Installation Manual
‒
18
‒
18-EN
q
In case of bottom right or bottom left piping
• After scribing slits of the front panel with a knife or a marking-off
pin, cut them with a pair of nippers or an equivalent tool.
Slit
q
Left-hand connection with piping
Bend the connecting pipe so that it is laid within 43 mm above the wall surface. If the connecting pipe
is laid exceeding 43 mm above the wall surface, the indoor unit may unstably be set on the wall. When
bending the connecting pipe, make sure to use a spring bender so as not to crush the pipe.
Bend the connecting pipe within a radius of 30 mm.
To connect the pipe after installation of the unit (
fi
gure)
570 mm
420 mm
43 mm
Liquid side
Gas side
(To the forefront of
fl
are)
Outward form of indoor unit
R 30 mm (Use polisin (polyethylene)
core or the like for bending pipe.)
Use the handle of screwdriver, etc.
80°
NOTE
If the pipe is bent incorrectly, the indoor unit may unstably be set on the wall.
After passing the connecting pipe through the pipe hole, connect the connecting pipe to the auxiliary
pipes and wrap the facing tape around them.