(Example of 2-lines wiring)
(Real line: Wiring, Broken line: Refrigerant pipe)
For the above example, perform setting by
connecting singly the wired remote controller
without remote controller inter-unit wire.
Group address
Individual : 0000
Header unit : 0001
Follower
unit
: 0002
In case of group control
Outdoor
Indoor
A B
A B
1 2 3
Indoor
A B
1 2 3
Indoor
A B
1 2 3
Indoor
A B
1 2 3
1 2 3
Outdoor
1 2 3
Remote controller
Line address
→
1
Indoor unit address
→
1
Group address
→
1
1
2
2
1
3
2
2
1
2
2
2
2
Indoor
A B
1 2 3
<Operation procedure>
1 2 3 4 5 6 7 8 9 10 11
END
1
3, 6, 9
END
11
2, 5, 8
4, 7, 10
SET
TIME
TIMER SET
TEST
FILTER
LL
RESET
TEMP.
CL
FAN
SAVE
A
A
SWING/FIX
VENT
MODE
ON / OFF
UNIT LOUVER
T
9-3. Address Setup (Manual Setting from Remote Controller)
In case that addresses of the indoor units will be
determined prior to piping work after wiring work
• Set an indoor unit per a remote controller.
• Turn on power supply.
1
Push
SET
+
CL
+
TEST
buttons
simultaneously for 4 seconds or more.
2
(Line address)
Using the temperature setup
/
buttons,
set
12
to the CODE No.
3
Using timer time / buttons, set the line address.
4
Push
SET
button.
(OK when display goes on.)
5
(Indoor unit address)
Using the temperature setup
/
buttons, set
13
13
13
13
13
to the CODE No.
6
Using timer time / buttons, set 1 to the line address.
7
Push
SET
button.
(OK when display goes on.)
8
(Group address)
Using the temperature setup
/
buttons, set
14
14
14
14
14
to the CODE No.
9
Using timer time / buttons, set
0000
0000
0000
0000
0000
to Individual,
0001
0001
0001
0001
0001
to Header unit, and
0002
0002
0002
0002
0002
to
Folloer unit.
10
Push
SET
button.
(OK when display goes on.)
11
Push
TEST
button.
Setup completes. (The status returns to the usual stop status.)
FILE NO. SVM-18039
- 81 -
Summary of Contents for RAV-RM1101BTP Series
Page 18: ...RM56 type RM80 type RM110 RM140 type FILE NO SVM 18039 18 ...
Page 19: ...3 WIRING DIAGRAM FILE NO SVM 18039 19 ...
Page 34: ...5 3 Indoor Print Circuit Board MCC 1631 FILE NO SVM 18039 34 ...
Page 89: ...11 EXPLODED VIEWS AND PARTS LIST 11 1 RAV RM561BTP E RAV RM561BTP TR FILE NO SVM 18039 89 ...
Page 91: ...11 2 RAV RM801BTP E RAV RM801BTP TR FILE NO SVM 18039 91 ...
Page 94: ...11 6 RAV RM1101BTP E RAV RM1101BTP TR RAV RM1401BTP E RAV RM1401BTP TR FILE NO SVM 18039 94 ...