(˚C)
F4
F5
F5
47
42
No.
6
Item
Air speed
selection
(Continued):
Outline of specifications
3) In heating operation, the mode changes to [UL] if thermostat
is turned off.
4) If Ta
≥
25°C when heating operation has started and when
defrost operation has been cleared, the air conditioner
operates with (H) mode or higher mode for 1 minute after Tc
entered in E zone of cool air discharge preventive control
(Item 7).
5) In automatic cooling/heating operation, the revolution
frequency of (HH) is set larger than that in the standard
cooling/heating operation.
However the revolution
frequency is restricted in the
automatic heating operation as
shown in the following figure.
6) Self-clean operation
When performing self-clean operation after stopping the
cooling operation, the mode becomes [UL].
CODE No.
[5d]
SW501 (1)/(2)
Tap
F1
F2
F3
F4
F5
F6
F7
F8
F9
FA
FB
FC
FD
Standard
Type 1
Type 3
0
1
3
OFF/OFF
ON/OFF
OFF/ON
HEAT COOL HEAT COOL HEAT COOL
HH
HH
HH
HH
H+
H+, H H+, H
H+
HH
H
HH
H
L+
L+
H+
H+
L
L
H
L+
H
L+
L
L+
L
L+
L
L
Remarks
Selection of high
ceiling type
CODE No.:
[5d] or selection of
high ceiling on P.C.
board SW501
However only when
Selt-clean is not
factory default.
Tcj:
Indoor heat exchanger
sensor temperature
the high ceiling
selection is set to
[Standard]
[Self-clean
] is
displayed.
Self-clean is not
factory default.
Tc
Tcj
UL
UL
UL
UL
UL
UL
Tap
H
M56
H
M80
H
M110
H
M140
Revolution speed (rpm)
F1
1000
1000
1140
1140
F2
880
910
1020
1080
F3
850
910
950
1000
F4
830
910
930
1000
F5
820
910
910
990
F6
790
910
910
990
F7
710
7
4
0
730
810
F8
700
730
720
790
F9
690
730
710
780
FA
590
610
630
710
FB
5
60
560
580
660
FC
550
550
570
640
FD
350
350
350
350
H
M
40
1000
8
30
8
0
0
790
780
7
80
690
670
6
6
0
590
560
550
350
H
M1
6
0
1140
1080
10
2
0
1000
990
990
8
6
0
84
0
83
0
7
4
0
6
8
0
6
7
0
350
H
M
9
0
1000
9
00
830
820
820
820
7
4
0
730
730
6
40
5
90
5
80
350
- 31 -