10-4. Address Setup (Manual setting from remote controller)
(Ex
a
mple of 2-lines c
a
bling)
(
S
olid line: C
a
bling, Broken line: Refriger
a
nt pipe)
For the
a
bove ex
a
mple, perform setting by
connecting singly the wired remote controller
without remote controller inter-unit c
a
ble.
Group
a
ddress
Individu
a
l :
0000
M
a
ster unit : 0001
S
ub unit
: 0002
In c
a
se of group control
Outdoor
Indoor
A B
A B
1 2
3
Indoor
A B
1 2
3
Indoor
A B
1 2
3
Indoor
A B
1 2
3
1 2
3
Outdoor
1 2
3
Remote controller
Line
a
ddress
→
1
Indoor unit
a
ddress
→
1
Group
a
ddress
→
1
1
2
2
2
1
2
2
2
2
<Operation procedure>
1 2 3 4 5 6 7 8 9 10 11
END
1
3, 6, 9
END
11
2, 5, 8
4, 7, 10
SET
TIME
TIMER SET
TEST
FILTER
LL
RESET
TEMP.
CL
FAN
SAVE
A
A
SWING/FIX
VENT
MODE
ON / OFF
UNIT LOUVER
T
In case that addresses of the indoor units will be
determined prior to piping work after wiring work
• Set an indoor unit per a remote controller.
• Turn on power supply.
1
Push + + buttons simultaneously for
4 seconds or more.
2
(
←
←
←
←
←
Line address)
Using the temperature setup
/
buttons, set the CODE No. to
12
12
12
12
12
.
3
Using timer time
/
buttons, set the line
address.
4
Push button.
(OK when display goes on.)
5
(
←
←
←
←
←
Indoor unit address)
Using the temperature setup
/
buttons, set the CODE No. to
13
13
13
13
13
.
6
Using timer time
/
buttons, set the line address to 1.
7
Push button.
(OK when display goes on.)
8
(
←
←
←
←
←
Group address)
Using the temperature setup
/
buttons, set the CODE No. to
14
14
14
14
14
.
9
Using timer time
/
buttons, set Individual to
0000
0000
0000
0000
0000
, Header unit to
0001
0001
0001
0001
0001
, and Follower
unit to
0002
0002
0002
0002
0002
.
10
Push button.
(OK when display goes on.)
11
Push button.
Setup completes. (The status returns to the usual stop status.)