Check
code
Outdoor
LED display
Check and troubleshooting
(Item without special mention Indicates part of outdoor unit.)
–
5
6
–
SVM-13072.indb 60
SVM-13072.indb 60
11/01/13 1:53 PM
11/01/13 1:53 PM
Is setting of group address
on the remote controller correct?
Check outdoor P.C. board.
Defect
→
Replace
Are inner wiring of the indoor unit
and inter-unit wires (1, 2, 3) correct?
Is wiring of the
outdoor terminal block correct?
Correct wiring
and inter-unit wires.
Check item code [14].
Correct wiring
of terminal block.
Does the case thermo operate?
Is the compressor abnormally heated?
Check and correct charged
refrigerant amount.
YES
YES
YES
NO
NO
NO
NO
YES
[E04]
—
[Indoor / Outdoor communication error]
FILE NO. SVM-18042
-1
[F04]
[F06]
[Discharge temp. sensor (TD) error]
Heat exchanger temp. sensor (TE) error]
Is
CN6
1
connection
correct?
Is resistance value of TE sensor correct?
Correct connector.
Sensor error
→
Replace
Check outdoor P.C. board.
Defect
→
Replace
YES
NO
Is CN6
2
connection correct?
Is resistance value of TD sensor correct?
Correct connector.
Sensor error
→
Replace
Check outdoor P.C. board.
Defect
→
Replace
YES
NO
—
—