Check
code
Outdoor
LED display
Check and troubleshooting
(Item without special mention Indicates part of outdoor unit.)
[L29]
[Communication trouble MCUs]
[L10]
[Heat sink temp. sensor (TH) trouble]
Cut jumper line according
to the explanation sheet packaged
with the service P.C. board.
[P03]
[Discharge temp. trouble]
Is there gas leak?
Is there refrigerant shortage?
NO
Replace the PMV.
Replace TD sensor.
YES
Remove and improve
the cause of overload.
NO
Check outdoor P.C. board.
Failure
→
Replace
NO
Fault part repair.
Recharge refrigerant.
Is connection of CN603 correct?
Is resistance value of TD sensor correct?
YES
NO
Is PMV normal?
YES
YES
Does an abnormal overload happen?
YES
Confirmation of
electrical work etc.
Does the supply voltage drop or rise
(AC198 to 264V)?
[P05]
[Powersupply trouble] Voltage failure
Check the same items as [P04] trouble.
Check outdoor P.C.board
Failure
→
Replace
NO
Check outdoor P.C.board
Failure
→
Replace