No.
4
Part name
Procedure
Remarks
Control P.C.
board
assembly
1)
Take off 1 screws (
ST1T Ø4 × 10L
)
that
fixed between ASM-COV-WIRING and
inverter box
.
then
disengage ASM-COV-
WIRING from inverter box.
2)
Remove P.C.board base’s hook (Hook 1,
2, 3, 4), hold P.C.board base, pull inverter
box up.
Remove lead wire
・
connector that
are
connected from control board frame to
other parts.
1.
Lead wire : Connect with terminal block
Black, white, orange (single phase),
earthed lines (black)
・・・
1 pc.
Please cut the bundling band that tie lead wire
connect with terminal block Black, White, Orange
with inverter box(metal plate).
※
Warning 1)
Please remove housing part’s lock before
removing connectors.
3)
4)
Remove inrter box from base P.C.board
base by disengage P.C.board base's hook
(Hook1,2,3,4) and pull inverter box up.
Remove control board frame from PC
board base. (Remove while heat sink is
still
attached to control board frame)
5)
Take off
5
screws that connect heat sink
and control board frame.
6)
Install new control board frame.
Warning
2
)
When install new control board frame,
please correctly insert the board. Make
sure to install that heat sink touch metal
plate.
Sub board
base
Power line
Remove
earth screw
FILE NO. SVM-18042
Hook 1, 2
Hook 4, 3
Inverter box
(metal plate)
Control
board frame
PC board
base
Control
board frame
PC board base
–
7
9
–