3. Capacity
control
Operation flow and applicable data, etc.
The cooling or heating capacity depending on the load is
adjusted.
According to difference between the setup value of tempera-
ture and the room temperature, the capacity is adjusted by
the compressor revolution.
Description
1) The difference between set
temperature on remote controller
(Ts) and room temperature (Ta)
is calculated.
2) According to the temperature
difference, the correction value of
Hz signal which determines the
compressor speed is set up.
3) The rotating position and speed
of the motor are detected by the
electromotive force occurred on
the motor winding with operation
of the compressor.
4) According to the difference
resulted from comparison of the
correction value of Hz signal with
the present operation Hz, the
inverter output and the commuta-
tion timing are varied.
5) Change the compressor motor
speed by outputting power to the
compressor.
* The contents of control
operation are same in cooling
operation and heating
operation
About "Current release control", Please refer to a service manual of connected Multi outdoor unit.
Set temp. (Ts)
Room temp. (Ta)
Correction of Hz signal
Detection of electromotive force
of compressor motor winding
Detection of motor speed operation Hz
Inverter output change
Change of compressor speed
Remote controller
Indoor unit
Ts
−
Ta
Correction value of Hz signal
≤
Operating Hz
and rotor position
Current
release control
Correction of Hz signal
Inverter output change
Commutation timing change