– 19 –
8
Applicable controls
REQUIREMENT
• When you use this air conditioner for the first time, it
takes approx. 5 minutes until the remote controller
becomes available after power-on. This is normal.
<When power is turned on for the first time after
installation>
It takes
approx. 5 minutes
until the remote controller
becomes available.
<When power is turned on for the second (or later)
time>
It takes
approx. 1 minute
until the remote controller
becomes available.
• Normal settings were made when the indoor unit was
shipped from factory.
Change the indoor unit settings as required.
• Use the wired remote controller to change the
settings.
* The settings cannot be changed using the
wireless remote controller, simplified wired
remote controller, or remote-controller-less
system (for central remote controller only).
Applicable controls setup
(settings at the site)
Remote controller model name:
RBC-AMSU5
Basic procedure
Change the settings while the air conditioner is not
working.
(Stop the air conditioner before making
settings.)
CAUTION
Set only the “Code (DN)
ˮ
shown in the following table:
Do not set any other “Code (DN)
ˮ
.
If a “Code (DN)
ˮ
not listed is set, it may not be possible
to operate the air conditioner or other trouble with the
product may result.
1
Push the [
MENU] button to display the
menu screen.
2
Push and hold the [
MENU] button and
the [
∨
] button at the same time to
display the “Field setting menu”.
Push and hold the buttons for more than 4
seconds.
Power on
“ Setting”
flashes
“ Setting”
goes out
Remote
controller is
available
Approx. 5 minutes
Power on
“ Setting”
flashes
“ Setting”
goes out
Remote
controller is
available
Approx. 1 minutes
6. Setting timer operation mode
7. DN setting
8. Reset power consumption data
9. Notice history
Field setting menu(2/2)
Return
Set
3
Push the [
∧
] / [
∨
] button to select
“7. DN setting” on the “Field setting menu”
screen, then push the “
Set” [
F2] button.
Push the [
∧
] / [
∨
] button to select
the “Indoor unit” and push the “
Set” [
F2] button.
The fan and louver of the indoor unit operate.
When the group control is used, the fan and
louver of the selected indoor unit operate.
Move the cursor to select “Code (DN)” with the
“
<
” [
F1] button, then set “Code
(DN)” with the [
∧
] / [
∨
] button.
Move the cursor to select “Data” with the
“
>
” [
F2] button, then set “Data”
with the [
∧
] / [
∨
] button.
4
Push the [
MENU] button to set the other
Code(DN) and Data. After “Continue?” is
displayed on the screen, push the
“
Yes” [
F1] button.
5
Push the “
No” [
F2] button to
finish the setting operation. “
Setting”
appears on the screen for a while, then the
screen returns to the “Field setting menu”
screen.
Pushing the “
No” [
F2] button
displays the unit selection screen when the
group control is used. Push the [
CANCEL]
button on the unit selection screen to finish the
setting operation. “ Setting” appears on the
screen for a while, then the screen returns to the
“Field setting menu” screen.
DN setting
Set
Return
Indoor unit
Code (DN) I.DN
Outdoor unit
Code (DN) O.DN
Set
Set
<
>
Yes
No
No
DN setting
Code
(DN) I.DN
Data
Return
0010
0000
Fix
<
>
DN setting
Code
Data
Return
0010
0001
Fix
<
>
(DN) I.DN
Return
Continue?
No
Yes