– 69 –
No.
Part name
IPDU P.C.
board
Procedure
1) Perform the works in item
.
2) Take off screws of the inverter assembly,
and then classify the inverter assembly.
(M4 × 8, 3 pcs. hooks at two positions)
3) Disconnect connectors and lead wires
connected from IPDU P.C. board to other
parts.
1. Connector
CN04: Connection with cycle P.C. board
(3P: White) *(Note 1)
CN05: Connection with cycle P.C. board
(2P: White) *(Note 1)
CN06: Connection with cycle P.C. board
(5P: Red)
CN13: Connection with cycle P.C. board
(5P: Red) *(Note 1)
CN600: Heat sink sensor (2P: Black)
*(Note 1)
2. Lead wire
CN01: Connection with power supply
terminal block (Red)
CN02: Connection with power supply
terminal block (White)
CN03: Connection with power supply
terminal block (Black)
CN07: Earth wire (Black)
CN14: Connection with reactor (White)
CN15: Connection with reactor (White)
CN09: Connection with compressor
(Red)
CN10: Connection with compressor
(White)
CN11: Connection with compressor
(Black)
*Note 1)
Unlock lock of the housing part, and then
disconnect the connectors.
4) Remove lead wires of 3-phase rectifier.
(5 pcs)
5) Remove cover of the heat sink.
(M4 × 8, 3 pcs)
6) Take off screws (2 pcs) fixing the heat sink
with IGBT, remove claws (4 positions) of P.C.
board support, and then remove IPDU P.C.
board.
7) Install a new IPDU P.C. board.
Remarks
Screw
Hooks
Screws
IPDU P.C. board
3-phase rectifier
Gray
Orange
Black, Brown, Red
from rear side
Heat sink cover
Screw
Screw
Heat sink