– 95 –
10-4. Address Setup (Manual setting from remote controller)
(Example of 2-lines wiring)
(Real line: Wiring, Broken line: Refrigerant pipe)
For the above example, perform setting by
connecting singly the wired remote controller
without remote controller group wiring.
Group address
Individual :
0000
Master
unit
:
0001
Sub unit
: 0002
In case of group control
Outdoor
Indoor
A B
A B
1 2 3
Indoor
A B
1 2 3
Indoor
A B
1 2 3
Indoor
A B
1 2 3
1 2 3
Outdoor
1 2 3
Remote controller
Line address
→
1
Indoor unit address
→
1
Group address
→
1
1
2
2
2
1
2
2
2
2
<Operation procedure>
1 2 3 4 5 6 7 8 9 10 11
END
1
3, 6, 9
END
11
2, 5, 8
4, 7, 10
SET
TIME
TIMER SET
TEST
FILTER
RESET
TEMP.
CL
FAN
SAVE
SWING/FIX
VENT
MODE
ON / OFF
UNIT LOUVER
In case that addresses of the indoor units will be
determined prior to piping work after wiring work
• Set an indoor unit per a remote controller.
• Turn on power supply.
1
Push + + buttons simultaneously for 4
seconds or more.
2
(
←
←
←
←
←
Line address)
Using the temperature setup
/
buttons,
set the CODE No. to
12
12
12
12
12
.
3
Using timer time
/
buttons, set the line address.
4
Push button. (OK when display goes on.)
5
(
←
←
←
←
←
Indoor unit address)
Using the temperature setup
/
buttons, set the CODE No. to
13
13
13
13
13
.
6
Using timer time
/
buttons, set the line address to 1.
7
Push button.
(OK when display goes on.)
8
(
←
←
←
←
←
Group address)
Using the temperature setup
/
buttons, set the CODE No. to
14
14
14
14
14
.
9
Using timer time
/
buttons, set Individual to
0000
0000
0000
0000
0000
, Header unit to
0001
0001
0001
0001
0001
, and Follower
unit to
0002
0002
0002
0002
0002
.
10
Push button. (OK when display goes on.)
11
Push button.
Setup completes. (The status returns to the usual stop status.)