E 706 43T50304 SENSOR HEAT EXCHANGER 702 43T6V307 ASM PCB SERV RAS 16N3AVP E 707 43T62313 BASE PLATE PC Description Description ...

Page 110: ... 56 FILE NO SVM 03005 TOSHIBA CARRIER THAILAND CO LTD ...

Reviews: