background image

– 27 –

Are there scratches or dents on the existing pipes?

Is it possible to operate the existing air conditioner?

 

y

After the existing air conditioner is operated in 
cooling mode for approx. 30 minutes or longer,* 
recover the refrigerant.

 

y

For cleaning the pipes and recovering oil

 

y

Refrigerant recovery: Pump down method

 

y

Remove the existing air conditioner from the piping 
and carry out 

fl

ushing (nitrogen pressure 0.5 MPa) 

to remove any remains inside of the pipe.

Note:

  In case of twin pipes, also be sure to 

fl

ush the 

branching pipe.

Connect the indoor / outdoor units to the existing 
pipe.

 

y

Use a 

fl

are nut attached to the main unit for the 

indoor / outdoor units. (Do not use the 

fl

are nut of 

the existing pipe.)

 

y

Re-machine the 

fl

are machining size to size for 

R32.

 

y

(Airtight test), Vacuum dry, Refrigerant charge, Gas 
leak check

Test run

Was largely discolored oil or a large quantity 

of remains discharged? (When the oil deteriorates, 

the color of the oil changes to a muddy or 

black color.)

Existing pipes: Cannot be used.

 

y

Use new pipes.

Clean the pipes or use new pipes.

Piping necessary to change the 

fl

are nut / machining 

size due to pipe compression

1) Flare nut width: H

H

(mm)

Copper pipe 
outer diameter

Ø6.4

Ø9.5

Ø12.7

Ø15.9

For R32, R410A 

17

22

26

29

For R22

Same as above

24

27

2) Flare machining size: A

A

(mm)

Copper pipe 
outer diameter

Ø6.4

Ø9.5

Ø12.7

Ø15.9

For R32, R410A 

9.1

13.2

16.6

19.7

For R22

9.0

13.0

16.2

19.4

Becomes a little larger for R32

Do not apply refrigerator oil to the 

fl

are surface.

(If there is discharge of remains, it is judged that a 

large quantity of remains are present.)

YES

YES

NO

NO

NO

YES

Nitrogen gas pressure 0.5 MPa

13

Appendix

Work instructions

The existing R22 and R410A piping can be reused for 
inverter R32 product installations.

 WARNING

Con

fi

rming the existence of scratches or dents on 

the existing pipes and con

fi

rming the reliability of 

the pipe strength are conventionally referred to the 
local site.
If the speci

fi

ed conditions can be cleared, it is 

possible to update existing R22 and R410A pipes 
to those for R32 models.

Basic conditions needed to reuse existing 
pipes

Check and observe the presence of three conditions in 
the refrigerant piping works.
1. 

Dry

 (There is no moisture inside of the pipes.)

2. 

Clean

 (There is no dust inside of the pipes.)

3. 

Tight

 (There are no refrigerant leaks.)

Restrictions for use of existing pipes

In the following cases, the existing pipes should 
not be reused as they are. Clean the existing pipes 
or exchange them with new pipes.

1. When a scratch or dent is heavy, be sure to use 

new pipes for the refrigerant piping works.

2. When the existing pipe thickness is thinner than the 

speci

fi

ed “Pipe diameter and thickness,” be sure to 

use new pipes for the refrigerant piping works.

 

y

The operating pressure of refrigerant is high. 
If there is a scratch or dent on the pipe or a 
thinner pipe is used, the pressure strength may be 
inadequate, which may cause the pipe to break in 
the worst case.

*  Pipe diameter and thickness (mm)

Pipe outer diameter

Ø6.4

Ø9.5 Ø12.7 Ø15.9

Thickness

R32, R410A

0.8

0.8

0.8

1.0

R22

3. When the outdoor unit was left with the pipes 

disconnected, or the gas leaked from the pipes and 
the pipes were not repaired and re

fi

lled.

 

y

There is the possibility of rain water or air, 
including moisture, entering the pipe.

4. When refrigerant cannot be recovered using a 

refrigerant recovery unit.

 

y

There is the possibility that a large quantity of dirty 
oil or moisture remains inside the pipes.

5. When a commercially available dryer is attached to 

the existing pipes.

 

y

There is the possibility that copper green rust has 
been generated.

6. When the existing air conditioner is removed after 

refrigerant has been recovered.

  Check if the oil is judged to be clearly different from 

normal oil.

 

y

The refrigerator oil is copper rust green in color:

  There is the possibility that moisture has mixed 

with the oil and rust has been generated inside 
the pipe.

 

y

There is discolored oil, a large quantity of residue, 
or a bad smell.

 

y

A large quantity of shiny metal dust or other wear 
residue can be seen in the refrigerant oil.

7. When the air conditioner has a history of the 

compressor failing and being replaced.

 

y

When discolored oil, a large quantity of residue, 
shiny metal dust, or other wear residue or mixture 
of foreign matter is observed, trouble will occur.

8. When temporary installation and removal of the air 

conditioner are repeated such as when leased etc.

9. If the type of refrigerator oil of the existing air 

conditioner is other than the following oil (Mineral 
oil), Suniso, Freol-S, MS (Synthetic oil), alkyl 
benzene (HAB, Barrel-freeze), ester series, PVE 
only of ether series.

 

y

The winding-insulation of the compressor may 
deteriorate.

NOTE

The above descriptions are results have been 
con

fi

rmed by our company and represent our views on 

our air conditioners, but do not guarantee the use of 
the existing pipes of air conditioners that have adopted 
R32 in other companies.

Curing of pipes

When removing and opening the indoor or outdoor unit 
for a long time, cure the pipes as follows:

 

y

Otherwise rust may be generated when moisture or 
foreign matter due to condensation enters the pipes.

 

y

The rust cannot be removed by cleaning, and new 
pipes are necessary.

Placement 

location

Term

Curing manner

Outdoors

1 month or more

Pinching

Less than 1 month

Pinching or taping

Indoors

Every time

54-EN

53-EN

Summary of Contents for RAV-GM901BTP-E

Page 1: ...AIR CONDITIONER SPLIT TYPE Installation Manual Indoor Unit Model name Concealed Duct Type RAV GM901BTP E For commercial use English ...

Page 2: ...ainted with the knowledge related to this work The qualified installer who is allowed to do the refrigerant handling and piping work involved in installation relocation and removal has the qualifications pertaining to this refrigerant handling and piping work as stipulated by the local laws and regulations and he or she is a person who has been trained in matters relating to refrigerant handling a...

Page 3: ...hich leave aftereffect and require hospitalization or long term treatment as an outpatient 2 Slight injury indicates injury burns electric shock and other injuries which do not require hospitalization or long term treatment as an outpatient 3 Damage to property indicates damage extending to buildings household effects domestic livestock and pets MEANINGS OF SYMBOLS DISPLAYED ON THE UNIT WARNING Ri...

Page 4: ...rotective gloves and safety work clothing during installation servicing and removal Do not touch the aluminum fin of the outdoor unit You may injure yourself if you do so If the fin must be touched for some reason first put on protective gloves and safety work clothing and then proceed Before opening the suction board cover set the circuit breaker to the OFF position Failure to set the circuit bre...

Page 5: ...ilure to follow these instructions may cause the product to fall down or topple over or give rise to noise vibration water leakage or other trouble Carry out the specified installation work to guard against the possibility of high winds and earthquake If the air conditioner is not installed appropriately a unit may topple over or fall down causing an accident If refrigerant gas has leaked during t...

Page 6: ... be easily accessed by the agent When installing the circuit breaker outdoors install one which is designed to be used outdoors Under no circumstances the power wire must not be extended Connection trouble in the places where the wire is extended may give rise to smoking and or a fire Electrical wiring work shall be conducted according to law and regulation in the community and installation manual...

Page 7: ...ith the service valve left open and the compressor still operating will cause air or other gas to be sucked in raising the pressure inside the refrigeration cycle to an abnormally high level and possibly resulting in rupture injury or other trouble CAUTION This Air Conditioner has adopted a refrigerant HFC R32 which does not destroy the ozone layer As the R32 refrigerant is easily affected by impu...

Page 8: ...the plastic parts to be damaged and other such problems to result y Locations near obstructions such as ventilation openings or lighting fixtures where the flow of the blown air will be disrupted a disruption of the air flow may cause the air conditioner s performance to deteriorate or the unit to shut down y Locations where an in house power generator is used for the power supply The power line f...

Page 9: ... cleaning of the remote controller can be changed according to the condition of installation For setup method refer to Filter sign setting in the Applicable controls of this Manual CAUTION Strictly comply with the following rules to prevent damage of the indoor units and human injury y Do not put a heavy article on the indoor unit or let a person get on it Even units are packaged y Carry in the in...

Page 10: ...ceiling correctly in order to prevent vibration of ceiling board y Attach the nuts and the M10 flat washers to the hanging bolt y Put washers at up and down of the hanging bracket of the indoor unit to hang down the indoor unit y Check that four sides are horizontal with a level gauge Horizontal degree Within 5 mm M10 flat washer M10 flat washer Hanging bolt W3 8 or M10 Nut W3 8 or M10 Nut W3 8 or...

Page 11: ...ing materials for piping work and insulating process are locally procured Pipe material Hard vinyl chloride pipe VP25 Nominal outer diameter Ø32 mm Insulator Foamed polyethylene foam thickness 10 mm or more Connecting drain pipe Insert flexible drain hose into the drain pipe of main unit as far as it will go Fix it with hose band REQUIREMENT Mount the flexible drain hose using the hose band withou...

Page 12: ...lly starts running Check whether the water is draining from the drain pipe connecting port and check that no water is leaking from the drain pipe After checking that the water drains and there are no water leaks turn off the power connect the float switch connector to its original location CN34 on the printed circuit board and return the electrical control box to its original position Supply water...

Page 13: ...00 1500 1600 1700 1800 1900 2000 2100 2200 Air volume m3 h External static pressure Pa Standard filter pressure loss Upper limit of external static pressure 120 Pa Lower limit of external static pressure 120 Pa High tap 120 Pa High tap 100 Pa High tap 80 Pa High tap 65 Pa High tap 50 Pa High tap 40 Pa High tap 30 Pa Low tap 30 Pa Low tap 120 Pa 24 EN 23 EN ...

Page 14: ...duct at the local site 254 27 27 37 5 37 5 1359 4 100 100 235 4 100 100 100 100 100 100 100 100 100 100 100 100 100 254 1375 27 27 37 5 37 5 1360 235 2 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 GM90 Under air intake Back air intake 6 Duct design 26 EN 25 EN ...

Page 15: ...ze The copper pipe gauge is useful for adjusting projection margin size y The sealed gas was sealed at the atmospheric pressure so when the flare nut is removed there will no whooshing sound This is normal and is not indicative of trouble y Use two wrenches to connect the indoor unit pipe Work using double spanner y Use the tightening torque levels as listed in the following table Outer dia of con...

Page 16: ...hortage of power circuit or incomplete installation may cause an electric shock or a fire CAUTION y For power supply specifications follow the Installation Manual of outdoor unit y Do not connect 220 240V power to the terminal blocks A B for control wiring Otherwise the system will fail Do not damage or scratch the conductive core and inner insulator of power and system interconnection wires when ...

Page 17: ...ncorrect connection causes a trouble y Pass the wires through the bushing of wire connection holes of the indoor unit y Keep a margin Approx 100 mm on a wire to hang down the electrical control box at servicing or other purpose y The low voltage circuit is provided for the remote controller Do not connect the high voltage circuit y Before performing wiring work in the electrical control box remove...

Page 18: ...x 1 minutes y Normal settings were made when the indoor unit was shipped from factory Change the indoor unit settings as required y Use the wired remote controller to change the settings The settings cannot be changed using the wireless remote controller sub remote controller or remote controller less system for central remote controller only Therefore install the wired remote controller to change...

Page 19: ...50 H 0002 2500 H Factory default 0003 5000 H 0004 10000 H To secure better effect of heating When it is difficult to obtain satisfactory heating due to installation place of the indoor unit or structure of the room the detection temperature of heating can be raised Also use a circulator or other device to circulate heat air near the ceiling Follow to the basic operation procedure 1 2 3 4 5 6 y For...

Page 20: ... TE 61 Outside air temperature TO 62 Compressor discharge temperature TD 63 Compressor suction temperature TS 64 65 Heatsink temperature THS 6A Operating current x1 10 F1 Compressor cumulative operating hours x100 h Group control Simultaneous twin triple or double twin system A combination with an outdoor unit allows simultaneous ON OFF operation of the indoor units The following system patterns a...

Page 21: ...ddress Indoor No After setup of automatic address Example of random setup Procedure example 1 After setup change of manual address Line system Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Remote controller Twin system Single system Triple system The above address is set by the automatic addressing when the power is turned on However line addresses and indoor addresses are set random...

Page 22: ... be again set up Therefore repeat procedure of the setup change from the Procedure 1 To recognize the position of the corresponding indoor unit though the indoor UNIT No is known Check the position during operation stop Stop operation of the unit 2 1 3 1 1 Push buttons simultaneously for 4 seconds or more After a while the display part flashes and the display appears as shown below In this time th...

Page 23: ...the power supply carry out the following procedure 1 By using 500V megger check that resistance of 1 MΩ or more exists between the terminal block 1 to 3 and the earth grounding If resistance of less than 1 MΩ is detected do not run the unit 2 Check the valve of the outdoor unit being opened fully y To protect the compressor at activation time leave power ON for 12 hours or more before operating Ex...

Page 24: ...oor units in test run TEMPORARY button 11 Maintenance Daily maintenance 4 Cleaning of the air filter If is displayed on the remote controller maintain the air filter 3 1 2 1 Push the button to stop the operation then turn off the circuit breaker After the cooling or dry operation the fan keeps running for self cleaning Push the button twice to stop the operation 1 Take out the air filter y Slide a...

Page 25: ...rmal sound is generated Filter Indoor Dust dirt breakage y Wash the filter with water when it is contaminated y Replace it when it is damaged Fan Indoor y Vibration balance y Dust dirt appearance y Replace the fan when vibration or balance is terrible y Brush or wash the fan when it is contaminated Air intake discharge grilles Indoor outdoor Dust dirt scratches Fix or replace them when they are de...

Page 26: ...op F13 ALT Heat sink sensor error Outdoor Abnormal temperature was detected by the temp sensor of the IGBT heat sink Entire stop Wired remote controller display Wireless remote controller Sensor block display of receiving unit Main problem parts Judging device Parts to be checked error description Air conditioner status Indication Operation Timer Ready GR GR OR Flashing F15 ALT Temp sensor connect...

Page 27: ...rs TC TCJ An error was detected due to temperature drop of the indoor unit heat exchanger sensor when heating Auto reset P20 ALT High pressure protective operation Outdoor High pressure protection Entire stop P22 ALT Outdoor unit fan error Outdoor Outdoor unit fan motor outdoor unit P C board An error overcurrent locking etc was detected in the outdoor unit fan drive circuit Entire stop P26 ALT Ou...

Page 28: ... works 2 When the existing pipe thickness is thinner than the specified Pipe diameter and thickness be sure to use new pipes for the refrigerant piping works y The operating pressure of refrigerant is high If there is a scratch or dent on the pipe or a thinner pipe is used the pressure strength may be inadequate which may cause the pipe to break in the worst case Pipe diameter and thickness mm Pip...

Page 29: ... 28 56 EN 55 EN ...

Page 30: ...1116950190 144 9 Moo 5 Bangkadi Industrial Park Tivanon Road Tambol Bangkadi Amphur Muang Pathumthani 12000 Thailand ...

Reviews: