59
–
FILE NO. SVM-12061
<Packed valve handling precautions>
Fig. 10-4-8
•
Open the valve stem all the way out, but do not try
to open it beyond the stopper.
Cap
Torque
Pipe size of Packed Valve
Size of Hexagon wrench
12.70 mm and smallers
A = 4 mm
15.88 mm
A = 5 mm
•
Securely tighten the valve cap with torque in the
following table
Cap Size (H)
Valve Rod
Cap
Service
Port Cap
H17 - H19
H22 - H30
H14
H17
14~18 N.m
(1.4 to 1.8 kgf·m)
33~42 N.m
(3.3 to 4.2 kgf·m)
8~12 N.m
(0.8 to 1.2 kgf·m)
14~18 N.m
(1.4 to 1.8 kgf·m)
A
H
Hexagon wrench
is required.
Service Port Cap
Valve Rod Cap
10-4-5. Wiring connection
1. Remove the valve cover from the outdoor unit.
2. Connect power cord to the terminal block ,
and then connect the connecting cable to the
terminals as identified with their respective matched
numbers on the terminal block of indoor and outdoor
unit.
3. Insulate the unused cords (conductors) from any
water coming in the outdoor unit. Proceed them so
that they do not touch any electrical or metal parts.
10
30
30
40
40
10
10
10
L N
1 2 3
Connecting cable
Power cord
Connecting cable
Power cord
Terminal
block
Earth line
•
Wrong wiring connection may cause some electrical
parts burn out.
•
Be sure to comply with local cords on running the
wire from indoor unit to outdoor unit (size of wire
and wiring method, etc.).
•
Every wire must be connected firmly.
•
This installation circuit breaker must be used specified
CAUTION
for the power supply line of this air conditioner.
Fig. 10-4-9
•
If incorrect or incomplete wiring is carried out, it will
<Stripping length of the connecting cable>
cause an ignition or smoke.
•
Prepare the power supply for exclusive use with the
air conditioner.
L
•
This product can be connected to the mains.
Connection to fixed wiring: A switch which
disconnects all poles and has a contact separation
of at least 3 mm must be incorporated in the fixed wiring
N
10-4-4. Electrical work
1.
The power supply line must be supplied to outdoor
unit.
2.
The supply voltage must be the same as the rated
voltage of the air conditioner.
•
Wire type : More than H07RN-F or 60245 IEC66
NOTE
(1.5 mm
2
or more)
•
Connection to fixed wiring:
CAUTION
A switch or circuit breaker which disconnects all
3. Prepare the power source for exclusive use with the
poles and has a contact separation of at least 3 mm
air conditioner.
must be incorporated in the fixed wiring. An approved
wiring capacity.
circuit breaker or switches must be used.
•
Perform wiring works so as to allow a general
Maximum running current
Circuit breaker
Connecting cable
Power cord
11
.
0
A
1
4
.0A
More than H07RN-F or 60245 IEC66
Power source
Model RAS-
B
16N3KV
2
-E
50 Hz, 2
2
0
-240
V Single phase
6
0 Hz, 2
2
0V Single phase
(1.5 mm
2
or more)
More than H07RN-F or 60245 IEC66
(1.0 mm
2
or more)