– 75 –
Check
code
Outdoor
LED display
Check and troubleshooting
(Item without special mention Indicates part of outdoor unit.)
[P22]
[Fan system trouble]
NO
Replace fan motor.
Replace fuse.
Check wiring construction.
Ask repair of power supply.
Replace fan motor
IPDU P.C.board
Is power supply voltage normal?
AC342 to 457V
NO
Is not the fuse (near the terminal block)
blows?
NO
YES
YES
YES
Rotate shaft of the fan motor by hands
during power-OFF. Can it rotate smoothly?
Is coil resistance of fan motor correct?
Between red and white lead wire : 12 to 20
Ω
Between white and black lead wire : 12 to 20
Ω
Between black and red lead wire : 12 to 20
Ω
[Confirmation of independent operation of outdoor fan]
Service switches SW01 and SW02 can be used to check the operation of the
4-way valve relay.
Use to check whether there are any problems with the 4-way valve or
4-way valve coil.
[Method of operation]
1) Ensure that D800 to D804 are off (or rapidly flashing) and that D805 is
lit up. If D800 to D804 are slowly flashing or D805 is flashing then please
push and hold down SW01 and SW02 at the same time for at least 5 seconds.
D800 to D804 will turn off (or rapidly flash) and D805 turn on.
2) Push and hold down SW01 for at least 5 seconds. D804 will start slowly flashing.
3) Push SW01 until reaching the below [Confirmation of independent operation
of outdoor fan] LED indication.
4) Push SW02 until D805 starts rapidly flashing.
5) Push and hold down SW02 for at least 5 seconds. D804 will start slowly
flashing, D805 will turn on, and fan will start operation.
6) Push and hold down SW01 and SW02 at the same time for at least
5 seconds or wait 2 minutes until fan operation stops.
∗
If any unclear point arises during an operation, press and hold down SW01
and SW02 at the same time for at least 5 seconds to return to step 1).
D800
Confirmation of independent
operation of outdoor fan
D801
D802
D803
D804
: Go OFF : Go ON : Flash (5 times/sec)