• After checking the draining, wrap the supplied thermal insulation
material for the drain connecting part around the flexible hose
leaving no clearance from the root of the drain pipe connecting
port of the indoor unit.
• Wrap the thermal insulation material (procured locally) around
the drain pipe so that it piles up on the supplied the thermal
insulation material for the drain connecting part, leaving no
clearance.
Thermal insulating process
CAUTION
Ensure water is poured slowly.
If water is poured vigorously, it is scattered inside of the indoor unit resulting in a cause of unit trouble.
Flexible hose
Attached heat insulator
Hose band
Heat insulator to be
procured locally
Hard vinyl chloride pipe
Drain pan
Air discharge
area
Check panel
Insert the leading part of
the hose between the
heat exchanger and the
drain pan, and then bend
it downward.
Polyethylene hand pump for
pouring water in drain pan
Vessel
Water (1500cc to 2000cc)