– 43 –
7-4. Optional connector specifications of indoor P.C. board
sk
ra
me
R
s
n
oit
aci
fi
ce
p
S
.
o
N
ni
P
.
o
N r
ot
ce
n
n
o
C
n
oit
c
n
u
F
Ventilation output
CN32
1
DC12V
Setting at shipment: Interlock of ON by indoor unit operation, with OFF by stop operation
∗
The single operation setting by FAN button on the remote controller is performed on the remote controller (DN [31] = 0000
→
0001)
2
Output (Open collector)
FILTER Option trouble / Humidifier setting (
∗
)
CN70
10
V
Selection of option trouble input (Protective operation display of device attached to outside) or Humidifier setting input (Vapo Drain pump ON) Humidifier is set at shipment from factory.
∗
Setting of option trouble input is performed on the remote controller. (DN [2A] = 0002
→
0001)
2
16
N
C
A
H
1
2
3
4
5
6
ON/OFF input
0V
Remote controller prohibited input
Operation output (Open collector)
DC12V
Warning output (Open collector)
HA ON/OFF input (J01: YES/NO=Pulse (At shipment from factory) /Static input selection)
Permission/Prohibition of remote controller operation stop is performed by input.
Operation ON (Answer back of HA)
Warning output ON
Option output
CN60
1
2
3
4
5
6
DC12V
Defrost output (Open collector)
Thermostat ON output (Open collector)
Cooling output (Open collector)
Heating output (Open collector)
Fan output (Open collector)
ON when outdoor unit is defrosted
ON when real thermostat is on. (Compressor ON)
ON when operation mode is cooling system (COOL, DRY, Cooling/Heating automatic cooling)
ON when operation mode is heating system (HEAT, Cooling/Heating automatic heating)
ON when indoor fan is on. (When air cleaner is used) OFF while clean operation is performed.
Outside trouble input
CN80
1
2
3
DC12V
NC
Outside trouble input
Generate the check code “L30” (continuously for 1 minute) and stop the operation forcibly.
CHK Operation check
CN71
1
2
0V
This check is used to check indoor operation. (Performs operation of indoor fan gH h, Louver horizontal and Drain pump ON without communication with outdoor and remote controller)
DISP Exhibition mode
CN72
1
2
0V
Communication is available by indoor unit and remote controller only.
EXCT Demand
CN73
1
2
0V
Indoor unit forced thermostat OFF operation
∗
This o
ption is not
provided to oversea models.