Installation Manual
‒
14
‒
14-EN
Installation space
The indoor unit shall be installed so that its top surface comes at a height of 2.5 m or more.
Also it must be avoided to put anything on top of the indoor unit.
*1 Reserve space required to install the indoor unit and for service work.
Keep 65 mm or more for clearance between top plate of the indoor unit and the ceiling surface.
*2 Provide a space as shown for service clearance for the cross
fl
ow fan.
Installation place
• A place which provides the spaces around the indoor unit as shown in the above diagram.
• A place where there is no obstacle near the air inlet and outlet.
• A place that allows easy installation of the piping to the outdoor unit.
• A place which allows the front panel to be opened.
CAUTION
• Direct sunlight to the indoor unit’s wireless receiver should be avoided.
• The microprocessor in the indoor unit should not be too close to RF noise sources.
(For details, see the owner’s manual.)
Wireless remote controller
• A place where there are no obstacles such as a curtain that may block the signal from the indoor unit.
• Do not install the remote controller in a place exposed to direct sunlight or close to a heating source,
such as a stove.
• Keep the remote controller at least 1m apart from the nearest TV set or stereo equipment.
(This is necessary to prevent image disturb-bounces or noise interference.)
• The location of the remote controller should be determined as shown below.
Indoor unit
(Side view)
(Top view)
Indoor unit
Reception
range
Remote controller
Reception range
Remote controller
* : Axial distance
* 7 m
7 m
75°
45°
45°
5 m
5 m