-35-
4.11 RAV-132UH-PE, RAV-162UH-PE, RAV-262UH-PE
No.
PARTS NAME
TYPE
SPECIFICATIONS
1
Indoor unit fan motor
SMF-230-45A
Output (Rated) 45W, 6 pole, 1 phase, 230V, 50Hz
2
Running capacitor for indoor
fan motor
EVM45M305UF
AC 400V, 2.5µF
3
Transformer for
Indoor unit
ST-9586
AC187~264V
4
Relay
LY2F
AC240V, 2ab
5
Geared motor
MT8-3-3
AC 240V, 3W
6
Drain pump
PAD-416A34TF
AC230V, 0.2A
7
Float switch
FS-085-003B
AC230V, 0.5A
8
Sensor for room temperature
Maximum input
38mA
°C
15
20
25
30
40
16.1
12.6
10.0
8.0
5.2
9
Indoor unit sensor for heat-
exchanger temp.
DTN-C103J40
Maximum input
34mA
°C
–12
0
25
50
62.29 32.82
10.0
3.59
4.12 RAV-362UH-PE
4.13 RAV-462UH-PE
K
W
K
W
K
W
K
W
K
W
K
W
No.
PARTS NAME
TYPE
SPECIFICATIONS
1
Indoor unit fan motor
SMF-230-90-4A Output (Rated) 90W, 6 pole, 1 phase, 230V, 50Hz
2
Running capacitor for indoor
fan motor
EEP2G405HQ1
AC 400V, 4µF
3
Transformer for
Indoor unit
ST-9586
AC187~264V
4
Relay
LY2F
AC240V, 2ab
5
Geared motor
MT8-3-3
AC 240V, 3W
6
Drain pump
PAD-416A34TF
AC230V, 0.2A
7
Float switch
FS-085-003B
AC230V, 0.5A
8
Sensor for room temperature
Maximum input
38mA
°C
15
20
25
30
40
16.1
12.6
10.0
8.0
5.2
9
Indoor unit sensor for heat-
exchanger temp.
DTN-C103J40
Maximum input
34mA
°C
–12
0
25
50
62.29 32.82
10.0
3.59
No.
PARTS NAME
TYPE
SPECIFICATIONS
1
Indoor unit fan motor
SMF-230-90-4A Output (Rated) 90W, 6 pole, 1 phase, 230V, 50Hz
2
Running capacitor for indoor
fan motor
EVM45M305UF
AC 450V, 3µF
3
Transformer for
Indoor unit
ST-9586
AC187~264V
4
Relay
LY2F
AC240V, 2ab
5
Geared motor
MT8-3-3
AC 240V, 3W
6
Drain pump
PAD-416A34TF
AC230V, 0.2A
7
Float switch
FS-085-003B
AC230V, 0.5A
8
Sensor for room temperature
Maximum input
38mA
°C
15
20
25
30
40
16.1
12.6
10.0
8.0
5.2
9
Indoor unit sensor for heat-
exchanger temp.
DTN-C103J40
Maximum input
34mA
°C
–12
0
25
50
62.29 32.82
10.0
3.59
Heronhill - for all your Toshiba requirements
Tel: 01823 665660
www.heronhill.co.uk
Fax: 01823 665807