– 53 –
Outline of troubleshooting
The primary judgment to check whether a trouble occurred in the indoor unit or outdoor unit is carried out with
the following method.
Method to judge the troubleshooting by flashing indication on indoor unit lamp display
(the signal receiving unit of wireless remote controller)
When the protective function operates the self-diagnosis contents appear in flashing indication on indoor unit
lamp display.
: Go off,
: Go on,
: Flash (0.5 sec.)
Lamp indication
Operation Timer
Ready
No indication at all
Operation Timer
Ready
Flash
Operation Timer
Ready
Flash
Operation Timer
Ready
Alternate flash
Operation Timer
Ready
Alternate flash
Check code
—
E01
E02
E03
E08
E09
E10
E18
E04
P01
P10
P12
P03
P04
P05
P07
P15
P19
P20
P22
P26
P29
P31
Cause of trouble occurrence
Power supply OFF or miss-wiring between receiving unit and indoor unit
Receiving trouble
Receiving unit
Miss-wiring or wire connection trouble
Sending trouble
Communication stop
between receiving unit and indoor unit
Duplicated indoor unit No.
Setup trouble
Duplicated header units of remote controller
Communication trouble between CPUs on indoor unit P.C. board
Wire connection trouble between indoor units, Indoor power OFF
(Communication stop between indoor header and follower or between header
and follower indoor twin)
Miss-wiring between indoor unit and outdoor unit or connection trouble
(Communication stop between indoor and outdoor units)
Overflow was detected.
Protective device of indoor unit worked.
Indoor DC fan trouble
Outdoor unit discharge temp. trouble
Protective device of
∗
1
Outdoor high pressure system trouble
outdoor unit worked.
Negative phase detection trouble
Heat sink overheat trouble
Outdoor unit trouble
Gas leak detection trouble
4-way valve system trouble (Indoor or outdoor unit judged.)
Outdoor unit high pressure protection
Outdoor unit: Outdoor unit trouble
Protective device of
Outdoor unit: Inverter Idc operation
∗
1
Outdoor unit: Position detection trouble
outdoor unit worked.
Stopped because of trouble of other indoor unit in a group
(Check codes of E03/L03/L07/L08)