No.
20
2
2
Item
Self-clean operation
(Dry operation)
Outline of specifications
1) When cooling operation mode (AUTO COOL, COOL, DRY) stopped, the following
three self-clean operations are performed.
2) During operation of self-clean,
lights on the wired
remote controller screen. However the operation lamp
(Green LED) goes off.
3) To stop the self-clean operation, push twice the
[ON/OFF] button on the remote controller continuously.
(Stop the operation as compressor ON time in the table
above: 10 minutes or below.)
4) When the follower unit executes self-clean operation in the
group connection, the segment of
is displayed on the
wired remote controller screen via master unit.
∗
If self-clean operation is not used, set invalidity
(does not use) of the self-clean operation by changing
[0001 (At shipment) of CODE No. (DN) [D3] to [0000].
∗
To erase the
display during operation of self-clean,
change CODE No. [D4] from [0000: Display
(At shipment)] to [0001: Non-display].
Remarks
It is recognized as
[STOP] from the
remote monitor side.
Compressor
ON period
0 to 10 min.
10 to 60 min.
60 min. to
Self-clean
operation period
None
1 hour
2 hours
FAN
Fan only
(UL)
Drain pump
STOP
Louver
Horizontal discharge position
2
1
Power saving
(Energy saving
operation)
(In the case of RBC-AMTU3
∗)
*
For RBC-AMSU5
∗
remote controller, refer to its
owner's manual.
SAVE
1) Turn on
button on the remote controller.
2) During operation of save operation,
SAVE
lights on the
wired remote controller.
3) During power save operation, the current release control
is performed with the restriction ratio set in EEPROM on
the outdoor unit.
4) The restriction ratio can be set by keeping
SAVE
button
pushed for 4 seconds or more on the remote controller.
5) When validating the power save operation, the next
operation starts with power save operation valid because
contents are held even when operation stops, operation
mode changes or power supply is reset.
6) The restriction ratio can be set by changing the setup
data of CODE No. (DN) [C2] in the range of 50 to 100%
(every 1%, Setting at shipment: 75%).
Carry out setting
operation during stop of
the unit; otherwise the
unit stops operation.
For the setup operation,
refer to "Power saving
mode" of Installation
Manual.
Drain pump delay
operation
When a cooling operation (including dry operation) is
stopped, the drain pump continues operating for 5 minutes
to reduce drain water in drain pan.
- 37 -