– 189 –
Fuse
Fuse holder
Thermostat
Thermostat
fixing plate
P-shape clamp
Power cord
Cord heater
* Transparent
L side
Close-end connector
insulation tape
Delete
Side cabinet (L)
No.
2-4
2-5
Photo / Explanatory diagram
Procedure
Rework the side cabinet (L) to remove part of it.
The area to be removed is indicated by the
shaded lines in the left figure.
After removing part of the side cabinet (L), deburr
the edges of the side cabinet (L).
Perform end process and bundling of each cable.
Using fixing screws (Self-tapping screw type-B
Ø3.5 × 6mm), fix the thermostat to the thermostat
fixing plate.
Perform end process for various lead cables and
connect them according to the wiring diagram.
Attach #250 Faston and UL-approved sleeves
each to the end of lead cables which are con-
nected to the thermostat.
Using insulation tape, apply protective measures
to the connected parts by the close-end connec-
tors.
Using P-shape clamp and the screws (Self-
tapping screw type-B Ø4 × 8mm), fix the power
cord to the thermostat fixing plate.
When the power cord size does not match with P-
shape clamp, procure the most appropriate one at
the local site.