EN
15
Engineering Data
1-2.
Outdoor Unit
* IEC standard
Model
Outdoor unit
RAV-SM2244AT8-E RAV-SM2804AT8-E RAV-SM2244AT7
RAV-SM2804AT7
Power supply
3 phase 380-415V 50Hz
(Power exclusive to outdoor is required.)
3 phase 380V 60Hz
(Power exclusive to outdoor is required.)
Compressor
Type
Hermetic compressor
Hermetic compressor
Motor
(kW)
3.75
3.75
3.75
3.75
Pole
4
4
4
4
Refrigerant charged
(kg)
5.9
5.9
5.9
5.9
Refrigerant control
Pulse motor valve
Pulse motor valve
Pipe
Max. total length
(m)
70
70
70
70
Min. length
(m)
7.5
7.5
7.5
7.5
Height
difference
Outdoor
lower
(m)
30
30
30
30
Outdoor
higher
(m)
30
30
30
30
Outer
dimension
Height
(mm)
1540
1540
1540
1540
Width
(mm)
900
900
900
900
Depth
(mm)
320
320
320
320
Appearance
Silky shade (Muncel 1Y8.5-0.5)
Silky shade (Muncel 1Y8.5-0.5)
Total weight
(kg)
134
134
134
134
Heat exchanger
Finned tube
Finned tube
Fan unit
Fan
Propeller fan
Propeller fan
Standard air flow
(m3/min)
133
133
133
133
Motor
(W)
100 + 100
100 + 100
100 + 100
100 + 100
Connecting pipe
(Outdoor unit
side)
Gas side
(mm)
19.1
19.1
19.1
19.1
Liquid side
(mm)
12.7
12.7
12.7
12.7
Sound pressure level
Cooling/
Heating
(dB/A)
56/57
57/58
56/57
57/58
Sound power level
Cooling/
Heating
(dB/A)
72/74
74/75
72/74
74/75
Outside air temperature, Cooling
(C)
46 to –15C
46 to –15C
Outside air temperature, Heating
(C)
15 to –20C
15 to –20C