Error codes and parts to be checked

Wired 

remote 

controller 

display

Wireless remote 

controller Sensor block 

display of receiving unit

Main problem parts

Judging

device

Parts to be checked / error description

Air 

conditioner 

status

Indication

Operation Timer 

Ready 

GR GR OR

Flashing

E01

No header remote 

controller

Remote 

controller

Incorrect remote controller setting --- The header 

remote controller has not been set (including two 

remote controllers).

*

Remote controller 

communication error

No signal can be received from the indoor unit.

E02

Remote controller 

transmission error

Remote 

controller

Indoor / Outdoor connecting wires, indoor P.C. 

board, remote controller

--- No signal can be sent to the indoor unit.

*

E03

Indoor unit-remote

controller regular

communication error

Indoor

Remote controller, network adapter, indoor P.C. 

board --- No data is received from the remote 

controller or network adapter.

Auto-reset

E04

Indoor unit-outdoor

unit serial

communication error 

Indoor

Indoor / Outdoor connecting wires, indoor P.C. 

board, outdoor P.C. board --- Serial communication 

error between indoor unit and outdoor unit

Auto-reset

IPDU-CDB

communication error

E08

Duplicated indoor 

addresses 

Indoor

Indoor address setting error --- The same address 

as the self-address was detected.

Auto-reset

E09

Duplicated header

remote controllers

Remote 

controller

Remote controller address setting error --- Two 

remote controllers are set as header in the double-

remote controller control.

*

(* The header indoor unit stops raising alarm and 

follower indoor units continue to operate.)

Е

10

CPU-CPU

communication error

Indoor

Indoor P.C. board --- Communication error between

main MCU and motor microcomputer MCU

Auto-reset

E11

Communication trouble 

between Application 

control kit and indoor 

unit

Indoor

Communication trouble between Application control 

kit and indoor unit

Entire stop

E18

Header unit follower

unit regular

communication error

Indoor

Indoor P.C. board --- Regular communication is 

not possible between header and follower indoor 

units or between twin header (main) and follower 

(sub) units.

Auto-reset

E31

IPDU communication

error

Outdoor

Communication error between IPDU and CDB

Entire stop

F01

ALT

Indoor unit heat

exchanger sensor

(TCJ) error

Indoor

Heat exchanger sensor (TCJ), indoor P.C. board --- 

Open-circuit or short-circuit of the heat exchanger 

sensor (TCJ) was detected.

Auto-reset

F02

ALT

Indoor unit heat

exchanger sensor

(TC) error

Indoor

Heat exchanger sensor (TC), indoor P.C. board --- 

Open-circuit or short-circuit of the heat exchanger 

sensor (TC) was detected.

Auto-reset

F04

ALT

Outdoor unit

discharge temp.

sensor (TD) error

Outdoor

Outdoor temp, sensor (TD), outdoor P.C. board --- 

Open-circuit or short-circuit of the discharge temp, 

sensor was detected.

Entire stop

F06

ALT

Outdoor unit temp.

sensor (TE / TS) error

Outdoor

Outdoor temp, sensors (

ТЕ

 / TS), outdoor P.C. 

board --- Open-circuit or short-circuit of the heat 

exchanger temp, sensor was detected.

Entire stop

F07

ALT

TL sensor error

Outdoor

TL sensor may be displaced, disconnected or 

short-circuited.

Entire stop

F08

ALT

Outdoor unit outside

air temp. sensor error

Outdoor

Outdoor temp, sensor (TO), outdoor P.C. board --- 

Open-circuit or short-circuit of the outdoor air temp, 

sensor was detected.

Operation 

continued

F10

ALT

Indoor unit room

temp. sensor (TA)

error

Indoor

Room temp, sensor (

ТА

), indoor P.C. board 

--- Open-circuit or short-circuit of the room temp, 

sensor (

ТА

) was detected.

Auto-reset

F12

ALT

TS sensor error

Outdoor

TS sensor may be displaced, disconnected or 

short-circuited.

Entire-stop

F13

ALT

Heat sink sensor error

Outdoor

Abnormal temperature was detected by the temp, 

sensor of the IGBT heat sink.

Entire stop

Wired 

remote 

controller 

display

Wireless remote 

controller Sensor block 

display of receiving unit

Main problem parts

Judging

device

Parts to be checked / error description

Air 

conditioner 

status

Indication

Operation Timer 

Ready 

GR GR OR

Flashing

F15

ALT

Temp. sensor

connection error

Outdoor

Temp, sensor (

ТЕ

 / TS) may be connected 

incorrectly.

Entire stop

F29

SIM

Indoor unit, other P.C. 

board error

Indoor

Indoor P.C. board --- EEPROM error

Auto-reset

F30

SIM

Occupancy sensor 

trouble

Indoor

Abnormality was detected from occupancy sensor.

Operation 

continued

F31

SIM

Outdoor unit P.C.

board

Outdoor

Outdoor P.C. board --- In the case of EEPROM 

error.

Entire stop

H01

Outdoor unit

compressor

breakdown

Outdoor

Current detect circuit, power voltage --- Minimum 

frequency was reached in the current releasing 

control or short-circuit current (Idc) after direct 

excitation was detected

Entire stop

H02

Outdoor unit

compressor lock

Outdoor

Compressor circuit --- Compressor lock was 

detected.

Entire stop

H03

Outdoor unit current

detect circuit error

Outdoor

Current detect circuit, outdoor unit P.C. board --- 

Abnormal current was detected in AC-CT or a 

phase loss was detected.

Entire stop

H04

Case thermostat

operation

Outdoor

Malfunction of the case thermostat

Entire stop

H06

Outdoor unit low-

pressure system error

Outdoor

Current, high-pressure switch circuit, outdoor P.C. 

board --- Pressure sensor error was detected or 

low- pressure protective operation was activated.

Entire stop

L03

SIM

Duplicated header 

indoor units 

Indoor

Indoor address setting error --- There are two or 

more header units in the group.

Entire stop

L07

SIM

Group line in individual 

indoor unit 

Indoor

Indoor address setting error --- There is at least 

one group-connected indoor unit among individual 

indoor units.

Entire stop

L08

SIM

Indoor group address 

not set 

Indoor

Indoor address setting error --- Indoor address 

group has not been set.

Entire stop

L09

SIM

Indoor unit capacity 

not set

Indoor

Indoor unit capacity has not been set.

Entire stop

L10

SIM

Outdoor unit P.C. 

board

Outdoor

In the case of outdoor P.C. board jumper wire 

(for service) setting error

Entire stop

L20

SIM

LAN communication 

error

Network 

adapter 

central 

control

Address setting, central control remote controller, 

network adapter --- Duplication of address in 

central control communication

Auto-reset

L29

SIM

Other outdoor unit

error

Outdoor

Other outdoor unit error

Entire stop

1)  Communication error between IPDU MCU and 

CDB MCU

Entire stop

2)  Abnormal temperature was detected by the heat 

sink temp, sensor in IGBT.

L30

SIM

Abnormal external 

input into indoor unit 

(interlock)

Indoor

External devices, outdoor unit P.C. board --- 

Abnormal stop due to incorrect external input into 

CN80

Entire stop

L31

SIM

Phase sequence 

error, etc.

Outdoor

Power supply phase sequence, outdoor unit P.C. 

board --- Abnormal phase sequence of the 3-phase 

power supply

Operation 

continued 

(thermost 

at OFF)

P01

ALT

Indoor unit fan error

Indoor

Indoor fan motor, indoor P.C. board --- Indoor AC 

fan error (fan motor thermal relay activated) was 

detected.

Entire stop

P03

ALT

Outdoor unit

discharge temp. error

Outdoor

An error was detected in the discharge temp, 

releasing control.

Entire stop

P04

ALT

Outdoor unit high-

pressure system error

Outdoor

High-pressure switch --- The IOL was activated 

or an error was detected in the high-pressure 

releasing control using the 

ТЕ

.

Entire stop

P05

ALT

Open phase detected

Outdoor

The power wire may be connected incorrectly. 

Check open phase and voltages of the power 

supply.

Entire stop

Summary of Contents for RAV-HM1101BTP-E

Page 1: ...CONDITIONER SPLIT TYPE Installation Manual Indoor Unit Model name Concealed Duct Type RAV HM561BTP E RAV HM801BTP E RAV HM901BTP E RAV HM1101BTP E RAV HM1401BTP E RAV HM1601BTP E For commercial use English ...

Page 2: ...oroughly acquainted with the knowledge related to this work Qualified service person The qualified service person is a person who installs repairs maintains relocates and removes the air conditioners made by Toshiba Carrier Corporation He or she has been trained to install repair maintain relocate and remove the air conditioners made by Toshiba Carrier Corporation or alternatively he or she has be...

Page 3: ...ture poisoning and other injuries which leave aftereffect and require hospitalization or long term treatment as an outpatient 2 Slight injury indicates injury burns electric shock and other injuries which do not require hospitalization or long term treatment as an outpatient 3 Damage to property indicates damage extending to buildings household effects domestic livestock and pets MEANINGS OF SYMBO...

Page 4: ... safety work clothing during installation servicing and removal Do not touch the aluminum fin of the outdoor unit You may injure yourself if you do so If the fin must be touched for some reason first put on protective gloves and safety work clothing and then proceed Before opening the suction board cover set the circuit breaker to the OFF position Failure to set the circuit breaker to the OFF posi...

Page 5: ...st the possibility of high winds and earthquake If the air conditioner is not installed appropriately a unit may topple over or fall down causing an accident If refrigerant gas has leaked during the installation work ventilate the room immediately If the leaked refrigerant gas comes in contact with fire noxious gas may generate Use forklift to carry in the air conditioner units and use winch or ho...

Page 6: ... Failure to do so may result in electrocution or short circuit Test run Before operating the air conditioner after having completed the work check that the electrical control box cover of the indoor unit and service panel of the outdoor unit are closed and set the circuit breaker to the ON position You may receive an electric shock if the power is turned on without first conducting these checks If...

Page 7: ...l and possibly resulting in rupture injury or other trouble CAUTION This Air Conditioner has adopted a refrigerant HFC R32 which does not destroy the ozone layer As the R32 refrigerant is easily affected by impurities such as moisture oxidized film oil etc due to the high pressure be careful not to allow the moisture dirt existing refrigerant refrigerating machine oil etc to get mixed up in the re...

Page 8: ... combust and start a fire y Locations where vapors from food oils are formed such as kitchens where food oils are used Blocked filters may cause the air conditioner s performance to deteriorate condensation to form the plastic parts to be damaged and other such problems to result y Locations near obstructions such as ventilation openings or lighting fixtures where the flow of the blown air will be...

Page 9: ...nditions Indoor side 27 C dry bulb temperature 24 C wet bulb temperature Air volume Low air volume operation time 4 hours Installation space Unit mm Reserve sufficient space required for installation or service work 25 A 25 120 B 25 570 570 25 570 25 Ceiling Ceiling Ceiling Ceiling Air intake Air intake Air intake 50 or more 300 or more 100 or more 2500 or more Floor surface Service door Ceiling o...

Page 10: ...the indoor unit Procure hanging bolts washer and nuts for installing the indoor unit these are not supplied Hanging bolt M10 or W3 8 4 pieces Nut M10 or W3 8 12 pieces Washer M10 8 pieces Installation of hanging bolt Use M10 hanging bolts 4 pcs locally procured Matching to the existing structure set pitch according to size in the unit external view as shown below New concrete slab Install the bolt...

Page 11: ...r unit with proper heat insulation Improper heat insulation will cause condensation to form y The drain pipe must be sloping downward at an angle of 1 100 or more and do not run the pipe up and down arched shape or allow it to form traps Doing so may cause abnormal sounds y Restrict the length of the traversing drain pipe to 20 meters or less For a long pipe provide support brackets at intervals o...

Page 12: ...hen installed in heating period When the electrical and wiring work has been completed Pour some water by following the method shown in the following figure Then while performing a cooling operation check that the water drains from the drain pipe connecting port transparent and that no water is leaking from the drain pipe When the electrical and wiring work has not been completed Disconnect the fl...

Page 13: ...140 150 160 170 180 190 200 210 220 600 800 1000 1200 1400 1600 1800 2000 2200 0 10 20 30 40 50 50 70 80 90 100 110 120 130 140 150 160 170 180 190 200 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220 800 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800 Standard air volume 800 m3 h Standard air volume 1700 ...

Page 14: ... 0 1 0 0 1 0 0 1 0 0 1 0 0 1 0 0 1 254 975 37 5 37 5 27 27 960 235 2 100 0 0 1 0 0 1 0 0 1 0 0 1 0 0 1 0 0 1 0 0 1 0 0 1 0 0 1 0 0 1 254 27 27 37 5 37 5 1359 4 100 100 235 4 100 0 0 1 0 0 1 100 0 0 1 0 0 1 100 100 100 0 0 1 0 0 1 0 0 1 100 254 1375 27 27 37 5 37 5 1360 235 2 0 0 1 0 0 1 100 0 0 1 0 0 1 0 0 1 0 0 1 0 0 1 100 0 0 1 0 0 1 0 0 1 100 100 100 HM56 HM80 HM90 HM110 HM140 HM160 Under air i...

Page 15: ...are size The copper pipe gauge is useful for adjusting projection margin size y The sealed gas was sealed at the atmospheric pressure so when the flare nut is removed there will no whooshing sound This is normal and is not indicative of trouble y Use two wrenches to connect the indoor unit pipe Work using double spanner y Use the tightening torque levels as listed in the following table Outer dia ...

Page 16: ...e is connected in the middle may give rise to smoking and or a fire CAUTION y For power supply specifications follow the Installation Manual of outdoor unit y Do not connect 220 240V power to the terminal blocks A B for control wiring Otherwise the system will fail Do not damage or scratch the conductive core and inner insulator of power and Indoor Outdoor connecting wires when peeling them Perfor...

Page 17: ...Be sure to connect both ends of the shield wire to earth leads y Connect earth wires for each indoor unit in the simultaneous twin simultaneous triple and simultaneous double twin systems Communication type TU2C Link can be used with these models If the indoor unit and the connected remote controller remote sensor are all TU2C Link models TU2C Link communication will be performed automatically If ...

Page 18: ...cted Wiring diagram A B A B Terminal block for remote controller wiring of indoor unit Remote controller wire Locally procured Terminal block Remote controller unit Applicable controls setup settings at the site Remote controller model name RBC ASCU1 Basic procedure Be sure to stop the air conditioner before making settings Change the setup while the air conditioner is not working CAUTION Set only...

Page 19: ...above is when SW501 1 and SW501 2 is OFF External static pressure When using the wireless remote controller To set up the external static pressure use the DIP switch on the circuit board of the wireless reception part For details refer to the instruction manual of the wireless remote controller kit Alternatively use the switch on the indoor micro computer circuit board as shown in the following fi...

Page 20: ... 2 3 4 5 6 7 Specify d1 for the Code No in Procedure 4 Select the following data for the set data in Procedure 5 SET DATA 8 C Operation setting 0000 None Factory default 0001 8OC Operation setting Installing optional parts When installing optional parts data setup may be required with remote controller Be sure to set the data according to Installation Manual for optional parts Information The foll...

Page 21: ... Procedure example 1 After setup change of manual address Line system Indoor unit Indoor unit Single system Twin system The above address is set by the automatic addressing when the power is turned on However line addresses and indoor addresses are set randomly For this reason change the setting to match line addresses with indoor addresses Manual address setting 1 Push and hold menu button and se...

Page 22: ...utton and then select HIGH with FAN button 10Test run 3 Cooling test run Heating test run Set the temperature to 17 C with the temp setup buttons Set the temperature to 30 C with the temp setup buttons 4 Cooling test run Heating test run After confirming a signal receiving sound beep immediately set the temperature to 18 C with the temp setup buttons After confirming a signal receiving sound beep ...

Page 23: ...S 65 Heatsink temperature THS 6A Operating current x1 10 6D Outdoor heat exchange coil temperature TL F1 Compressor cumulative operating hours x100 h 1 The above temperature values are estimated from the temperature of the heat exchanger It may differ from the actual discharge temperature 2 For outdoor unit data refer to the Installation Manual and Service Manual of the outdoor unit Daily maintena...

Page 24: ...irt appearance y Replace the fan when vibration or balance is terrible y Brush or wash the fan when it is contaminated Air intake discharge grilles Indoor outdoor Dust dirt scratches Fix or replace them when they are deformed or damaged Drain pan Indoor Dust dirt clogging drain contamination Clean the drain pan and check the downward slope for smooth drainage Ornamental panel louvers Indoor Dust d...

Page 25: ...sconnected or short circuited Entire stop F13 ALT Heat sink sensor error Outdoor Abnormal temperature was detected by the temp sensor of the IGBT heat sink Entire stop Wired remote controller display Wireless remote controller Sensor block display of receiving unit Main problem parts Judging device Parts to be checked error description Air conditioner status Indication Operation Timer Ready GR GR ...

Page 26: ...sor when heating Auto reset P20 ALT High pressure protective operation Outdoor High pressure protection Entire stop P22 ALT Outdoor unit fan error Outdoor Outdoor unit fan motor outdoor unit P C board An error overcurrent locking etc was detected in the outdoor unit fan drive circuit Entire stop P26 ALT Outdoor unit inverter Idc activated Outdoor IGBT outdoor unit P C board inverter wiring compres...

Page 27: ...omes invalid if technical or operational modifications are introduced without the manufacturer s consent Declaration of Conformity Manufacturer Toshiba Carrier Thailand Co Ltd 144 9 Moo 5 Bangkadi Industrial Park Tivanon road Tambol Bangkadi Amphur Muang Pathumthani 12000 Thailand TCF holder TOSHIBA CARRIER UK LTD Porsham Close Belliver Industrial Estate Roborough Plymouth Devon PL6 7DB United Kin...

Page 28: ...s 2 When the existing pipe thickness is thinner than the specified Pipe diameter and thickness be sure to use new pipes for the refrigerant piping works y The operating pressure of refrigerant is high If there is a scratch or dent on the pipe or a thinner pipe is used the pressure strength may be inadequate which may cause the pipe to break in the worst case Pipe diameter and thickness mm Pipe out...

Page 29: ...1128950185 144 9 Moo 5 Bangkadi Industrial Park Tivanon Road Tambol Bangkadi Amphur Muang Pathumthani 12000 Thailand ...

Reviews: