– 23 –
Address is displayed here.
Address is displayed here.
6
Push the [
MENU] button to set the other
Code (DN) and Data. After “Continue?” is
displayed on the screen, push the
“
Yes” [ F1] button.
Indoor address change
Change “Code (DN)” from [0010] to [0013] with
the [
∧
] / [
∨
] button.
Change “Data” from [0003] to [0002] with the
[
∧
] / [
∨
] button.
7
Push the [
MENU] button to set the other
Code (DN) and Data. After “Continue?” is
displayed on the screen, push the
“
Yes” [ F1] button.
Group address change
Change “Code (DN)” from [0010] to [0014] with
the [
∧
] / [
∨
] button.
Change “Data” from [0001] to [0002] with the
[
∧
] / [
∨
] button.
8
Push the [
MENU] button to set the other
Code (DN) and Data. After “Continue?” is
displayed on the screen, push the
“
No” [ F2] button to finish the
setting operation. “ Setting” appears on
the screen for a while, then the screen
returns to the “Field setting menu” screen.
Pushing the “
No” [ F2] button
displays the unit selection screen when the
group control is used. Push the [
CANCEL]
button on the unit selection screen to finish the
setting operation. “ Setting” appears on the
screen for a while, then the screen returns to the
“Field setting menu” screen.
DN setting
Code
Data
3-3
Return
0013
0003
Fix
<
>
(DN) I.DN
DN setting
Code
Data
3-3
Return
Fix
<
>
0002
0013
(DN) I.DN
DN setting
Code
Data
3-3
Return
0014
0001
Fix
<
>
(DN) I.DN
DN setting
Code
Data
3-3
Return
Fix
<
>
0002
0014
(DN) I.DN
Yes
Yes
No
No
9
Test run
Before test run
• Before turning on the power supply, carry out the following procedure.
1) By using tester (500 VM
Ω
), check that resistance of 1 M
Ω
or more exists between the terminal block 1 to
3 and the earth (grounding).
If resistance of less than 1 M
Ω
is detected, do not run the unit.
2) Check the valve of the outdoor unit being opened fully.
• To protect the compressor at activation time, leave power-ON for 12 hours or more before operating.
Execute a test run
Operate the unit with the remote controller as usual.
For the procedure of the operation, refer to the attached Owner’s Manual.
A forced test run can be executed in the following procedure even if the operation stops by thermostat-OFF.
In order to prevent a serial operation, the forced test run is released after 60 minutes have passed and returns to
the usual operation.
CAUTION
• Do not use the forced test run for cases other than the test run because it applies an excessive load to the devices.
• Be careful of fan operation when the circuit breaker is turned on. If the refrigerant leak detection sensor detects the
refrigerant leak, a fan automatically rotates even while an air conditioner stops. Be careful not to be injured by the fan.
1
Push the [
MENU] button to display the
menu screen.
2
Push and hold the [
MENU] button and
the [
∨
] button at the same time to
display the “Field setting menu”.
Push and hold the buttons for more than 4
seconds.
3
Push the [
∧
] / [
∨
] button to select
“1. Test mode” on the “Field setting menu”
screen, then push the “
Set” [
F2] button.
Pushing the “
Yes” [ F1] button
sets the test mode and the screen returns to the
“Field setting menu” screen.
Push [
CANCEL] twice, the screen (2)
appears.
1.Test mode
2.Register service info.
3.Alarm history
4.Monitor function
5.Setting louver position
Field setting menu(1/2)
Return
Set
1.Test mode
2.Register service info.
3.Alarm history
4.Monitor function
5.Setting louver position
Field setting menu(1/2)
Return
Set
Set
Yes
Return
Test mode start.
No
Yes
Test mode
45-EN
46-EN
Summary of Contents for RAV-HM1101FT-TR