background image

6

EN

• A place which provides enough space around the outdoor 

unit as shown in the diagram.

• A place which can bear the weight of the outdoor unit and 

does not allow an increase in noise level and vibration.

• A place where the operation noise and discharged air do not 

disturb neighbors.

• A place which is not exposed to a strong wind.
• A place free of combustible gases.
• A place which does not block a passageway.
• When the outdoor unit is to be installed in an elevated 

position, be sure to secure its feet.

• Piping connections to the outdoor unit should be arranged in 

the sequence A, then B, starting from the bottom. (For each 
piping connection, the gas pipe is on the bottom and the 
liquid pipe on top.)

• When multiple indoor units are to be connected to the 

outdoor unit, make sure the ends of the pipes and wires from 
each indoor unit are connected to the outdoor unit correctly. 
(Problems caused by indoor units being connected to the 
outdoor unit incorrectly are very common in multiple-unit 
installations.)

• The length and height differences of the connecting pipes, 

between the indoor and outdoor units, must be within the 
ranges indicated below.
• Total piping length:

Two room (A+B) Multi 
• This air conditioner accepts a connection piping length 

of up to 30 m.
• There is no need to add refrigerant as long as the 

length of the connection piping is 20 m or less.

• You will need to add 20 g of refrigerant per meter of 

added connection piping for installations requiring 
connection piping to be between 21 m to 30 m.

• Minimum piping length:

A or B = 2 m or more

• Maximum indoor piping length: 

A or B = 20 m or less

• Maximum piping height difference: 

A or B = 10 m or less

• Maximum piping / height difference

between two rooms = 10 m or less

• If the outdoor unit is to be mounted on a wall, make sure the platform supporting it is sturdy enough. 

The platform should be designed and manufactured to maintain its strength over a long period of time, and sufficient consideration 
should be given to ensuring that the outdoor unit will not fall. 

• When the outdoor unit is to be mounted high on a wall, take particular care to ensure that parts do not fall, and that the installer is 

protected.

• When doing installation work at ground level, it is usual to make wiring and pipe connections to the indoor units, first, and then to 

make connections to the outdoor unit.  
However, if outdoor work is difficult it is possible, instead, to make changes to the procedure. 
For example, by making adjustments to the wiring and piping lengths on the inside (rather than the outside).

• A place where the drain water does not cause any problems.
• The outdoor unit should not be installed with one indoor unit only. Be sure the (outdoor) unit is installed with at least two indoor 

units.

Precautions for Adding Refrigerant

• Use a scale having a precision with at least 10 g per index line when adding the refrigerant. Do not use a bathroom scale or similar 

instrument.

• Use liquid refrigerant when refilling the refrigerant. Since the refrigerant is in liquid form, it can fill quickly. Therefore, perform the 

filling operation carefully and insert the refrigerant gradually.

4 INSTALLATION OF OUTDOOR UNIT

Installation Location

100 mm or

more from

wall

Extension drain hose
(Option: RB–821SW)

80 mm or more only 
when unobstructed to 
the front and both sides

250 mm or 
more from wall

200 mm or more

50 mm or more 
from wall

In principle,

leave open

When installing the 
outdoor unit, leave open 
in at least two of 
directions (A), (B), (C) 
and (D) shown in the 
right figure.

Ensure sufficient space 
to allow drainage

(A)

(B)

(C)

(D)

power cord

As shown in the 
figure, position 
power cord and 
connecting 
cable 
downward, and 
lead out along 
piping 
connection port.

Installation diagram of 
outdoor units

10

 m o

les

s

Outdoor 

unit

OutdoorInstallation.book  Page 6  Wednesday, February 1, 2006  9:12 AM

Summary of Contents for RAS-M14GACV-E

Page 1: ...ΟΝΑ Α ΠΟΛΛΑΠΛΟΥ ΤΥΠΟΥ Για γενική δηµόσια χρήση КОНДИЦИОНЕР МУЛЬТИ РАЗДЕЛИТЕЛЬНОГО ТИПА Для общего бытового использования Outdoor Unit Unité extérieure Außengerät Unità esterna Unidad exterior Unidade exterior Εξωτερική µονάδα Наружный блок RAS M14GAV E RAS M18GAV E RAS M14GACV E RAS M18GACV E Please read this installation manual carefully before installing the air conditioner Veuillez lire attenti...

Page 2: ...SOBRE SEGURIDAD 1 2 PARTES OPCIONALES ACCESORIOS Y HERRAMIENTAS 3 3 QUÉ MODELOS PUEDEN COMBINARSE 5 4 INSTALLATION DE LA UNIDAD EXTERIOR 6 5 CONEXIÓN A TIERRA 11 6 COMPROBACIÓN Y OPERACIÓN DE PRUEBA 11 7 FUNCIÓN PRÁCTICA 12 1 PRECAUÇÕES DE SEGURANÇA 1 2 PEÇAS OPCIONAIS ACESSÓRIOS E FERRAMENTAS 3 3 MODELOS QUE PODEM SER COMBINADOS 5 4 INSTALAÇÃO DA UNIDADE EXTERIOR 6 5 LIGAÇÃO À TERRÀ 11 6 VERIFICA...

Page 3: ...dust former refrigerant or refrigeration machine oil does not enter into the new type refrigerant R410A air conditioner circuit To prevent mixing of refrigerant or refrigerating machine oil the sizes of connecting sections of charging port on main unit and installation tools are different from those used for the conventional refrigerant units Accordingly special tools are required for the new refr...

Page 4: ...L CAUSE AIR ETC TO BE SUCKED IN RAISING THE PRESSURE INSIDE THE REFRIGERATION CYCLE TO AN ABNORMALLY HIGH LEVEL AND POSSIBLY RESULTING IN RUPTURING INJURY ETC WHEN CARRYING OUT THE PUMP DOWN WORK SHUT DOWN THE COMPRESSOR BEFORE DISCONNECTING THE REFRIGERANT PIPE DISCONNECTING THE REFRIGERANT PIPE WITH THE SERVICE VALVE LEFT OPEN AND WITH THE COMPRESSOR STILL OPERATING WILL CAUSE AIR ETC TO BE SUCK...

Page 5: ...utdoor unit Secure the outdoor unit with the attachment bolts and nuts if the unit is likely to be exposed to a strong wind Use φ8 mm or φ10 mm anchor bolts and nuts If it is necessary to drain the defrost water attach drain nipple to the base plate of the outdoor unit before installing it Accessory and Installation Parts Part No Part name Q ty Part No Part name Q ty a Outdoor unit installation ma...

Page 6: ...rs have been changed Charge hose In order to increase pressure resisting strength hose materials and port sizes have been changed to 1 2 UNF 20 threads per inch When purchasing a charge hose be sure to confirm the port size Electronic balance for refrigerant charging As working pressure is high and gasification speed is fast it is difficult to read the indicated value by means of charging cylinder...

Page 7: ...10GKCV E RAS M13GKCV E RAS M16GKCV E RAS M10GDCV E RAS M13GDCV E RAS M16GDCV E Type Outdoor unit Combinations of indoor unit models that can be connected Heat pump RAS M14GAV E 10 10 10 13 RAS M18GAV E 10 10 10 13 10 16 13 13 Cooling only RAS M14GACV E 10 10 10 13 RAS M18GACV E 10 10 10 13 10 16 13 13 NOTES A 1 room connection is not an option for the indoor units you cannot connect only one indoo...

Page 8: ...s sturdy enough The platform should be designed and manufactured to maintain its strength over a long period of time and sufficient consideration should be given to ensuring that the outdoor unit will not fall When the outdoor unit is to be mounted high on a wall take particular care to ensure that parts do not fall and that the installer is protected When doing installation work at ground level i...

Page 9: ...he drain nipple c is installed refer to the installation diagram of the indoor and outdoor units Check that the outdoor unit is horizontal and route the drain hose at a downward sloped angle while ensuring that it is connected tautly CAUTION 1 Install the outdoor unit without anything blocking the discharging air 2 When the outdoor unit is installed in a place always exposed to strong winds like o...

Page 10: ...rigerant Piping Connection Outer diameter of copper pipe R410A tool used Conventional tool used 6 35 0 to 0 5 1 0 to 1 5 9 52 0 to 0 5 1 0 to 1 5 12 7 0 to 0 5 1 0 to 1 5 Outer diameter of copper pipe R410A 6 35 1 5 to 2 0 9 52 1 5 to 2 0 12 7 2 0 to 2 5 Outer diameter of copper pipe B R410A R22 6 35 9 1 9 0 9 52 13 2 13 0 12 7 16 6 16 2 CAUTION Do not apply excessive force Otherwise the nut may b...

Page 11: ...15 minutes if the piping length is 20 meters 15 minutes for 20 meters assuming a pump capacity of 27 liters per minute Confirm that the compound pressure gauge reading is 101 kPa 76 cmHg 5 Close the low pressure valve handle of gauge manifold 6 Open fully the valve stem of the packed valves both sides of Gas and Liquid 7 Remove the charging hose from the service port 8 Securely tighten the caps on...

Page 12: ...reaker or fuse all types can be used Power cord H07RN F or 60245IEC66 1 5 mm2 Connecting cable H07RN F or 60245IEC66 1 0 mm2 CAUTION Incorrect wiring connection may cause electrical parts to burn out Be sure to comply with local regulations codes when running the wire from outdoor unit to indoor unit Size of wire and wiring method etc Every wire must be securely connected If incorrect or incomplet...

Page 13: ...rotective devices specified in this manual Insulate the unused cords conductors with PVC tape 1 Turn on the electrical power breaker 2 Operate the indoor unit in cooling mode 3 Start checks Run the indoor unit in room A and confirm cool air blows out Confirm the indoor unit in room B is not running Also check at this time that refrigerant which can be heard is not flowing Stop operation of the ind...

Page 14: ... running None IGBT short circuit Compressor motor rear short 14 Trouble on position detecting circuit 16 Trouble on current detecting circuit 17 CONDENSOR PIPE TEMPERATURE SENSOR TE fault 18 SUCTION PIPE TEMPERATURE SENSOR TS fault 18 DISCHARGE PIPE TEMPERATURE SENSOR TD fault 19 Trouble on outdoor fan 1A OUTDOOR TEMPERATURE SENSOR TO fault 1B Trouble on compressor system 1C GAS SIDE PIPE TEMPERAT...

Page 15: ...EG32906701 a 00_OutdoorInstallation_BCO fm Page 2 Wednesday February 1 2006 10 54 AM ...

Reviews: