-61-
N
ITEM
OUTLINE OF SPECIFICATIONS
REMARKS
14 Low ambient
cooling
<Outdoor unit
control>
15 Check display
See other item:
Using [TIME]
display
16 Anti-restart timer
17 Group
operation
control
- 1 0
TL sensor
+1 wave,–1 wave is
(current number of waves)
± (1 wave)
Air quantity “M”
automatic control
Timer accuracy: 20
sec.
+ 0
1 minute and 30
sec.
- 1 0
+ 0
Fault diagnosis is carried out by check for serial transmission and reception
with outdoor unit as well as the self check by indoor microcomputer. And check
code is transmitted to protective operation/remote controller based on the
contents of it.
In the remote controller, check code is displayed on the liquid crystal by
pressing [CHECK] key.
Up to 16 units can be controlled in same setting condition by one remote
controller.
However, thermo-control function is independent.
Respective delayed start time for preventing simultaneous large starting current
can be obtained by different setting of the unit No. switch on the indoor PC
board.
Air quantity
A Zone
H
B Zone Per 1 minute and 30
sec. +1 wave
C Zone Maintain
D
Zone
Per 20 sec. 1 wave
–
14-1 Control on outdoor fan is made
14-1
to meet with cooling at low outdoor
14-1
temperature based on outdoor heat
14-1
exchange temperature TL.
14-2 Control by outdoor heat
14-2
exchange temperature TL
14-2
is illustrated on the right.
14-3 For first 2 minutes after starting
14-3
cooling operation the fan(s)
14-3
operate in “H” speed.
The outdoor unit delays restarting for 2 mins 20s to prevent short cycling
compressor operation.
Unit NO.
Check
code