– 44 –
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
YES
Correct connection of connector.
Replace TCJ sensor.
Improve the power supply line.
Replace IPDU.
Check indoor P.C. board.
Defect
®
Replace
Is connection of TCJ sensor connector
(Indoor P.C. board CN102) normal?
Are characteristics of
TCJ sensor resistance value normal?
* Refer to Characteristics-2.
* Replace control P.C. board of SM56, SM80.
Is power voltage normal?
Check and correct circuit wires.
Correct connection of connector.
Check and correct reactor connection.
Are connections of
wiring/connector normal?
Are not “14” errors output
when an operation is performed by
removing 3P connector of compressor?
* Replace control P.C. board of SM56, SM80.
Is compressor normal?
Check rare short of compressor trouble.
Defect
®
Replace
Check IPDU.
Defect
®
Replace
[F01 error]/[0F error]
[P26 error]/[14 error]