Error mode detected by remote controller or central controller (TCC-LINK)
∗
1 The check code cannot be displayed by the wired remote controller.
(Usual operation of air conditioner becomes unavailable.)
For the wireless models, an error is notified by indication lamp.
∗
2 This trouble is related to communication of remote controller (A, B), central system (TCC-LINK U3, U4),
and [E01], [E02], [E03], [E09] or [E18] is displayed or no check display on the remote controller according
to the contents.
Operation of diagnostic function
Check code
Not displayed at all
(Operation on
remote controller
cannot be operated.)
E01
∗
1
E02
E09
L20
Central controller
L20
—
∗
2
Central controller
(Send)
C05
(Receive)
C06
—
Central controller
P30
Remote controller wiring is not correct.
Power of indoor unit is not turned on.
Automatic address cannot be completed.
No communication with master indoor unit
Disconnection of inter-unit wire between
remote controller and master indoor unit
(Detected by remote controller side)
Signal send error to indoor unit
(Detected by remote controller side)
There are multiple main remote controllers.
(Detected by remote controller side)
Duplicated indoor central addresses on
communication of central control system
(Detected by indoor/central controller side)
Communication circuit error of central
control system
(Detected by central controller side)
Indoor Gr sub unit error
(Detected by central controller side)
Status of
air conditioner
Stop
∗
If center exists,
operation continues.
∗
If center exists,
operation continues.
Stop
(Sub unit
continues operation.)
Continues
(By remote controller)
Continuation/Stop
(According
to each case)
Condition
—
Displayed when
error is detected
Displayed when
error is detected
Displayed when
error is detected
Displayed when
error is detected
Displayed when
error is detected
Displayed when
error is detected
Judgment and measures
Power supply error of remote controller, Indoor
EEPROM error
1. Check remote controller inter-unit wiring.
2. Check remote controller.
3. Check indoor power wiring.
4. Check indoor P.C. board.
5. Check indoor EEPROM.
(including socket insertion)
→
Automatic address repeating phenom-
enon generates.
Receiving error from remote controller
1. Check remote controller inter-unit wiring.
2. Check remote controller.
3. Check indoor power wiring.
4. Check indoor P.C. board.
Error sending of remote controller
1. Check sending circuit inside the remote
controller.
→
Replace remote controller.
1. In 2-remote controllers (including wireless),
there are multiple main units.
Check that there are 1 main remote
controller and other sub remote controllers.
1. Check setting of central control system
network address. (Network adapter SW01)
2. Check network adapter P.C. board.
1. Check communication wire / miswiring
2. Check communication (U3, U4 terminals)
3. Check network adapter P.C. board.
4. Check central controller (such as central
control remote controller, etc.)
5. Check terminal resistance. (TCC-LINK)
Check the check code of the corresponding
unit from remote controller.
Cause of errors
Stop
(Automatically reset)
Stop
(Automatically reset)
Stop
(Automatically reset)
No communication with master indoor unit