– 65 –
Check
code
Outdoor
LED display
Check and troubleshooting
(Item without special mention Indicates part of outdoor unit.)
[F15]
[Miss-wiring of heat exchanger sensor (TE, TS)]
Is mounting status of
TE and TS sensors correct?
NO
Correct sensor mounting.
NO
Correct connector.
Replace TS sensor
[F31]
[EEPROM trouble]
YES
Is connection of CN600 correct?
Is resistance value of TS sensor correct?
YES
NO
Correct connector.
Replace TE sensor
Replace Interface
P.C. board.
Replace Interface
P.C. board.
Replace Interface
P.C. board.
Is connection of CN601 correct?
Is resistance value of TE sensor correct?
YES
[F23]
[Low pressure sensor (PS) trouble]
Is the PS sensor connector
correct connected?
NO
Connector connection
correction
(PS sensor: CN 606)
NO
NO
Replace PS sensor
Check
compressor
YES
Is the PS sensor output voltage
characteristic normal?
Is the low pressure
during compressor
operation 1.45 MPa
or less?
NO
Is not the refrigerant
bypassing from
discharge to suction
by the 4-way valve?
YES
YES
Replace 4-way valve
YES