8-2-3. Monitor Function of Remote Controller Switch
Calling of sensor temperature display
<Contents>
Each data of the remote controller, indoor unit and outdoor unit can be shown by calling the service
monitor mode from the remote controller.
<Procedure>
1
Push
TEST
+
CL
buttons simultaneously for 4 seconds to
call the service monitor mode.
The service monitor shows up, the master indoor unit No. is
displayed at first and then the temperature CODE No.
is
displayed.
2
Push temperature set
TEMP.
buttons and then change
the CODE No. of data to be monitored.
The CODE No. list is shown below.
Indoor unit data
CODE No.
01
02
03
04
∗
07
∗
F2
F3
∗
F8
Data name
Room temperature
(Remote controller)
Indoor suction temperature (TA)
Indoor heat exchanger (Coil)
temperature (TCJ)
Indoor heat exchanger (Coil)
temperature (TC)
Indoor fan revolution frequency
Indoor fan calculated operation time
Filter sign time
Indoor discharge temperature*1
(4-way only)
Unit
°C
°C
°C
°C
rpm
×100h
×1h
°C
Outdoor unit data
CODE No.
60
61
62
63
65
6A
∗
6D
∗
70
∗
72
∗
73
F1
Data name
Outdoor heat exchanger (Coil) temperature (TE)
Outside temperature (TO)
Compressor discharge temperature (TD)
Compressor suction temperature (TS)
Heat sink temperature (TH)
Operation current (× 1/10)
Outdoor heat exchanger (Coil) temperature (TL)
Compressor operation frequency
Outdoor fan revolution frequency (Lower)
Outdoor fan revolution frequency (Upper)
Compressor calculated operation time
Unit
°C
°C
°C
°C
°C
A
°C
rps
rpm
rpm
×100h
<RBC-AMT32E>
s
The CODE No. with
∗
marks in the above table are displayed only
on the indoor units of
4
series models and later.
(
4
series indoor units mean RAV-SM140
4
UT-E for example.).
s
The indoor discharge temperature of CODE No. [F8] is the esti-
mated value from TC or TCJ sensor.
Use this value to check discharge temperature at test run.
(A discharge temperature sensor is not provided to this model.)
s
The data value of each item is not the real time, but value delayed
by a few seconds to ten-odd seconds.
3
Push
UNIT LOUVER
button to select the indoor unit to be monitored.
Each data of the indoor unit and its outdoor units can be monitored.
4
Pushing
TEST
button to returns to the usual display.