background image

– 

13

 –

Gauge manifold

[ Cylinder with siphon ]

[ Cylinder without siphon ]

OUTDOOR unit

Gauge manifold

OUTDOOR unit

Refrigerant

cylinder

Electronic 

balance

Electronic 

balance

Siphon

1. Be sure to make setting so that liquid can be charged.

2. When using a cylinder equipped with a siphon, liquid can be charged without turning it upside down.

It is necessary for charging refrigerant under condition of liquid because R410A is mixed type of refrigerant.
Accordingly, when charging refrigerant from the refrigerant cylinder to the equipment, charge it turning the
cylinder upside down if cylinder is not equipped with siphon.

R410A refrigerant is HFC mixed refrigerant.
Therefore, if it is charged with gas, the composi-
tion of the charged refrigerant changes and the
characteristics of the equipment varies.

3-5. Brazing of Pipes

3-5-1. Materials for Brazing

1. Silver brazing filler

Silver brazing filler is an alloy mainly composed
of silver and copper. It is used to join iron, copper
or copper alloy, and is relatively expensive though
it excels in solderability.

2. Phosphor bronze brazing filler

Phosphor bronze brazing filler is generally used
to join copper or copper alloy.

3. Low temperature brazing filler

Low temperature brazing filler is generally called
solder, and is an alloy of tin and lead. Since it is
weak in adhesive strength, do not use it for
refrigerant pipes.

1. Phosphor bronze brazing filler tends to react

with sulfur and produce a fragile compound
water solution, which may cause a gas
leakage. Therefore, use any other type of
brazing filler at a hot spring resort, etc., and
coat the surface with a paint.

2. When performing brazing again at time of

servicing, use the same type of brazing filler.

3-5-2. Flux

1. Reason why flux is necessary

• By removing the oxide film and any foreign

matter on the metal surface, it assists the flow
of brazing filler.

• In the brazing process, it prevents the metal

surface from being oxidized.

• By reducing the brazing filler’s surface tension,

the brazing filler adheres better to the treated
metal.

Fig. 3-4-2

FILE NO. SVM-12061

Refrigerant

cylinder

Summary of Contents for RAS-B16N3KV2-E

Page 1: ...A SERVICE MANUAL SPLIT TYPE Indoor Unit Outdoor Unit High Wall Heat PumpType Heat PumpType August 2012 FILE NO SVM 12061 SWING FAN FIX QUIET HiPOWER ONE T OUCH COM FOR T SLEE P RAS B16N3KV2 E RAS 16N3AV2 E ...

Page 2: ...5 5 WIRING DIAGRAM 17 6 SPECIFICATIONS OF ELECTRICAL PARTS 18 7 REFRIGERANT CYCLE DIAGRAM 19 8 CONTROL BLOCK DIAGRAM 21 9 OPERATION DESCRIPTION 23 10 INSTALLATION PROCEDURE 47 11 HOW TO DIAGNOSE THE TROUBLE 61 12 HOW TO REPLACE THE MAIN PARTS 82 13 EXPLODED VIEWS AND PARTS LIST 99 FILE NO SVM 12061 ...

Page 3: ... EXPLOSION TO PREVENT OVERHEATING THE INDOOR UNIT AND CAUSING A FIRE HAZARD PLACE THE UNIT WELL AWAY MORE THAN 2 M FROM HEAT SOURCES SUCH AS RADIATORS HEATERS FURNACE STOVES ETC WHEN MOVING THE AIR CONDITIONER FOR INSTALLING IT IN ANOTHER PLACE AGAIN BE VERY CAREFUL NOT TO GET THE SPECIFIED REFRIGERANT R410A WITH ANY OTHER GASEOUS BODY INTO THE REFRIGERATION CYCLE IF AIR OR ANY OTHER GAS IS MIXED ...

Page 4: ...t where flammable gas may leak It there is any gas leakage or accumulation around the unit it can cause a fire Do not select a location for installation where there may be excessive water or humidity such as a bathroom Deterioration of insulation may cause elestrical shock or fire Installation work must be performed following the instructions in this installation manual Improper installation may c...

Page 5: ... Ensure that drained water is discharged Improper drainage can result in water leakage causing water damage to furniture Tighten the flare nut with a torque wrench using the prescribed method Do not apply excess torque Otherwise the nut may crack after a long period of usage and it may cause the leakage of refrigerant Wear gloves heavy gloves such as cotton gloves for installation work Failure to ...

Page 6: ... Depth mm 290 Net weicht kg 38 Compressor Motor output W 1100 Type Twin rotary type with DC inverter variable speed control Model DA131S1B 31FZ Fan motor output W Air flow rate Cooling Heating m 3 min 36 32 Piping Type Flare connection connection Indoor unit Liquid side mm 6 35 Gas side mm 12 7 Outdoor unit Liquid side mm 6 35 Gas side mm 12 7 Maximum length m 20 Maximum charge less length m 15 Ma...

Page 7: ...C Air Flow High Pipe Length 5m Voltage 230V Conditions Indoor DB 20oC Outdoor DB 7oC WB 6oC Air Flow High Pipe Length 5m Voltage 230V 50 55 60 65 70 75 80 85 90 95 100 105 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 Capacity ratio Outdoor temp oC 0 20 40 60 80 100 120 15 10 5 0 5 10 Capacity ratio Outdoor temp oC Conditions Indoor DB 27oC WB 19oC Outdoor DB 35oC Air Flow High Pipe Length 5m Volta...

Page 8: ... in the refrig eration cycle may become abnormally high so that a rupture or personal injury may be caused 5 After completion of installation work check to make sure that there is no refrigeration gas leakage If the refrigerant gas leaks into the room coming into contact with fire in the fan driven heater space heater etc a poisonous gas may occur 6 When an air conditioning system charged with a l...

Page 9: ...et joints Nominal diameter 1 4 3 8 1 2 5 8 Reference outer diameter of copper pipe jointed mm 6 35 9 52 12 70 15 88 Minimum joint thickness mm 0 50 0 60 0 70 0 80 3 2 2 Processing of Piping Materials When performing the refrigerant piping installation care should be taken to ensure that water or dust does not enter the pipe interior that no other oil than lubricating oils used in the installed air...

Page 10: ... to 0 5 0 to 0 5 0 to 0 5 0 to 0 5 Conventional flare tool Clutch type Wing nut type 1 0 to 1 5 1 5 to 2 0 1 0 to 1 5 1 5 to 2 0 1 0 to 1 5 2 0 to 2 5 1 0 to 1 5 2 0 to 2 5 Table 3 2 4 Dimensions related to flare processing for R22 Nominal diameter 1 4 3 8 1 2 5 8 Outer diameter mm 6 35 9 52 12 70 15 88 Thickness mm 0 8 0 8 0 8 1 0 A mm Flare tool for R22 clutch type 0 to 0 5 0 to 0 5 0 to 0 5 0 t...

Page 11: ...torque for R410A is the same as that for conventional R22 Incidentally when the torque is weak the gas leakage may occur When it is strong the flare nut may crack and may be made non removable When choosing the tighten ing torque comply with values designated by manufacturers Table 3 2 7 shows reference values NOTE When applying oil to the flare surface be sure to use oil designated by the manufac...

Page 12: ...ant charging Refrigerant cylinder Leakage detector Charging cylinder Usage Pipe flaring Flaring by conventional flare tool Connection of flare nut Evacuating refrigerant charge run check etc Vacuum evacuating Refrigerant charge Refrigerant charge Gas leakage check Refrigerant charge R410A air water heat pump installation Existence of new equipment for R410A Yes Yes Yes Yes Yes Yes Yes Yes Note 2 W...

Page 13: ...d the connecting port of the electronic balance and charge liquid refrigerant Indoor unit Outdoor unit Opened Opened Refrigerant cylinder with siphon Check valve Open close valve for charging Electronic balance for refrigerant charging Opened Closed Service port 3 4 Recharging of Refrigerant When it is necessary to recharge refrigerant charge the specified amount of new refrigerant according to th...

Page 14: ... It is used to join iron copper or copper alloy and is relatively expensive though it excels in solderability 2 Phosphor bronze brazing filler Phosphor bronze brazing filler is generally used to join copper or copper alloy 3 Low temperature brazing filler Low temperature brazing filler is generally called solder and is an alloy of tin and lead Since it is weak in adhesive strength do not use it fo...

Page 15: ... flux which does not contain chlorine 3 When adding water to the flux use water which does not contain chlorine e g distilled water or ion exchange water 4 Remove the flux after brazing 3 5 3 Brazing As brazing work requires sophisticated techniques experiences based upon a theoretical knowledge it must be performed by a person qualified In order to prevent the oxide film from occurring in the pip...

Page 16: ...ont panel 225 63 7 48 480 4 1 Indoor Unit Installation plate outline Hanger Hanger Center line Hanger 621 Drain hose 0 50m Connecting pipe 0 40m Connecting pipe 0 35m 6 35mm Flare Installation plate hanger Installation plate hanger Flare 12 70mm 116 170 or more 170 or more 65 or more Minimum distance to wall Minimum distance to wall Minimum distance to ceiling 63 Remote controller holder 17 5 149 ...

Page 17: ...r Liquid side Flare 6 35 Ø Flare 12 70 Gas side Service port 2 11 x 14 Long holes For 8 10 anchor bolt Installation dimension Air outlel 100 or more 100 or more 600 or more 600 or more Air intlel Ø Ø Ø Ø6 hole 86 Ø6 hole Ø11x14 hole R15 28 A 320 R5 5 36 108 125 50 137 92 5 4 600 320 90 600 90 275 290 550 Ø 436 Z R15 50 36 2 320 342 69 2 R5 5 x 17L Ushape For 8 10 anchor bolt FILE NO SVM 12061 ...

Page 18: ...U BLUE WHI WHITE GRN YEL GREEN YELLOW Varistor Line Filter Heat exchanger GRN YEL GRN YEL POWER SUPPLY From outdoor Unit Indoor terminal block BLK WHI RED YEL WHI BLK RED BLU WP 027 Infrared rays receiver and indication parts Thermo Sensor TA Heat Exchanger Sensor TC DC Motor Louver Motor FAN motor Main P C Board WP 026 Power Supply Circuit DC 12V DC 15V DC 5V Fuse F01 T6 3A 250VAC CN10 WHI CN81 W...

Page 19: ...ications L 10mH 16A 2 Outdoor fan motor ICF 140 43 4R DC140V 43W 3 Suction temp sensor TS sensor Inverter attached 10kΩ 25 C 4 Discharge temp sensor TD sensor Inverter attached 62kΩ 20 C 5 Outside air temp sensor TO sensor Inverter attached 10kΩ 25 C 6 Heat exchanger temp sensor TE sensor Inverter attached 10kΩ 25 C Reactor 1 1 Fan motor for indoor 20A AC250V DA131S1B 31FZ CAM MD12TCTH 5 STF 3 pha...

Page 20: ...an Deoxidized copper pipe Outer dia 6 35mm Thickness 0 8mm Sectional shape of heat insulator Allowable height difference 10m Allowable pipe length P Pressure measurement Gauge attaching port Vacuum pump connecting port Strainer Pulse Modulating valve at liquid side Ø1 2 x 80 Ø1 2 x 80 TD 4 way valve Compressor DA131S1B 31FZ TS T2 Outdoor heat exchanger Split capillary Temp measurement Propeller fa...

Page 21: ...door Outdoor Compressor RAS pressure fan mode fan mode revolution Indoor Outdoor P MPa T1 C T2 C rps 27 19 35 B16N3KV2 E 0 8 to 1 0 11 to 13 40 to 42 High High 71 condition C Tempeature Heat exchanger pipe temp Model name Standard Indoor Outdoor Compressor RAS pressure fan mode fan mode revolution Indoor Outdoor P MPa T1 C T2 C rps 20 7 6 2 7 to 2 9 43 to 45 0 to 2 High High 72 condition C Tempeat...

Page 22: ...lator Circuit Power Supply Circuit Infrared Rays 36 7kHz Remote Controller Thermo Setting Fan Speed Selection ON TIMER Setting OFF TIMER Setting Louver AUTO Swing Louver Direction Setting QUIET Operation Mode Selection AUTO COOL DRY HEAT REMOTE CONTROLLER ECO Hi POWER Heat Exchanger Sensor Tc Room Temperature Sensor Ta Infrared Rays Signal Receiver and Indication Functions Cold draft preventing Fu...

Page 23: ...ynthesis function Input current release control IGBT over current detect control Outdoor fan control High power factor correction control Inverter output frequency control A D converter function P M V control Discharge temp control 4 way valve control Signal communication to indoor unit P M V Pulse Motor Valve M C U Micro Control Unit M C U For INDOOR UNIT 4 way valve P M V Inverter DC AC Gate dri...

Page 24: ...ir purifier operation control 2 Role of outdoor unit controller Receiving the operation command signal Serial signal from the indoor unit controller the outdoor unit performs its role Compressor operation control Operation control of outdoor fan motor P M V control 4 way valve control Operations followed to judgment of serial signal from indoor side Detection of inverter input current and current ...

Page 25: ...stment 33 3 Swing 33 9 ECO operation 34 10 Temporary operation 35 11 12 Discharge temperature control 35 13 Pulse Modulating valve P M V control 36 Self Cleaning function 37 14 15 Remote A or B selection 38 9 3 Auto Restart Function 9 3 1 How to Set the Auto Restart Function 41 9 3 2 How to Cancel the Auto Restart Function 42 9 3 3 Power Failure During Timer Operation 42 19 FILTER Indicator 40 9 4...

Page 26: ...mote controller ON OFF Air conditioner Air purifier Operation select COOL HEAT AUTO DRY Temperature setup Air direction Swing Air volume select AUTO LOW LOW MED MED HIGH ECO ON timer setup OFF timer setup Hi POWER Indoor unit control Command signal generating function of indoor unit operation Calculation function temperature calculation Activation compensation function of indoor fan Cold draft pre...

Page 27: ... When reselecting the operation mode the fan speed is controlled by the previous operation mode 4 DRY operation DRY operation is performed according to the difference between room temperature and the setup temperature as shown below In DRY operation fan speed is controlled in order to prevent lowering of the room temperature and to avoid air flow from blowing directly to persons 1 Detects the room...

Page 28: ... the constant speed shown in Fig 1 2 When setting the fan speed to AUTO on the remote controller revolution of the fan motor is controlled to the fan speed level shown in Fig 2 and Table 1 according to the setup tempera ture room temperature and heat exchanger temperature Fig 1 Fig 2 Table 1 Indoor fan air flow rate 2 5 Ta C 2 0 1 5 1 0 0 5 Tsc a b c d e M WB 3 4 5 L W6 Air volume AUTO L L M M H W...

Page 29: ...ue TSC TA C b 0 5 c 1 0 d 1 5 e 2 0 f 2 5 g 5 0 5 5 L W9 M WD 1 2 3 H WE H WE Line approximate H and SUL with Tc SUL W2 Stop 46 46 Tc 34 45 45 33 33 33 21 32 32 20 A 4 A 4 A 4 A 4 A 4 A 4 Fan speed MANUAL in starting Fan speed AUTO in stability Fan speed AUTO in starting L L M M H W8 L M 2 WA M H 2 WE Indication Fan speed Fan speed setup HEAT ON AUTO YES NO MANUAL TC 42 C Min air flow rate control...

Page 30: ...s selected 2 Fan speed 400 when the motor stopped Air conditioner ON Remote controller YES YES NO NO Indoor unit controller Fan motor ON 3 Fan lock OFF status of fan motor continues 4 Motor operates as shown in the table below 1 Outdoor unit operation command Outdoor fan control Air conditioner OFF Alarm display Outdoor fan speed rpm Compressor speed rps To 38 C To 28 C To To 15 C To 5 5 C To 0 C ...

Page 31: ...ls drive circuit of the compressor speed so that electric power of the compressor drive circuit does not exceed the specified value 5 Current release control Set temp Ts Room temp Ta Correction of Hz signal Outdoor temp To Setup of current release point Capacity control continues Detection of electromotive force of compressor motor winding Detection of motor speed and rotor position Inverter outpu...

Page 32: ... C to 55 C the compressor speed is kept Q zone When temperature of the indoor heat exchanger drops in the range from 48 C to under 55 C the compressor speed is kept Q zone 2 When temperature of the indoor heat exchanger rises to 55 C or higher the compressor speed is reduced P zone 3 When temperature of the indoor heat exchanger does not rise to 52 C or when it drops below to 48 C the capacity con...

Page 33: ...r becomes 38 C or lower stop the indoor fan Finish of defrost operation Returning conditions from defrost operation to heating operation 1 Temperature of outdoor heat exchanger rises to 8 C or higher 2 Temperature of outdoor heat exchanger is kept at 5 C or higher for 80 seconds 3 Defrost operation continues for 15 minutes Returning from defrost operation 1 Stop operation of the compressor for app...

Page 34: ...range 35 from the limit 3 Swing 2 Louver position in heating operation 2 Air direction adjustment The position is automatically controlled according to the operation The set louver position is stored in memory by the microcomputer The angle of the louver is indicated as the louver closes fully is 0 1 Louver position in cooling operation mode COOL HEAT and the louver returns to the stored position ...

Page 35: ...DRY max COOL min 6 x 1 COOL min 30 minutes A B C A B C Time Compressor speed 0Hz A zone aHz B zone a to cHz C zone cHz 0 0 5 1 0 1 5 2 0 2 5 3 0 4 0 5 0 6 0 7 0 8 0 9 0 10 0 11 0 Room temp Set temp 1 The control target temperature increase 0 5ºC per hour up to 2ºC starting from the set temperature when ECONO has been received 2 The indoor fan speed is depend on presetting and can change every spee...

Page 36: ...ter lamp ON Press RESET button Did you press RESET button for 3 seconds or more Did you press RESET button for 10 seconds or more Switch to AUTO RESTART control YES YES NO NO NO YES Temporary AUTO operation Temporary COOL Operation FILE NO SVM 12061 11 Discharge temperature control 1 Purpose This function detects error on the refrigerating cycle or error on the com pressor and performs protective ...

Page 37: ... in the range of set tempera ture Discharge temp control 4 When defrost operation is performed the open degree of valve is adjusted accord ing to each setup conditions during preparation for defrost and during defrost operation 4 way valve is inversed 5 To turn off the compressor while the air conditioner stops by control of the thermostat or by remote controller adjust the open degree of valve to...

Page 38: ... operation performed prior to the reception of the stop code 3 After the Self Cleaning operation has been performed for the specified period the unit stops operating Unit now performing cooling or dry operation Press STOP button Only timer indicator lights and Self Cleaning operation starts Time set now elapses Operation stops function During Self Cleaning operations The louver opens slightly The ...

Page 39: ... nearby rooms this operation prevents the remote controller signal from being received simultaneously by both units thus preventing both units from operating 3 Operation The indoor unit on which the remote controller selection has been set to B receives the signal of the remote control ler also set to B At the factory the remote controller selection is set to A on all the indoor units There is no ...

Page 40: ...e COMFORT SLEEP button is pressed again means cancel comfort sleep mode Heating mode The preset temperature will drop down as show on ECO operation Item No 9 choose the operating hours Repeat Press the COMFORT SLEEP button to pressing to setect thehours If the COMFORT SLEEP button is pressed again means cancel comfort sleep mode 1hr 3hr 5hr or 9hr 1hr 3hr 5hr or 9 hr 39 capacity SLEEP mode FILE NO...

Page 41: ...cator lights After cleaning the filters turn off the FILTER indicator How to Turn Off FILTER Indicator Press RESET button on the indoor unit NOTE If RESET button is pushed while the FILTER indicator is not lit the indoor unit will start the automatic operation 40 FILE NO SVM 12061 20 Short Timer In the normal condition after switching one circuit breaker 3 minute delay time for compressor and 1 ho...

Page 42: ...ion This indoor unit is equipped with an automatic restarting function which allows the unit to restart operating with the set operating conditions in the event of a power supply being accidentally shut down The operation will resume without warning three minutes after power is restored This function is not set to work when shipped from the factory Therefore it is necessary to set it to work 9 3 1...

Page 43: ...ired to operate at this time press RESET button once more or use the remote controller to turn it on 9 3 2 How to Cancel the Auto Restart Function To cancel auto restart function proceed as follows Repeat the setting procedure the unit receives the signal and beeps three times The unit will be required to be turned on with the remote controller after the main power supply is turned off When the sy...

Page 44: ...misplaced or discharged remote control Pressing the RESET button the unit can start or stop without using the remote control Operation mode is set on AUTOMATIC operation preset temperature is 24 C and fan operation is automatic speed 8 TIMER OPERATION Setting the ON Timer Setting the OFF Timer Press ON Set the desired ON timer Press OFF Set the desired OFF timer Press SET Set the timer Press SET S...

Page 45: ...mds Do not operate ON timer and OFF timer 2 Press and hold the RESET button on the indoor unit for 3 seconds to cancel the Setting operation 3 beep sound but OPERATION lamp does not blink 11 QUIET OPERATION To operate at super low fan speed for quiet operation except in DRY mode Press QUIET Start and stop the operation Note Under certain conditions QUIET operation may not provide adequate cooling ...

Page 46: ...t button FILTER 19 Set clock button CLOCK 20 Check button CHECK 21 Reset button RESET SWING FAN FIX QUIET Hi POWER ONE TOUCH COMFORT SLEEP 4 5 10 21 11 14 16 8 1 2 13 17 20 15 12 3 19 7 6 18 9 9 4 2 Operation of remote control 1 ONE TOUCH Press the ONE TOUCH button for fully automated operation that is customised to the typical consumer preferences in your region of the world The coutomised settin...

Page 47: ... than 3 seconds while the mark is blinks Press another button to turn off the mark 8 ECO indicator Indicates when the ECO is in activated Press the ECO button to start and press it again to stop operation 9 A B change indicator remote controller When the remote controller switching function is set B appears in the remote controller display When the remote controller setting is A there is no indica...

Page 48: ... bottom right or bottom left Right Rear right Bottom right Rear left Bottom left Left 6 mm thick heat resisting polyethylene foam 1 Batteries Flat head wood screw Remote control holder Vinyl tape Apply after carrying out a drainage test Wireless remote control Saddle Extension drain hose Not available provided by installer Shield pipe Attach to the front panel Air filter Hook Installation plate Ho...

Page 49: ...d cap water proof 11 to the bottom plate of the outdoor unit before installing it A Air inlet Air outlet Drain outlet 600 mm 90 mm 125 mm 108 mm 28 mm 86 mm 102 mm 320 mm 2 5 m m Æ Parts name Refrigerant piping Liquid side 6 35 mm Gas side 12 70 mm Pipe insulating material polyethylene foam 6 mm thick Putty PVC tapes Part Code Q ty One each 1 One each 10 2 1 Optional installation parts 10 2 Instal...

Page 50: ... Part No Part No Part name Q ty 10 Flat head wood screw 3 1 x 25 s x 1 Others Name Owner s manual Installation manual Remote control holder x 1 4 Toshiba New IAQ filter L x 1 5 6 Battery cover x 1 Mounting screw 4 x 25 s x 6 7 8 Drain nipple x 1 9 11 The part marked with asterisk is packaged with the outdoor unit Flat head wood screw 3 1 x 16 s x 2 Cap water proof x 2 ...

Page 51: ... size have been changed to 1 2 UNF 20 threads per inch When purchasing a charge hose be sure to confirm the port size As pressure is high and gasification speed is fast it is difficult to read the indicated value by means of charging cylinder as air bubbles occur The size of opposite sides of flare nuts have been increased Incidentally a common wrench is used for nominal diameters 1 4 and 3 8 By i...

Page 52: ...h as a stove Keep the remote control at least 1 m apart from the nearest TV set or stereo equipment This is necessary to prevent image disturbances or noise interference The location of the remote control should be determined as shown below Fig 10 3 1 45 45 75 Top view Indoor unit Reception range Reception range Remote control Indoor unit Remote control Side view 10 3 Indoor Unit 10 3 1 Installati...

Page 53: ...ews to install it Installation plate Keep horizontal direction How to connect the connecting cable Wiring of the connecting cable can be carried out 10 3 3 Wiring connection 1 Remove the air inlet grille Open the air inlet grille upward and pull it toward you 2 Remove the terminal cover and cord clamp 3 Insert the connecting cable according to the local cords into the pipe hole on the wall 4 Take ...

Page 54: ...s are exist please take them out The combination of using wire controller and batteries may cause of batteries explosion 3 Make hole for insert control wire by use screwdriver break the polyester sheet as shown on figure 7 4 Insert control wire from rear side of remote controller as shown on figure 8 5 Fix control wire which arrange as shown on figure 9 and 10 to terminal by provided screws tighte...

Page 55: ...it on the left or right side of the front panal for the left or right connection and the slit on th bonttom left or right side of the front panel for the botto left or right connection with a pair of nippers Heat insulator Drain hose How to install the drain hose Firmly insert drain hose connecting part until hitting on a heat insulator and fix it with a screw How to remove the drain hose Fig 10 3...

Page 56: ...pe Bend the connection pipe within a radius of 30 mm To connect the pipe after installation of the unit figure Fig 10 3 17 NOTE If the pipe is bent incorrectly the indoor unit may unstably be set on the wall After passing the connecting pipe through the pipe hole connect the connecting pipe to the auxiliary pipes and wrap the facing tape around them CAUTION Bind the auxiliary pipes two and connect...

Page 57: ...se sloped downwards NOTE Hole should be made at a slight downward slant on the outdoor side Fig 10 3 20 2 Put water in the drain pan and make sure that the water is drained out of doors 3 When connecting extension drain hose insulate the connecting part of extension drain hose with shield pipe Fig 10 3 21 CAUTION Arrange the drain pipe for proper drainage from the unit Improper drainage can result...

Page 58: ... and vibration A place where the operation noise and discharged air do not disturb your neighbors A place which is not exposed to a strong wind A place free of a leakage of combustible gases A place which does not block a passage When the outdoor unit is to be installed in an elevated position be sure to secure its feet The allowable pipe length is up to 20 m If the length is over 15 m add 20 g of...

Page 59: ... minute Then confirm that the compound pressure gauge reading is 101 kPa 76 cmHg 5 Close the low pressure side valve handle of gauge manifold valve 6 Open fully the valve stem of the packed valves both gas and liquid sides 7 Remove the charging hose from the service port 8 Securely tighten the caps on the packed valves Fig 10 4 7 Packed valve at liquid side Pressure gauge Manifold valve Packed val...

Page 60: ...t size of wire and wiring method etc Every wire must be connected firmly This installation circuit breaker must be used specified CAUTION for the power supply line of this air conditioner Fig 10 4 9 If incorrect or incomplete wiring is carried out it will Stripping length of the connecting cable cause an ignition or smoke Prepare the power supply for exclusive use with the air conditioner L This p...

Page 61: ... of the pencil 00 will be shown on the display 4 Press MODE during pushing CHECK B will show on the display and 00 will disappear and the air conditioner will turn OFF The Remote Control B NOTE 1 Repeat above step to reset Remote Control to be A 2 Remote Control A has not A display 3 Default setting of Remote Control from factory is A is memorized Picture Picture 1 2 10 5 3 Test operation To switc...

Page 62: ...parts on the P C board by hand The new inverter 3DV inverter will be incorporated starting with this unit 3DV 3 shunt Discrete Vector control K The control circuitry has an uninsulated construction No 1 2 3 4 5 Troubleshooting Procedure First Confirmation Primary Judgment Judgment by Flashing LED of Indoor Unit Self Diagnosis by Remote Controller Judgment of Trouble by Every Symptom No 6 7 8 9 10 ...

Page 63: ...e components Sensor leads Do NOT lay the circuit board assembly flat K Precautions when inspecting the control section of the outdoor unit NOTE A large capacity electrolytic capacitor is used in the outdoor unit controller inverter Therefore if the power supply is turned off charge charging voltage DC280 to 380V remains and discharging takes a lot of time After turning off the power source if touc...

Page 64: ... Increasing of compressor motor speed stops approx 30 seconds after operation started and then compressor motor speed increases again approx 30 seconds after In AUTO mode the operation mode is changed In HEAT mode the compressor motor speed does not increase up to the maxi mum speed or decreases before the temperature arrives at the set temperature Description The OPERATION lamp of the indoor unit...

Page 65: ...onditioner operates 2 When item B and C and item B and a part of item E occur concurrently priority is given to the block of item B 3 The check codes can be confirmed on the remote controller for servicing OPERATION Green Flashing display 1 Hz OPERATION Green TIMER Yellow FILTER Orange Flashing display 5 Hz OPERATION Green FILTER Orange Flashing display 5 Hz OPERATION Green TIMER Yellow Flashing d...

Page 66: ...ton If there is no fault with a code the indoor unit will beep once Beep and the display of the remote controller will change as follows The TIMER indicator of the indoor unit flashes continuously 5 times per 1 sec Check the unit with all 52 check codes to as shown in Table 11 4 1 Press ON or OFF button to change the check code backward If there is a fault the indoor unit will beep for 10 seconds ...

Page 67: ...e initial status However the check codes are not deleted even if the power supply is turned off because they are stored in the fixed memory 3 After servicing press CLR button under check mode status and then send the check code 7F to the indoor unit The error code stored in memory is cleared Table 11 4 1 Block distinction Operation of diagnosis function Block Indoor P C board etc Not displayed Con...

Page 68: ...tion Block Outdoor P C board Not displayed Outdoor P C board Others including compressor Operation of diagnosis function Cause of operation Inverter over current protective circuit operates Short time Position detect circuit error or short circuit between windings of compressor Current detect circuit error Being out of place disconnection or short circuit of the outdoor heat exchanger sensor TE or...

Page 69: ...e controller Is voltage DC12V or 5V indicated on rear of indoor control board normal Does transmission mark on remote controller flash normally and is its signal transmitted properly Is DC310 340V supplied between CN10 1 3 Does fan motor connector between CN10 1 3 short circuit Item by symptoms Operation Check Item Considerable principle cause Measures Parts R01 R02 DB01 C01 C03 IC11 and T101 are ...

Page 70: ...ble to detect DC 1V or more between 5 and 3 of motor connector CN31 Start to operate the indoor unit in except heating operation At this time is it possible to detect DC 1V or more between 5 and 3 of motor connector CN31 Check this condition within 15 seconds after starting unit Start to operate the indoor unit in except heating operation At this time is it possible to detect DC 1V or more between...

Page 71: ...motor Cause The IC is built in the indoor fan motor Therefore the P C board is also mounted to inside of the motor If the P C board is soldered imperfectly or the IC is defective the fan motor may automatically rotate by turning on power supply Inspection procedure 1 Remove the front panel Remove 2 screws 2 Remove the cover of the fan motor lead wires 3 Check DC voltage with CN31 connector while t...

Page 72: ...indoor unit beep and operate Remote control is defective Does indoor unit start to operate by automatic restart function Does radio sound is affected by remote control when a signal is transmitted at distance of 5 cm from radio P C board is defective Keep indoor unit away from thyristor fluorescent light Avoid direct sunlight Replace P C board Replace batteries Normal operation Replace remote cont...

Page 73: ...transmission from indoor unit to outdoor unit is correctly performed based upon the follow ing diagram NOTE Measurement should be performed 2 minutes and 30 seconds after starting of the operation Be sure to prepare a diode for judgment Normal time Voltage swings between DC15 and 60V Inverter Assembly check 11 7 1 Abnormal time Voltage does not vary 2 Outdoor unit stops in a little while after ope...

Page 74: ...d gas if pressure is low Is connecter of coil connected to inverter Is coil of the pulse motor valve P M V correctly set Existence of condensation at outlet of P M V If there is condensation at outlet 1 4 inch Ø6 35mm valve side the valve is clogged Are temp sensors of indoor outdoor units correctly set to the holder NOTE The temperature sensors which are used to control pulse motor valve include ...

Page 75: ...mary If fuse was blown be sure to check the electrolytic capacitor and diode block DB01 Connect discharge resistance approx 100Ω 40W or soldering iron plug between terminals of the electro lytic capacitor 500µF or 760µF of C14 with printed CAUTION HIGH VOLTAGE on P C board OK if 500µF or 760µF DC280 to 380V Remove CN300 while pushing the part indicated by an arrow because CN300 is a connector with...

Page 76: ...1 How to Check the P C Board Indoor Unit 1 Operating precautions 1 When removing the front panel or the P C board be sure to shut off the power supply breaker 2 When removing the P C board hold the edge of the P C board and do not apply force to the parts 3 When connecting or disconnecting the connectors on the P C board hold the whole housing Do not pull at the lead wire 2 Inspection procedures 1...

Page 77: ... not all indicators OPERATION TIMER FILTER PRE DEF Hi POWER are lit for 3 seconds and they return to normal 3 seconds later 1 Check whether or not the compressor operates 2 Check whether or not the OPERATION indicator flashes 1 Check whether or not the compressor operates 2 Check whether or not the OPERATION indicator flashes 1 Check it is impossible to detect the voltage DC 15V between 3 and 4 of...

Page 78: ...0 30 40 50 60 70 80 90 20 10 0 0 10 20 30 40 50 Resistance value k Temperature C TD Discharge temp sensor TO Outdoor temp sensor TE Outdoor heat exchanger temp sensor TS Suction temp sensor TA TC TO TE TS TD 1 Sensor characteristic table 12V GND 5V ...

Page 79: ... 3 2 1 Refer to 11 5 1 5 Measure the resistance value of each winding coil by using the tester Under normal temp 25 C Position 1 to 2 1 to 3 1 to 4 1 to 5 Resistance value 250Ω 7 Refer to 11 5 1 3 and 4 Under 20 C Disconnect the connector and measure resistance value with the tester Normal temperature Outdoor temperature sensor TO discharge temperature sensor TD suction temperature sensor TS outdo...

Page 80: ...re show in continuity test by the tester C12 C13 C14 500µF 400V 2 Converter module 1 Turn OFF the power supply breaker 2 Discharge all three capacitors completely 3 Check that the normal rectification characteristics are shown in continuity test by the tester Case that product is good Pointer swings once and returns slowly When performing test once again under another polarity the pointer should r...

Page 81: ...of the outdoor fan motor 4 Motor drive circuit failure of the outdoor P C board 3 How to simply judge whether outdoor fan motor is good or bad NOTE However GND circuit error inside of the motor may be accepted in some cases when the above check is performed When the fan motor does not become normal even if P C board is replaced replace the outdoor fan motor If the resistance value between 1 Red le...

Page 82: ...ker then hold down the RESET button on the indoor unit for 3 seconds but not more than 10 seconds The indoor unit s buzzer will emits 3 beeps 3 To operate a cooling mode for 20 minutes then turn off by remote control to ensure that Clean operation is cancelled Remark If Auto restart still require take off J201 when finish a Clean operation cancelling procedure J201 81 RESET button ...

Page 83: ...shed they may ignite any oil mixed with the refrigerant gas 2 Do not use welding equipment in an airtight room Carbon monoxide poisoning may result if the room is not properly ventilated 3 Do not bring welding equipment near flammable objects Flames from the equipment may cause the flammable objects to catch fire If keeping the power on is absolutely unavoidable while doing a job such as inspectin...

Page 84: ... screws 2 pcs 6 Take off three hooks of panel from rear side How to assemble the front panel 1 Press three center positions and two lower center positions of the air outlet and then hang the hanging hooks 3 pcs at the top side of the front panel to the rear plate 2 Tighten two screws Incomplete hanging or incomplete pressing may cause a dewdrops or generation of a fluttering sound 2 Screws Three h...

Page 85: ...parts box assembly onto the claws on the back body Now attach the display unit Connect the connectors for the fan motor and louver motor 2 Secure the grounding wire using the fixing screw Insert the TC sensor into the sensor holder Be absolutely sure to loop the grounding wire and TC sensor leads once at the bottom 5 Disengage the display unit by simply pushing at the top of the display unit 6 Rem...

Page 86: ... the pipe holder from the rear side of the main unit 3 Remove two fixing screws at the left side of the end plate of the heat exchanger Remarks 4 Remove one fixing screw on the heat exchage fixing holder to separate the heat exchage from the back body 5 Remove right side of the end plate from two fixing rib while sliding slightly the heat exchanger rightward 2 screws Heat exchanger fixing holder S...

Page 87: ... Remove the two screws used to secure the bearing base 3 Remove the bearing base Caution at assembling If the bearing is out from the housing push it into the specified position and then incorporate it in the main body Remarks Two screws Bearing Bearing base FILE NO SVM 12061 ...

Page 88: ...ove two fixing screws of the motor cover and them remove the motor cover 4 Remove two more fixing screws of the motor band and remove the motor band Remarks 5 Pull the fan motor outward Set screw Two screws Motor cover Two screws on motor band Part name FILE NO SVM 12061 Reference condition of Fan Motor s assembly ...

Page 89: ...he set screw install the cross flow fan so that flat area on shaft of the fan motor comes to the mounting hole of the set screw FILE NO SVM 12061 Perform positioning of the fan motor as follows When assembling the fan motor the fan motor must be installed in such a way that the fan motor leads will be taken out is positioned at the bottom front After assembling the two hooking claws of the motor b...

Page 90: ... power supply off to stop the operation of air conditioner 2 Remove the front panel Remove the 2 fixing screws 3 Remove the electrical part base Remarks Replace terminal block microcomputer ass y and the P C board ass y 12 2 Microcomputer FILE NO SVM 12061 ...

Page 91: ...e the indoor unit 2 Attach the upper cabinet ST1TØ4 10L 5 pcs 3 Perform cabling of connecting cable and attach the cord clamp Fix the cord clamp by tightening the screws ST2T 4 x 14L 3 pcs fitting 2 concave parts of the cord clamp to each connecting cables 4 Attach the valve cover ST1T 4 x 10L 3 pcs Insert the upper part into the square hole of the side cabinet set hook claws of the valve cover to...

Page 92: ...t is fitted into the side cabinet left at the front left side so pull up the top of the front cabinet to remove it 2 Attachment 1 Insert the claw on the front left side into the side cabinet left 2 Hook the bottom part of the front right side onto the concave section of the bottom plate Insert the claw of the side cabinet right into the square hole in the front cabinet 3 Return the screws that wer...

Page 93: ...tor is one with mass capacity Therefore it is dangerous that a large spark generates if short circuiting between Requirement As each connector has a lock mecha nism avoid to remove the connector by holding the lead wire but by holding the connector Discharging position Discharging period 10 seconds or more Plug of soldering iron 4 Remove screw ST1T 4 x 10L 4pcs fixing the terminal part of inverter...

Page 94: ...their housing must be released before they are disconnected 2 Remove the control board assembly from the P C board base Remove the heat sink and control board assembly while keeping them screwed together NOTE Disengage the four claws of the P C board base hold the heat sink and lift to remove it 3 Remove the two fixing screws used to secure the heat sink and control board assembly 4 Mount the new ...

Page 95: ...d heat exchanger Remarks Detail A Detail B Detail C 1 Perform work of item 1 of and 2 Remove the flange nut fixing the fan motor and the propeller Flange nut is loosened by turning clock wise To tighten the flange nut turn counterclockwise 3 Remove the propeller fan 4 Disconnect the connector for fan motor from the inverter 5 Remove the fixing screws 4 pcs holding by hands so that the fan motor do...

Page 96: ...th a burner Take care to keep the 4 way valve away from naked flames Otherwise it may malfunction 7 Remove the fixing screw of the bottom plate and heat exchanger ST1TØ4 10L 1 pc 8 Remove the fixing screw of the bottom plate and valve fixing plate ST1TØ4 10L 1 pc 9 Pull upward the refrigeration cycle 10 Remove NUT 3 pcs fixing the compres sor to the bottom plate Remarks Reactor 1 Perform work of i...

Page 97: ...ng claws by pushing minus screwdriver according to the arrow mark in the right figure and remove the fan guard 2 Attachment 1 Insert claws of the fan guard in the holes of the front cabinet Push the hooking claws 9 positions by hands and fix the claws Check that all the hooking claws are fixed to the specified positions FILE NO SVM 12061 1 Detachment 1 Perform step 1 in all the steps in and 1 in 2...

Page 98: ...er positions as instructed The product will not be controlled properly and trouble will result if the sensors have not been installed in their proper positions TS sensor Suction pipe temperature sensor Attachment Install the senser onto the straight pipe part of the suction pipe Be careful for the lead direction of the sensor TD sensor Discharge pipe temperature sensor Attachment With its leads po...

Page 99: ... them 9 Wind the attached color tape round the both terminals of the protective tube when colored protective tube is used 10 Fix the sensor again Remarks 1 2 3 4 5 6 Parts name Sensor Sensor Spring A Sensor Spring B Thermal constringent tube Color tape Terminal Q ty 1 1 1 3 1 3 Cutting here Cutting here Cutting here Soldered part Dryer Winding the color tape 100 200 Connector Thermal sensor part T...

Page 100: ...tion Part Location Part No No No No 401 43T69319 TEMPERATURE SENSOR 405 43T6V316 PC BOARD ASSY WRS LED 402 43T50306 TEMPERATURE SENSOR 406 43T6V323 PC BOARD ASSY 403 43T69320 TEMPERATURE SENSOR 407 43T60378 TERMINAL 404 43T62340 CORD CLAMP 408 43T60417 TERMINAL Description Description ...

Page 101: ...205 43T20325 CROSS FLOW FAN ASSEMBLY 218 43T79313 CAP DRAIN 206 43T49010 PIPE SHIELD 219 43T44483 REFRIGERANT CYCLE ASSEMBLY 207 43T83305 HOLDER REMOTE CONTROL 221 43T00598 PANEL SERVICE ASSEMBLY 208 43T60382 MOTOR CORD 222 43T80327 FILTER AIR R 209 43T82310 INSTALLATION PLATE 223 43T80328 FILTER AIR L 211 43T19333 HOLDER SENSOR 224 43T09482 GRILLE OF AIR INLET 212 43T09408 PIPE HOLDER 226 43T6234...

Page 102: ... CUSHION 8 43T41446 COMPRESSOR 26 43T46375 4 WAY VALVE 9 43T43412 CONDENSER ASSEMBLY 27 43T63337 4 WAY VALVE COIL ASSEMBLY 10 43T46358 VALVE PACKED 6 35 DIA 28 43T63319 HOLDER SENSOR 11 43T46374 VALVE PACKED 12 7DIA H4 29 43T79305 DRAIN NIPPLE 12 43T47331 BONNET 6 35 DIA 30 43T39333 MOTOR BASE CONNECTION PLATE 13 43T47333 BONNET 12 70 DIA 31 43T63318 HOLDER SENSOR 14 43T00448 FIXING PLATE VALVE 32...

Page 103: ... Location Part Location Part No No No No 701 43T62320 HEATSINK 705 43T60377 TEMPERATURE SENSOR 702 43T69941 PC BOARD 706 43T50304 SENSOR HEAT EXCHANGER 703 43T60392 TERMINAL 5P 707 43T62313 BASE PLATE PC 704 43T60326 FUSE Description Description ...

Page 104: ... 56 FILE NO SVM 03005 TOSHIBA CARRIER THAILAND CO LTD ...

Reviews: