1. SPECIFICATIONS
1-1. Outdoor Unit
<Digital Inverter>
Model name
Outdoor unit
RAV-
G
M
1601
AT
*
P
*
Power supply
1 phase 220-240V, 50Hz
1 phase 220V, 60Hz
(Power exclusive to outdoor is required.)
Compressor
Type
Hermetic compressor
Motor
(kW)
3.75
Pole
4
Refrigerant charged
(kg)
2.4
Refrigerant control
Pulse motor valve
Inter
connecting pipe
Standard length
(m)
7.5
Min. length
(m)
5
Max. total length
(m)
50
Additional refrigerant charge
under long piping connector
35
g/m
(
3
1m to
5
0m)
Height
difference
Outdoor lower
(m)
30
Outdoor higher
(m)
30
Outer dimension
Height
(mm)
1340
Width
(mm)
900
Depth
(mm)
320
Appearance
Silky shade (Muncel 1Y8.5/0.5)
Total weight
(kg)
95
Heat exchanger
Finned tube
Fan unit
Fan
Propeller fan
Standard air flow high
(m3/min.)
115
Motor
(W)
100+100
Connecting pipe
Gas side
(mm)
1
5.9
Liquid side
(mm)
6.4
Sound pressure level
Cooling/Heating (dB·A)
53/55
Sound power level
Cooling/Heating (dB·A)
70/72
Outside air temperature, Cooling
°C (Dry bulb temp.)
46 to -15
Outside air temperature, Heating
°C (Wet bulb temp.)
15 to -15
- 17 -