3. REFRIGERATING CYCLE DIAGRAM
RAV-SM561AT-E
*
4 poles are provided to this compressor.
The compressor frequency (Hz) measured with a clamp meter is 2 times of revolutions (rps) of the compressor.
Standard
Cooling Overload
Low load
Standard
Heating Overload
Low load
Pressure
(MPa)
(kg/cm²G)
Pd
Ps
Pd
Ps
3.50
0.97
35.7
9.9
3.90
1.08
39.8
11.0
1.90
0.70
19.4
7.1
2.31
0.61
13.6
6.2
2.86
0.89
29.2
9.1
1.86
0.25
19.0
2.6
Pipe surface temperature (°C)
Discharge
Suction
Indoor heat Outdoor heat
exchanger
exchanger
(TD)
(TS)
(TC)
(TE)
85
14
12
48
93
26
17
54
48
7
5
30
87
5
40
1
86
17
47
11
69
–14
31
–15
Compressor
revolutions per
second (rps)
*
70
70
50
97
95
98
Indoor
fan
HIGH
HIGH
LOW
HIGH
HIGH
HIGH
Indoor/Outdoor
temp. conditions
(DB/WB) (°C)
Indoor
Outdoor
27/19
35/–
32/24
43/–
18/15.5
–5/–
20/–
7/6
28/–
24/18
15/–
–10/
(70%)
Indoor unit
Outdoor unit
Outer diameter of refrigerant pipe
Gas side ØA
Liquid side ØB
12.7mm
6.4mm
TCJ
sensor
Air heat exchanger
Strainer
TC sensor
Refrigerant pipe
at gas side
Ø12.7
Packed valve
Refrigerant pipe
at liquid side
Ø6.4
Packed valve
Packed valve
Outer dia. ØA
Packed valve
Outer dia. ØB
Max.
30m
Min.
5m
TS sensor
TD sensor
TO sensor
TE
sensor
Distributor
4-way valve
(STF-0108Z)
2-step muffler
Ø19.05 × 200L
Muffler
Ø19 × L160
Rotary compressor
(DA150A1F-20F)
Heat exchanger
Ø8 ripple, 2 rows,
14 steps
FP1.3, flat fin
PMV
(Pulse Motor Valve)
(CAM-B30YGTF-1)
Cooling
Heating