– 25 –
FILE NO. SVM-13072
RAV-SM1104AT
*
P
*
Pressure
Pipe surface temperature (°C)
*
Comp.
Hz
Fan
Temp
(MPa)
(kg/cm
2
G)
Pd
Ps
Pd
Ps
(TD)
(TS)
(TC)
(TE)
In
Out
Cooling
Standard
3.10 0.94 31.6 9.6
81
15
12
39
55
HIGH
27/19
35/-
Overload
3.60 1.13 36.7 11.5
78
16
18
54
50
HIGH
32/24
46/-
Low
load
2.03 0.82 20.7 8.4
55
11
8
4
30
LOW
18/15.5
-15/-
Heating
Standard
2.57 0.65 26.2 6.6
75
3
41
2
58
HIGH
20/-
7/6
Overload
3.13 1.12 31.9 11.4
76
19
52
16
30
LOW
30/-
24/18
Low
load
2.15 0.24 21.9 2.4
82
-19
34
-17
79
HIGH
15/-
-15/-
RAV-SM1404AT
*
P
*
Pressure
Pipe surface temperature (°C)
*
Comp.
Hz
Fan
Temp
(MPa)
(kg/cm
2
G)
Pd
Ps
Pd
Ps
(TD)
(TS)
(TC)
(TE)
In
Out
Cooling
Standard
3.37 0.85 34.4 8.7
89
13
11
40
70
HIGH
27/19
35/-
Overload
3.65 1.07 37.2 10.9
80
16
18
54
53
HIGH
32/24
46/-
Low
load
2.05 0.83 20.9 8.5
56
10
8
4
30
LOW
18/15.5
-15/-
Heating
Standard
2.79 0.63 28.4 6.4
79
3
45
2
67
HIGH
20/-
7/6
Overload
3.10 1.12 30.6 11.4
75
19
51
16
30
LOW
30/-
24/18
Low
load
2.30 0.23 23.5 2.3
86
-19
38
-17
99
HIGH
15/-
-15/-
*
4 poles are provided to this compressor.
The compressor frequency (Hz) measured with a clamp meter is 2 times of revolutions (rps) of the compressor.