– 24 –
Item
Operation flow and applicable data, etc.
Description
1. Basic
operation
1-5. AUTO operation
Ta: Room temp.
Ts: Setup temp.
To: Outside temp.
k = deg
1) The judgment of selecting COOL/HEAT is carried out as shown
below. When +1.5 exceeds against Tsh 10 minutes and after
thermo. -OFF, heating operation (Thermo. OFF) exchanges to
cooling operation. Description in the parentheses shows an example
of cooling ON/OFF.
When –1.5 lowers against Tsc 10 minutes and after thermo. OFF,
cooling operation (Thermo. OFF) exchanges to heating operation.
2) For the automatic capacity control after judgment of cooling/heating,
see Item 4.
3) For temperature correction of room temp. control in automatic
heating, see Item 3.
Tsc: Setup temp. in cooling
operation
Tsh: Setup temp. in heating
ope temp.
correction of room
temp. control
1-6. DRY operation
DRY operation is aimed to dehumidification.
In order to prevent lowering of the room temperature,
• Indoor fan speed is fixed to cooling L tap.
• Cooling capacity is restricted to low. When the room temperature is
lower than the setup temperature, the compressor is turned off.
Remote controller
command
Control outline
AUTO
• COOL/HEAT operation mode is
automatically selected by Ta, Ts
and To for operation.
• The operation is performed as
shown in the following figure
according to Ta value at the first
time only. (In the range of Ts +
α
–1 < Ta < Ts +
α
+ 1, Cooling
thermo. OFF (Fan)/Setup air
volume operation continues.)
•
α
is corrected according to the outside temperature.
Cooling
operation
Cooling thermo. OFF (Fan only)
• Setup air volume
+1.0
Ts +
α
Ta
(°C)
-1.0
Heating
operation
Outside temp.
Correction value (
α
)
No To
0K
To
≥
24°C
–1K
24 > To
≥
18°C
0K
To < 18°C
+1K
To error
0K
Cooling
Cooling OFF
or
Ta
(°C)
-1.5
Heating
(Cooling ON)
+1.5
Tsc
Tsh