Central Control indication
Remote Controller indication
Sensor lamp part
Defected position
Detection
Explanation of error contents
Automatic
Reset
Operation continuation
Block indication
Operation Timer Ready
Flash
4B
E11
◎
● ●
Communication error between Application control kit and indoor unit
Indoor
Communication error between Application control kit and indoor unit P.C. board
○×
97,99
E18
◎
● ●
Regular communication error between master and follower indoor units
Indoor
Regular communication cannot be performed between master and follower indoor units. Communication between twin master (Main unit) and follower (sub unit) cannot be performed.
○×
96
L03
◎
● ◎
SIM
Duplicated indoor master units
Indoor
There are multiple master units in a group.
××
99
L07
◎
● ◎
SIM
There is group cabl
e i
n individual indoor u
nit.
Indoor
When even one group connection indoor unit exists in individual indoor unit
××
99
L08
◎
● ◎
SIM
Unset indoor group a
dd
re
ss
Indoor
Indoor address group was unset.
××
46
L09
◎
● ◎
SIM
Unset indoor capacity
Indoor
Capacity of indoor unit was unset.
××
66
L30
◎
○ ◎
SIM
Outside error input to indoor unit (Interlock)
Indoor
Abnormal stop by CN80 outside error input
××
08
P19
◎
● ◎
ALT
4-way valve inverse error
Indoor Outdoor
In heating operation, error was detected by temp. down of indoor heat exchanger or temp. up of TE, TS.
○×
When this warning was detected before group construction/address check finish at power supply was turned on, the mode shifts au
tomatically to AUTO address setup mode.