– 59 –
Filter sign setting
According to the installation condition, the lighting time
of the filter sign (Notification of filter cleaning) can be
changed.
Follow to the basic operation procedure
(
1
2
3
4
5
6
).
• For the CODE No. in
3
, specify
[01]
.
• For the [Set data] in
4
, select the setup data of filter sign
lighting time from the following table.
To secure better effect of
heating
When it is difficult to obtain satisfactory heating due to
installation place of the indoor unit or structure of the room,
the detection temperature of heating can be raised. Also use
a circulator, etc. to circulate heat air near the ceiling.
Follow to the basic operation procedure
(
1
2
3
4
5
6
).
• For the CODE No. in Procedure
3
, specify
[06]
.
• For the set data in Procedure
4
, select the setup data of
shift value of detection temperature to be set up from the
table below.
Power saving mode setting
* When an outdoor unit RAV-SP***2AT / SM***3AT type or
earlier is used, the power level is fixed to 75 % regardless
of the value on the display.
1
Push
button for at least four seconds when
the air conditioner is not working.
flashes.
Indicates CODE No.
[C2.]
2
Select an indoor unit to be set by pushing
(left side of the button).
Each time you push the button, unit numbers change as
follows:
The fan of the selected unit runs.
3
Adjust the power save setting by pushing TIME
buttons.
Each push of the button changes the power level by 1%
within the range from 100 % to 50 %.
* The factory default is 75 %.
4
Determine the setting by pushing
button.
5
Push
button to complete the setting.
Setup data
Filter sign lighting time
0000
None
0001
150H
0002
2500H factory default)
0003
5000H
0004
10000H
Setup data
Detection temp shift value
0000
No shift
0001
+1°C
0002
+2°C (factory default)
0003
+3°C
0004
+4°C
0005
+5°C
0006
+6°C
Unit No.
1-1
Unit No.
1-2
Unit No.
1-3
Unit No.
1-4
Setting of power level in
power saving mode
Remote controller switch monitoring function
This function is available to call the service monitor mode from the remote controller during a test run to acquire temperatures
of sensors of the remote controller, indoor unit, and outdoor unit.
1
Push
and
buttons simultaneously for at least 4 seconds to call the service monitor mode.
The service monitor indicator lights up and the header indoor unit number is displayed first. CODE No.
is also
displayed.
2
Pushing TEMP.
buttons, select the number of sensor, etc. (CODE No.) to be monitored. (See the
following table.)
3
Pushing
(left side of the button), select an indoor unit to be monitored. The sensor temperatures of indoor
units and their outdoor unit in the control group are displayed.
4
Push
button to return to the normal display.
1
3
4
2
Indoor unit data
CODE No.
Data name
01
Room temperature (remote controller)
02
Indoor unit intake air temperature (TA)
03
Indoor unit heat exchanger (coil)
temperature (TCJ)
04
Indoor unit heat exchanger (coil)
temperature (TC)
F3
Indoor unit fan cumulative operating
hours (x1 h)
Outdoor unit data
CODE No.
Data name
60
Outdoor unit heat exchanger (coil)
temperature (TE)
61
Outside air temperature (TO)
62
Compressor discharge temperature
(TD)
63
Compressor suction temperature (TS)
65
Heatsink temperature (THS)
6A
Operating current (x1/10)
6D
Outdoor heat exchange (coil)
temperature (TL)
F1
Compressor cumulative operating
hours (x100h)
117-EN
118-EN
Summary of Contents for RAV-RM301SDT-E
Page 68: ...EB99819301 ...