– 30 –
Concealed Duct High Static Pressure
Installation Manual
EN
Procedure
6
If there is other indoor unit to be changed, repeat
procedure
2
to
5
to change the setup.
When the above setup has finished, push
to select the indoor unit No. before change of
setup, specify CODE No. [
12
], [
13
], [
14
] in order
with temp. setup
/
buttons, and then
check the changed contents.
Address change check Before change:
[
3-3-1
]
→
After change: [
2-2-2
]
Pushing
button clears the contents of which
setup was changed.
(In this case, procedure from
2
is repeated.)
Procedure
7
After check of the changed contents, push
button. (Setup is determined.) When pushing
button, the display disappears and the status
becomes the usual stop status. (When pushing
button the operation from the remote controller
is not accepted for approx. 1 minute.)
* If the operation from the remote controller is not
accepted even 1 minute or more passed after
pushing
button, it is considered that the
address setup is incorrect.
In this case, the automatic address must be
again set up.
Therefore repeat procedure of the setup
change from the Procedure
1
.
To recognize the position of the
corresponding indoor unit though the
indoor unit No. is known
Check the position during operation stop.
(Be sure to stop operation of the set.)
Procedure
1
Push simultaneously
+
buttons for 4
seconds or more.
After a while, the display part flashes and the
display appears as shown below.
In this time, the position can be checked because
fan of the indoor unit operate.
• For the group control, the indoor unit No. is
displayed as [
] and fans of all the indoor
units in the group control operate.
Check the displayed CODE No. is [
01
].
• When the CODE No. is other than [
01
], push
button to erase the display and repeat
procedure from the first step.
(After pushing
button, operation of the remote
controller is not accepted for approx. 1 minute.)
Procedure
2
In the group control, every pushing
button, the indoor unit No. in the group control is
displayed in order.
In this time, the position of the indoor unit can be
confirmed because only fan of the selected indoor
unit operate.
(For a group control, No. of the firstly displayed
indoor unit becomes the header unit.)
Procedure
3
After confirmation, push
button to return the
mode to the usual mode.
When pushing
button, the display disappears
and the status becomes the usual stop status.
(When pushing
button the operation from the
remote controller is not accepted for approx. 1
minute.)
Indoor unit No. before setup change is displayed.
2
1,3
1
(* Display changes according to
the model No. of indoor unit.)
30-EN