Check
code
[H03]
Outdoor
LED display
Check and troubleshooting
(Item without special mention Indicates part of outdoor unit.)
[Current detection circuit error]
Check outdoor P.C. board.
Defect
→
Replace
[L10]
[Unset model type] :
Only when service P.C. board is used
Cut jumper line according to the explanation
sheet packaged with the service P.C. board.
Check outdoor P.C. board.
Defect
→
Replace
Correct connector.
Sensor error
→
Replace
Repair defective position.
Replace defective part.
Repair defective position.
Recharge refrigerant.
Does an abnormal overload happen
Is CN601 connection correct?
Is resistance value of TD sensor correct?
Is there gas leak?
Is there refrigerant shortage?
YES
NO
NO
YES
NO
NO
YES
YES
[Discharge temp. error]
[P03]
Is PMV under correct condition
Remove and improve the
cause of overload.
–
5
9
–
SVM-13072.indb 64
SVM-13072.indb 64
11/01/13 1:53 PM
11/01/13 1:53 PM
—
—
—
FILE NO. SVM-18042
-1
[P05]
[Power supply error]
[P07]
[Heat sink overheat error]
Confirm power supply, etc.
Check outdoor P.C. board.
Defect
→
Replace
YES
NO
Is the power supply voltage
is lower than or over the range?
50 Hz : AC 198 to 264 V
60 Hz : AC 198 to 242 V
Check outdoor P.C. board.
Defect
→
Replace
Remove blocking matter.
Correct short-circuit.
NO
NO
YES
YES
Apply radiation grease
to the power device.
Retightening of screws.
Does anything block the ventilation
around the heat sink?
Does anything block air flow
from the fan?
Is the power device on P.C. board
tightly screwed?
Are radiation grease properly applied?
—
—