– 63 –
+3.0
Ta (˚C)
E
D
C
B
F
G
A
HH
(HH)
H (HH)
H (HH)
L(H)
L(H)
L(H)
L(L)
+2.0
+2.5
+1.5
+0.5
Tsc
-0.5
+1.0
No.
3
4
5
Item
Room
temperature
control
Automatic
capacity control
(GA control)
Air speed
selection
Outline of specifications
1) Adjustment range Remote controller setup tem-
perature (°C)
Wired type
Wireless type
*
COOL/
DRY
18 to 29
18 to 30
Heating
operation
18 to 29
16 to 30
Auto
operation
18 to 29
17 to 27
*
: Only for 4-way air discharge cassette type and
Under ceiling type
2) Using the item code 06, the setup temperature in
heating operation can be compensated.
Setup data
Setup temp.
compensation
0
2
4
6
+0°C
+2°C
+4°C
+6°C
Setting at shipment
Setup data
2
1) Based on the difference between Ta and Ts, the
operation frequency is instructed to the outdoor
unit.
1) Operation with (HH), (H), (L), or [AUTO] mode is
performed by the command from the remote control-
ler.
2) When the air speed mode [AUTO] is selected, the air
speed varies by the difference between Ta and Ts.
<COOL>
• Controlling operation in case when thermo of remote
controller works is same as a case when thermo of
the body works.
• If the air speed has been changed once, it is not
changed for 3 minutes. However when the air volume
is exchanged, the air speed changes.
• When cooling operation has started, the air speed
selects a downward slope, that is, the high position.
• If the temperature is just on the difference boundary,
the air speed does not change.
• Mode in the parentheses indicates one in automatic
cooling operation.
Remarks
Shift of suction tempera-
ture in heating operation
HH > H > L > LL
Toshiba SDI / DI tuotteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
www.ilmalämpöpumput.com