– 50 –
8-1-1. Monitor Function of Remote Controller
Calling of sensor temperature display
<Contents>
Each data of the remote controller, indoor unit and outdoor unit can be understood by calling the service
monitor mode from the remote controller.
<Procedure>
<Oper
a
tion procedure>
1 2 3 4
Returned to usu
a
l displ
a
y
2
4
1
3
S
ET
TIME
TIMER
S
ET
TE
S
T
FILTER
L
RE
S
ET
TEMP.
CL
FAN
S
AVE
A
S
WING/FIX
VENT
MODE
ON / OFF
UNIT LOUVER
T
Indoor unit data
CODE No.
01
02
0
3
04
07
F2
F
3
F
8
Data name
Room temper
a
ture
(Remote controller)
Indoor room
a
ir temper
a
ture (TA)
Indoor he
a
t exch
a
nger (Coil)
temper
a
ture (TCJ)
Indoor he
a
t exch
a
nger (Coil)
temper
a
ture (TC)
Indoor f
a
n revolution frequency
Indoor f
a
n c
a
lcul
a
ted oper
a
tion time
Indoor unit f
a
n cumul
a
tive oper
a
ting hours
Indoor disch
a
rge temper
a
ture
Unit
˚C
˚C
˚C
˚C
rpm
×100h
×1h
˚C
Outdoor unit data
CODE No.
60
61
62
6
3
65
6A
6D
70
72
7
3
F1
Data name
Outdoor he
a
t exch
a
nger (Coil) temper
a
ture (TE)
Outside temper
a
ture (TO)
Compressor disch
a
rge temper
a
ture (TD)
Compressor suction temper
a
ture (T
S
)
He
a
t sink temper
a
ture (TH
S
)
Oper
a
tion current (× 1/10)
Outdoor he
a
t exch
a
nger (Coil) temper
a
ture (TL)
Compressor oper
a
tion frequency
Outdoor f
a
n revolution frequency (Lower)
Outdoor f
a
n revolution frequency (Upper)
Compressor c
a
lcul
a
ted oper
a
tion time
Unit
˚C
˚C
˚C
˚C
˚C
A
˚C
rps
rpm
rpm
×100h
1
Push + buttons simultaneously for 4 seconds to
call the service monitor mode.
The service monitor goes on, the header indoor unit No. is
displayed at first and then the temperature of CODE No.
00
is
displayed.
Ø
2
Push temperature set
buttons and then change
the CODE No. of data to be monitored.
The CODE No. list is shown below.
Ø
3
Push
UNIT LOUVER
button to select the indoor unit to be monitored.
Each data of the indoor unit and its outdoor units can be monitored.
Ø
4
Pushing button returns the status to the usual display.
∗
1 The indoor discharge temperature of CODE No. [F8] is the estimated value from TC or TCJ sensor.
Use this value to check discharge temperature at test run.
(A discharge temperature sensor is not provided to this model.)
• The data value of each item is not the real time, but value delayed by a few seconds to ten-odd seconds.