-16-
7.3
Cooling capacity
RAV-132AH-PE
RAV-162AH-PE
Indoor Unit
Outdoor Unit
Heating Capacity Ratio
Piping Length (m)
Cooling Capacity Ratio
Piping Length (m)
Outdoor Unit Height H (m)
Outdoor Unit Height H (m)
7.4 Piping length/additional refrigerant volume
45
5
0.95
Recharge quantity (kg)
30
1.55
25
1.35
Additional amount of refrigerant
at installation site (kg)
40
50
20
1.20
20
Filled at
factory
Piping length
less than (m)
Model
30
30
RAV-132AH-PE
l
The amount of refrigerant put into the outdoor unit at the factory is equivalent to that which fills up 20m length of refrigerant pipe.
l
If the length of refrigerant pipe is 20m or less, addition of refrigerant at the installation site is unnecessary. If the length of the pipe
exceeds 20m, add the refrigerant R-22.
l
Overcharge or undercharge of refrigerant in the outdoor unit will cause malfunction of the compressor. The prescribed amount of
the replenishment of the refrigerant is shown in the table above.
The permissible amount of refrigerant is the prescribed amount ±50g.
Filled at
factory
RAV-162AH-PE
35
30
0.35
25
0.15
0.15
0.35
10
1.05
15
1.10
1.35
1.45
1.50
1.60
1.75
1.95