– 58 –
:Go on, : Flash, : Go off
ALT (Alternate): Alternate flashing when there are two flashing LED SIM (Simultaneous): Simultaneous flashing when there are tw
o flashing LED
Remote
controller
indication
Sensor lamp part
Block indication
Operation
Timer
Ready
Flash
Representative trouble position
Detection
Explanation of trouble contents
Automatic
reset
Operation
continuation
L20
LAN system communication trouble
Duplicated indoor address of central control system communication
SIM
Network adapter/
Center
O
×
P01
Indoor unit Indoor fan trouble
ALT
Indoor
Indoor AC fan trouble was detected. (Fan thermal relay worked.)
××
F29
Indoor unit Other indoor P.C. board trouble
SIM
Indoor
EEPROM trouble (Other trouble may be detected. If no trouble, automatic address is repeated.
××
F10
Indoor unit Room temp. sensor (TA) trouble
ALT
Indoor
Open/Short of room temp. (TA) was detected.
O
×
F01
Indoor unit Heat exchanger sensor (TCJ) trouble
ALT
Indoor
Open/Short of heat exchanger (TCJ) was detected.
O
×
F02
Indoor unit Heat exchanger sensor (TC) trouble
ALT
Indoor
Open/Short of heat exchanger (TC) was detected.
O
×
—
—
There are multiple communication adapters.
Network adapter
There are multiple communication adapters on remote controller commu
nication line.
OO
—
By unit with warning No.
Trouble in indoor group
ALT
Network adapter
Sub remote controller trouble in a group
(Details of remote controller are displayed with unit No. Only central control side is displayed.)
——
—
—
LAN system communication trouble
Network adapter/
Center
Communication trouble of central control system signal
∗
Is not displayed on the remote controller
OO
P31
Other indoor unit trouble
ALT
Indoor
Other indoor under condition of warning in group. E03/L07/L03/L08 warning
O
×
P12
Indoor unit Indoor fan trouble
ALT
Indoor
Indoor fan trouble (Over-current / Lock, etc.) was detected.
××
P10
Indoor unit Overflow detection
ALT
Indoor
Float switch worked.
××